Senin, 10 Oktober 2011

Cat. No. H083-E1-02A












E5AK
Digital Controller











USER MANUAL


Certain Terms and Conditions of Sale


1. Offer; Acceptance. These terms and conditions (these "Terms") are deemed
part of all catalogs, manuals or other documents, whether electronic or in writ-
ing, relating to the sale of goods or services (collectively, the "Goods") by
Omron Electronics LLC and its subsidiary companies ("Seller"). Seller hereby
objects to any terms or conditions proposed in Buyer's purchase order or other
documents which are inconsistent with, or in addition to, these Terms. Please
contact your Omron representative to confirm any additional terms for sales
from your Omron company.
2. Prices. All prices stated are current, subject to change without notice by
Seller. Buyer agrees to pay the price in effect at time of shipment.
3. Discounts. Cash discounts, if any, will apply only on the net amount of
invoices sent to Buyer after deducting transportation charges, taxes and
duties, and will be allowed only if (i) the invoice is paid according to Seller's
payment terms and (ii) Buyer has no past due amounts owing to Seller.
4. Orders. Seller will accept no order less than $200 net billing.
5. Governmental Approvals. Buyer shall be responsible for, and shall bear all
costs involved in, obtaining any government approvals required for the impor-
tation or sale of the Goods.
6. Taxes. All taxes, duties and other governmental charges (other than general
real property and income taxes), including any interest or penalties thereon,
imposed directly or indirectly on Seller or required to be collected directly or
indirectly by Seller for the manufacture, production, sale, delivery, importation,
consumption or use of the Goods sold hereunder (including customs duties
and sales, excise, use, turnover and license taxes) shall be charged to and
remitted by Buyer to Seller.
7. Financial. If the financial position of Buyer at any time becomes unsatisfactory
to Seller, Seller reserves the right to stop shipments or require satisfactory
security or payment in advance. If Buyer fails to make payment or otherwise
comply with these Terms or any related agreement, Seller may (without liability
and in addition to other remedies) cancel any unshipped portion of Goods sold
hereunder and stop any Goods in transit until Buyer pays all amounts, includ-
ing amounts payable hereunder, whether or not then due, which are owing to it
by Buyer. Buyer shall in any event remain liable for all unpaid accounts.
8. Cancellation; Etc. Orders are not subject to rescheduling or cancellation
unless Buyer indemnifies Seller fully against all costs or expenses arising in
connection therewith.
9. Force Majeure. Seller shall not be liable for any delay or failure in delivery
resulting from causes beyond its control, including earthquakes, fires, floods,
strikes or other labor disputes, shortage of labor or materials, accidents to
machinery, acts of sabotage, riots, delay in or lack of transportation or the
requirements of any government authority.
10. Shipping; Delivery. Unless otherwise expressly agreed in writing by Seller:
a. Shipments shall be by a carrier selected by Seller;
b. Such carrier shall act as the agent of Buyer and delivery to such carrier
shall constitute delivery to Buyer;
c. All sales and shipments of Goods shall be FOB shipping point (unless oth-
erwise stated in writing by Seller), at which point title to and all risk of loss of
the Goods shall pass from Seller to Buyer, provided that Seller shall retain a
security interest in the Goods until the full purchase price is paid by Buyer;
d. Delivery and shipping dates are estimates only.
e. Seller will package Goods as it deems proper for protection against normal
handling and extra charges apply to special conditions.
11. Claims. Any claim by Buyer against Seller for shortage or damage to the
Goods occurring before delivery to the carrier must be presented in writing to
Seller within 30 days of receipt of shipment and include the original transporta-
tion bill signed by the carrier noting that the carrier received the Goods from
Seller in the condition claimed.


12. Warranties. (a) Exclusive Warranty. Seller's exclusive warranty is that the
Goods will be free from defects in materials and workmanship for a period of
twelve months from the date of sale by Seller (or such other period expressed
in writing by Seller). Seller disclaims all other warranties, express or implied.
(b) Limitations. SELLER MAKES NO WARRANTY OR REPRESENTATION,
EXPRESS OR IMPLIED, ABOUT NON-INFRINGEMENT, MERCHANTABIL-
ITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE GOODS.
BUYER ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
GOODS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR
INTENDED USE. Seller further disclaims all warranties and responsibility of
any type for claims or expenses based on infringement by the Goods or other-
wise of any intellectual property right. (c) Buyer Remedy. Seller's sole obliga-
tion hereunder shall be to replace (in the form originally shipped with Buyer
responsible for labor charges for removal or replacement thereof) the non-
complying Good or, at Seller's election, to repay or credit Buyer an amount
equal to the purchase price of the Good; provided that in no event shall Seller
be responsible for warranty, repair, indemnity or any other claims or expenses
regarding the Goods unless Seller's analysis confirms that the Goods were
properly handled, stored, installed and maintained and not subject to contami-
nation, abuse, misuse or inappropriate modification. Return of any goods by
Buyer must be approved in writing by Seller before shipment. Seller shall not
be liable for the suitability or unsuitability or the results from the use of Goods
in combination with any electrical or electronic components, circuits, system
assemblies or any other materials or substances or environments. Any
advice, recommendations or information given orally or in writing, are not to be
construed as an amendment or addition to the above warranty.
13. Damage Limits; Etc. SELLER SHALL NOT BE LIABLE FOR SPECIAL, INDI-
RECT OR CONSEQUENTIAL DAMAGES, LOSS OF PROFITS OR PRODUC-
TION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE
GOODS, WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY,
NEGLIGENCE OR STRICT LIABILITY. Further, in no event shall liability of
Seller exceed the individual price of the Good on which liability is asserted.
14. Indemnities. Buyer shall indemnify and hold harmless Seller, its affiliates and
its employees from and against all liabilities, losses, claims, costs and
expenses (including attorney's fees and expenses) related to any claim, inves-
tigation, litigation or proceeding (whether or not Seller is a party) which arises
or is alleged to arise from Buyer's acts or omissions under these Terms or in
any way with respect to the Goods. Without limiting the foregoing, Buyer (at
its own expense) shall indemnify and hold harmless Seller and defend or settle
any action brought against Seller to the extent that it is based on a claim that
any Good made to Buyer specifications infringed intellectual property rights of
another party.
15. Property; Confidentiality. The intellectual property embodied in the Goods is
the exclusive property of Seller and its affiliates and Buyer shall not attempt to
duplicate it in any way without the written permission of Seller. Notwithstand-
ing any charges to Buyer for engineering or tooling, all engineering and tooling
shall remain the exclusive property of Seller. All information and materials
supplied by Seller to Buyer relating to the Goods are confidential and propri-
etary, and Buyer shall limit distribution thereof to its trusted employees and
strictly prevent disclosure to any third party.
16. Miscellaneous. (a) Waiver. No failure or delay by Seller in exercising any right
and no course of dealing between Buyer and Seller shall operate as a waiver
of rights by Seller. (b) Assignment. Buyer may not assign its rights hereunder
without Seller's written consent. (c) Amendment. These Terms constitute the
entire agreement between Buyer and Seller relating to the Goods, and no pro-
vision may be changed or waived unless in writing signed by the parties.
(d) Severability. If any provision hereof is rendered ineffective or invalid, such
provision shall not invalidate any other provision. (e) Setoff. Buyer shall have
no right to set off any amounts against the amount owing in respect of this
invoice. (f) As used herein, "including" means "including without limitation".



Certain Precautions on Specifications and Use


1. Suitability of Use. Seller shall not be responsible for conformity with any stan-
dards, codes or regulations which apply to the combination of the Good in the
Buyer's application or use of the Good. At Buyer's request, Seller will provide
applicable third party certification documents identifying ratings and limitations
of use which apply to the Good. This information by itself is not sufficient for a
complete determination of the suitability of the Good in combination with the
end product, machine, system, or other application or use. The following are
some examples of applications for which particular attention must be given.
This is not intended to be an exhaustive list of all possible uses of this Good,
nor is it intended to imply that the uses listed may be suitable for this Good:
(i) Outdoor use, uses involving potential chemical contamination or electrical
interference, or conditions or uses not described in this document.
(ii) Energy control systems, combustion systems, railroad systems, aviation
systems, medical equipment, amusement machines, vehicles, safety
equipment, and installations subject to separate industry or government
regulations.
(iii) Systems, machines and equipment that could present a risk to life or
property. Please know and observe all prohibitions of use applicable to
this Good.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS
RISK TO LIFE OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM
AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS, AND THAT
THE SELLER'S PRODUCT IS PROPERLY RATED AND INSTALLED FOR
THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.


2. Programmable Products. Seller shall not be responsible for the user's pro-
gramming of a programmable Good, or any consequence thereof.
3. Performance Data. Performance data given in this catalog is provided as a
guide for the user in determining suitability and does not constitute a warranty.
It may represent the result of Seller's test conditions, and the user must corre-
late it to actual application requirements. Actual performance is subject to the
Seller's Warranty and Limitations of Liability.
4. Change in Specifications. Product specifications and accessories may be
changed at any time based on improvements and other reasons. It is our prac-
tice to change part numbers when published ratings or features are changed,
or when significant construction changes are made. However, some specifica-
tions of the Good may be changed without any notice. When in doubt, special
part numbers may be assigned to fix or establish key specifications for your
application. Please consult with your Seller's representative at any time to con-
firm actual specifications of purchased Good.
5. Errors and Omissions. The information in this catalog has been carefully
checked and is believed to be accurate; however, no responsibility is assumed
for clerical, typographical or proofreading errors, or omissions.


E5AK






Preface


Thank you for your purchase of your E5AK, intelligent digital controller.
The E5AK allows the user to carry out the following:
• Select from many types of temperature and analog input (multiple input)
• Support position-proportional control (position-proportional type controllers only).
• Select output functions such as control output or alarm (output assignment)
• Use the HBA (heater burnout alarm) function (standard type controllers only).
• Use four setpoints (multi-SP function)
• Use remote SP input.
• Monitor the control loop by LBA (Loop Break Alarm)
• Use the communications function
• Calibrate input or transfer output
• It also features a watertight construction (NEMA4: equivalent to IP66)

This User’s Manual describes how to use the E5AK compact, high-function digital con-
troller.
Before using your E5AK, thoroughly read and understand this manual in order to
ensure correct use.





















About this manial

E OMRON, 1996
(1) Al rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted,
in any form, or by any means, mechanical, electronic, photocopying, recording, recording, or otherwise, without
the prior written permission of OMRON.
(2) No patent liability is assumed with respect to the use of the information contained herein.
(3) Moreover, because OMRON is constantly striving to improve its high-quality products, the information in this
manual is subject to change without notice. Every precaution has been taken in the preparation of this manual.
Nevertheless, OMRON assumes no responsibility for errors or omissions. Neither is any liability assumed for
damages resulting from the use of the information contained in this publication.


I

E5AK






Conventions Used in This Manual



J Meanings of Abbreviations
Sometimes the following abbreviations are used in parameter names, figures and in text
explanations. These abbreviations mean the following.

Abbreviation Term
PV Process value
SP Set point
RSP Remote set point
LSP Local set point
LBA Loop break alarm
HB Heater burnout
AT Auto-tuning
ST Self-tuning

J How to Read Display Symbols
The following tables show the correspondence between the symbols displayed on the displays
and alphabet characters.




A B C D E F G H I J K L M






N O P Q R S T U V W X Y Z

J “Reference” mark
This mark indicates that extra, useful information follows, such as supplementary explanations
and how to apply functions.
















II

E5AK








J Notice:
OMRON products are manufactured for use according to proper procedures by a qualified opera-
tor and only for the purposes described in this manual.
The following conventions are used to indicate and classify precautions in this manual. Always
heed the information provided with them. Failure to heed precautions can result in injury to
people or damage to the product.


! DANGER


! WARNING


! Caution


Indicates information that, if not heeded, is likely to result in loss of life
or serious injury.

Indicates information that, if not heeded, could possibly result in loss
of life or serious injury.

Indicates information that, if not heeded, could result in relatively seri-
ous or minor injury, damage to the product, or faulty operation.
















































III


E5AK








J How this Manual is Organized
Purpose











Title











Description

D Learning about the gen-
eral features of the E5AK


D Setting up the E5AK





D Basic E5AK operations

Chapter 1 Introduction




Chapter 2 Preparations






Chapter 3 Basic Operation
Chapter 5 Parameters

This chapter describes the fea-
tures of the E5AK, names of
parts, and typical functions.


This chapter describes the opera-
tions that you must carry out
(e.g. installation, wiring and
switch settings) before you can
use the E5AK.

These chapters describe how to
use the front panel keys and how
to view the display when setting
the parameters of the major func-
tions for the E5AK.


D Applied E5AK operations Chapter 4 Applied Operation
Chapter 5 Parameters


These chapters describe the
important functions of the E5AK
and how to use the parameters
for making full use of the E5AK.


D Using a Position-propor-
tional Type Controller


D Communications with a
host computer


D Calibration


Chapter 4 Applied Opera-
tion/4.1 Selecting the Control
Method


Chapter 6 Using the Commu-
nications Function



Chapter 7 Calibration


This chapter describes the func-
tions related specifically to posi-
tion-proportional type control-
lers.

This chapter mainly describes
the communications commands,
and gives program examples.


This chapter describes how the
user should calibrate the E5AK.



D Troubleshooting




















IV



Chapter 8 Troubleshooting This chapter describes what to do
if any problems occur.


E5AK





Pay Attention to the Following when Installing
this Controller

F If you remove the controller from its case, never touch nor apply shock to the electronic
parts inside.
F Do not cover the area around the E5AK. (Ensure sufficient space around the controller
to allow heat radiation.)
F Use a voltage (AC100-240V or AC/DC24V at 50 to 60 Hz). At power ON, the pre-
scribed voltage level must be attained within two seconds.
F When wiring input or output lines to your controller, keep the following points in mind
to reduce the influence from inductive noise:
• Allow adequate space between the high voltage/current power lines and the input/out-
put lines.
• Avoid parallel or common wiring with high voltage sources and power lines carrying
large currents.
• Using separating pipes, duct, and shielded line is also useful in protecting the controller,
and its lines form inductive noise.
F Allow as much space as possible between the controller and devices that generate a pow-
erful, high frequency (high-frequency welders, high-frequency sewing machines, and so
forth) or surge. These devices may cause malfunctions.
F If there is a large power-generating peripheral device and any of its lines, attach a surge
suppressor or noise filter to the device to stop the noise affecting the controller system.
In particular, motors, transformers, solenoids and magnetic coils have an inductance
component, and therefore can generate very strong noises.
F When mounting a noise filter, be sure to first check the filter’s voltage and current
capacity, then mount the filter as close as possible to the controller.
F Do not use the controller in places where icing, condensation, dust, corrosive gas (espe-
cially sulfurized gas or ammonia gas), shock, vibration, splashing liquid, or oil atmo-
sphere occur. Also, avoid places where the controller can be subjected to intense heat
radiation (like from a furnace) or sudden temperature changes.
F Ambient temperature must be kept between -10_C to 55_C. Ambient humidity must be
kept between 35%RH to 85%RH (with no icing or condensation). If the controller is
installed inside a control board, the ambient temperature must be kept under 55_C,
including the temperature around the controller. If the controller is subjected to heat
radiation, use a fan to cool the surface of the controller to under 55_C.
F Store the controller at an ambient temperature between -25_C to 65_C. The ambient
humidity must be between 35%RH to 85%RH (with no icing or condensation).
F Never place heavy objects on, or apply pressure to the controller that may cause it to
deform and deterioration during use or storage.
F Avoid using the controller in places near a radio, television set, or wireless installation.
These devices can cause radio disturbances which adversely affect the performance of
the controller.









V



Table of Contents


Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . I
Conventions Used in This Manual . . . . . . . . . . . . . . . II
Pay Attention to the Following when Installing
this Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . V


CHAPTER 1 INTRODUCTION


. . . . . . . . . . . . . . . . . . . . . . . . . . . 1- 1

This chapter introduces the E5AK. First-time users should read this chapter with-
out fail.
For details on how to use the control er and parameter settings, see Chapters 2
onwards.
1.1 Names of parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1- 2
1.2 Input and Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1- 4
1.3 Parameters and Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1- 7

1.4 About the Communications Function

. . . . . . . . . . . . . . . . . . . . . . . 1- 10

1.5 About Calibration

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1- 11


CHAPTER 2 PREPARATIONS


. . . . . . . . . . . . . . . . . . . . . . . . . . . 2- 1

This chapter describes the operations you should carry out before turning the
E5AK ON.
2.1 Setting up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2- 2
2.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2- 5
2.3 Wiring Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2- 8


CHAPTER 3 BASIC OPERATION


. . . . . . . . . . . . . . . . . . . . . . . . 3- 1

This chapter describes an actual example for understanding the basic operation
of the E5AK.
3.1 Convention Used in this Chapter . . . . . . . . . . . . . . . . . . . . . . . . . . . 3- 2

3.2 Setting Input Specifications

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3- 4

3.3 Setting Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3- 6
3.4 Setting Alarm Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3- 9
3.5 Protect Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3- 12
3.6 Starting and Stopping Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 3- 13
3.7 Adjusting Control Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3- 14

CHAPTER 4 APPLIED OPERATION . . . . . . . . . . . . . . . . . . . . . . 4- 1
This chapter describes each of the parameters required for making ful use of the
features of the E5AK. Read this chapter while referring to the parameter descrip-
tions in chapter 5.
4.1 Selecting the Control Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4- 2
4.2 Operating Condition Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . 4- 5

4.3 How to Use Event Input

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4- 8

4.4 How to Use the Remote SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4- 11
4.5 How to Use the Heater Burnout Alarm . . . . . . . . . . . . . . . . . . . . . . 4- 13
4.6 LBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4- 15
4.7 How to Use Transfer Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4- 17







CHAPTER 5 PARAMETERS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5- 1
This chapter describes the parameters of the E5AK. Use this chapter as a refer-
ence guide.

Protect Mode

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5- 3

Manual Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5- 5

Level 0 Mode
Level 1 Mode
Level 2 Mode
Setup Mode

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5- 6
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5- 10
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5- 18
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5- 25

Expansion Mode

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5- 32

Option Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5- 37
Calibration Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5- 46
CHAPTER 6 USING THE COMMUNICATIONS FUNCTION . . 6- 1
This chapter mainly describes communications with a host computer and com-
munications commands.
6.1 Outline of the Communications Function . . . . . . . . . . . . . . . . . . . . 6- 2

6.2 Preparing for Communications

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 6- 3

6.3 Command Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6- 5
6.4 Commands and Responses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6- 6
6.5 How to Read Communications Error Information . . . . . . . . . . . . . 6- 12

6.6 Program Example

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6- 14

CHAPTER 7 CALIBRATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7- 1

This chapter describes procedures for each calibration operation.
Read this chapter only when the control er must be calibrated.

7.1 Structure of Parameters

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7- 2

7.2 Calibrating Thermocouple . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7- 4

7.3 Calibrating Platinum Resistance Thermometer

. . . . . . . . . . . . . . 7- 7

7.4 Calibrating Current Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7- 9
7.5 Calibrating Voltage Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7- 10

7.6 Checking Indication Accuracy

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7- 12

CHAPTER 8 TROUBLESHOOTING

. . . . . . . . . . . . . . . . . . . . . . 8- 1

This chapter describes how to find out and remedy the cause if the E5AK does
not function properly.
8.1 Initial Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8- 2
8.2 How to Use the Error Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8- 3
8.3 How to Use Error Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8- 5
8.4 Checking Operation Restrictions . . . . . . . . . . . . . . . . . . . . . . . . . . . 8- 6
APPENDIX
SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . A- 2
ABOUT CURRENT TRANSFORMER (CT) . . . A- 5
CONTROL BLOCK DIAGRAM . . . . . . . . . . . . . . A- 6
SETTING LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . A- 8
MODEL LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A- 11
PARAMETER OPERATIONS LIST . . . . . . . . . . A- 12
FUZZY SELF-TUNING . . . . . . . . . . . . . . . . . . . . A- 14
X FORMAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A- 17
ASCII CODE LIST . . . . . . . . . . . . . . . . . . . . . . . . A- 20
INDEX
REVISION HISTORY


E5AK









1
CHAPTER 1




CHAPTER 1 INTRODUCTION

INTRODUCTION



This chapter introduces the E5AK. First-time users should read this
chapter without fail.
For details on how to use the controller and parameter settings, see
Chapters 2 onwards.









1.1 Names of parts









. . . . . . . . . . . . . . . . . . . . . . . . 1-2

Main parts
Front panel

. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
. . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2

About the displays

. . . . . . . . . . . . . . . . . . . . . 1-3

How to use keys

. . . . . . . . . . . . . . . . . . . . . . . 1-3

1.2 Input and Output . . . . . . . . . . . . . . . . . . . . . . 1-4
Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4
Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5
1.3 Parameters and Menus . . . . . . . . . . . . . . . . . 1-7

Parameter types

. . . . . . . . . . . . . . . . . . . . . . . 1-7

Selecting modes . . . . . . . . . . . . . . . . . . . . . . . . 1-8
Selecting parameters . . . . . . . . . . . . . . . . . . . 1-9
Fixing settings . . . . . . . . . . . . . . . . . . . . . . . . . 1-9

1.4 About the Communications Function

. . . . 1-10

1.5 About Calibration . . . . . . . . . . . . . . . . . . . . . . 1-11
















1--1


E5AK




CHAPTER 1 INTRODUCTION



1.1 Names of parts




J Main parts
Terminals
P 2-8

























Rear case




J Front panel

Bar graph



Operation indicators
OUT1 OUT2




























































RMT




























































RSP





















































PV





MANU

























































SV


SUB1




























































SUB2













































Front panel
This page






No.1 display



No.2 display

SUB1 SUB2
MANU
STOP
RMT
RST
AT

OUT1 OUT2

STOP

AT







E5AK









1--2



A/M key
A/M



Display key



Down key



Up key


E5AK








J About the displays

F No.1 display












Displays the process value or parameter symbols.




1.1 Names of parts


F No.2 display

F Operation indica-
tors

















F Bar graph





J How to use keys

F A/M key


Displays the set point, manipulated variable or parameter settings.

• OUT1 : Lits when the pulse output function assigned to “control
output 1” is ON.
• OUT2 : Lits when the pulse output function assigned to “control
output 2” is ON.
• SUB1 : Lits when the output function assigned to “auxiliary output
1” is ON.
• SUB2 : Lits when the output function assigned to “auxiliary
output 2” is ON.
• MANU : Lits in the manual operation mode.
• STOP : Lits when operation has stopped.
• RMT : Lits during remote operation.
• RSP : Lits during remote SP operation.
• AT : Flashes during auto-tuning.

On a standard type controller (E5AK-AA2), this bar graph indicates the
manipulated variable (heat) in 10% increments per single segment. On a
position-proportional type controller (E5AK-PRR2), this bar graph indi-
cates the valve opening in 10% increments per single segment.

The following describes basic key operations.

Each press of this key switches between the auto and manual operations.


F


key


The functions of this key change according to how long it is pressed. If the
key is pressed for less than one second, the parameters are switched. If the
key is pressed for one second or more, the menu display appears. In key
operations from here on, “press the key” refers to pressing the key for less
than one second.
For details on parameter switching and menu display items, see page 1-8.



F


key


Each press of the


key increments or advances the values or settings

on the No.2 display, while each press of the
the values or settings on the No.2 display.

key decrements or returns




Functions vary, for example, when the A/M key is held down simulta-
neously with the display key, or a key is held down continuously. For
details, see page 1-8. Also, chapters 3 and 4 describe examples using vari-
ous key combinations.

1--3


E5AK




CHAPTER 1 INTRODUCTION



1.2 Input and Output




Controller
Temperature input
Voltage input
Current input


CT input
Potentiometer



Remote SP input



Event input















Control output
(heat)
Control output
(cool)
Alarm 1

Alarm 2

Alarm 3

HBA

LBA

Error 1

Error 2

Error 3















Control output 1


Control output 2



Auxiliary output 1


Auxiliary output 2



Transfer output



J Input



The E5AK supports following inputs: temperature input, current input,
voltage input, CT input/Potentiometer, remote SP input and event input.


F Temperature input/Voltage input/Current input
• Only one of temperature input, voltage input and current input can be
selected and connected to the controller. The above figure shows temper-
ature input connected to the controller.
• The following input sensors can be connected for temperature input:
Thermocouple: K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer: JPt100, Pt100
• The following currents can be connected for current input:
4 to 20 mA, 0 to 20 mA
• The following voltages can be connected for voltage input:
1 to 5 VDC, 0 to 5 VDC, 0 to 10 VDC


F CT input/Poten-
tiometer



F Remote SP input








1--4


• Connect CT input when using the HBA (heater burnout alarm) function
on a standard type controller (E5AK-AA2).
• Connect the potentiometer when monitoring the valve opening on a
position-proportional type controller (E5AK-PRR2).

When the remote SP function is enabled, inputs within the range 4 to 20
mA are used as the remote SP.


E5AK








F Event input








J Output















F Output assign-
ments




1.1 Names of parts



When using event input, add on the input unit (E53-CKB).
You can select from the following five event inputs:
Multi-SP
Run/Stop
Remote/Local
Auto/Manual
SP mode


The E5AK supports the following five outputs.
Control output 1
Control output 2
Auxiliary output 1
Auxiliary output2
Transfer output
When using control outputs 1 and 2, set the output unit (sold separately).
Nine output units are available to suit the output circuit configuration.
When using transfer output, add on the communication unit (E53-AKF).
Note: The output functions of the E5AK do not operate for five seconds af-
ter the E5AK is turned ON.

The E5AK supports the following ten output functions.
Control output (heat)
Control output (cool)
Alarms 1 to 3
HBA
LBA
Error 1 (input error)
Error 2 (A/D converter error)
Error 3 (RSP input error)
Assign these output functions to control output 1, control output 2, auxil-
iary output1, and auxiliary output2.
However, note that as control output 1 is used as the open output and con-
trol output 2 is used as close output on a position-proportional type con-
troller (E5AK-PRR2), control outputs 1 and 2 cannot be used as assign-
ment destinations. Also, of the output functions, control output (heat),
control output (cool), HBA and LBA are disabled.
On a standard type controller, there are restrictions on how assignment
destinations (control output 1, control output2, auxiliary output1, and
auxiliary output2) can be used. For details, see 3.3 Setting Output Specifi-
cations.
In the example on the previous page, “control output (heat)” is assigned
to “control output 1”, “alarm 1” is assigned to “control output 2”, and
“alarm 2” is assigned to “auxiliary output 1”. Accordingly, the configura-
tion is such that heating control output is connected to control output 1,
and alarm output is connected to control output 2 and auxiliary output 1.







1--5

E5AK




CHAPTER 1 INTRODUCTION



Control outputs 1 and 2 are used depending on the differences in control
method as follows.


Control Method
Standard control

Heating and cooling
control
Position-proportional
control


Model
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
E5AK-AA2 AC100-240
E5AK-AA2 AC/DC24
E5AK-PRR2 AC100-240
E5AK-PRR2 AC/DC24


Control Output 1/
Control Output 2
Control output (heat) /
Alarm, etc.,
Control output (heat) /
Control output (cool)
Open/Close


F Transfer output


















































1--6


The E5AK supports the following six transfer outputs.
Set point
Set point during SP ramp
Process value
Heating side manipulated variable
Cooling side manipulated variable
Valve opening
However, note that heating/cooling side manipulated variables can be out-
put only standard type controllers, and valve opening can be output on
position-proportional type controllers
These transfer outputs can be output after being scaled. Setting of an
upper limit value smaller than the lower limit value is allowed, so reverse
scaling can also be carried out.


E5AK








1.3 Parameters and Menus




1.1 Names of parts





J Parameter types
















F Protect mode



F Manual mode


F Level 0 mode




F Level 1 mode



F Level 2 mode




F Setup mode



F Expansion mode




F Option mode





E5AK parameters are distributed between the following nine modes.
Protect mode
Manual mode
Level 0 mode
Level 1 mode
Level 2 mode
Setup mode
Expansion mode
Option mode
Calibration mode
The settings of parameters in each of seven modes (excluding the protect
mode and manual mode) can be checked and modified by selection on the
menu display.

This mode is used to limit use of the menu and A/M keys. The protect func-
tion is for preventing unwanted modification of parameters and switching
between the auto and manual operation.

In this mode, the controller can be switched manual operation. The
manipulated variable can be manipulated manually only in this mode.

Set the controller to this mode during normal operation. In this mode, you
may change the set point during operation, and stop and start operation.
You can also monitor (not change) the process value, ramp SP and manip-
ulated variable.

This is the main mode for adjusting control. In this mode, you can execute
AT (auto-tuning), and set alarm values, the control period and PID param-
eters.

This is the auxiliary mode for adjusting control. In this mode, you can set
the parameters for limiting the manipulated variable, switch between the
remote and local modes, switch between the SP modes, and set the loop
break alarm (LBA), alarm hysteresis and the digital filter value of inputs.

This is the mode for setting the basic specifications. In this mode, you can
set parameters that must be checked or set before operation such as the
input type, scaling, output assignments and direct/reverse operation.

This is the mode for setting expanded functions. In this mode, you can set
ST (self-tuning), SP setting limiter, selection of advanced PID or ON/OFF
control, specification of the standby sequence resetting method, time for
automatic return to the monitoring display.

This is the mode for setting option functions. You can select this mode only
when the option unit is set in the controller. In this mode, you can set the
communications conditions, transfer output and event input parameters

1--7


E5AK




CHAPTER 1 INTRODUCTION



to match the type of option unit set in the controller. Heater burnout latch
function, position-proportional travel time and remote SP scaling param-
eters are also located in this mode.

F Calibration mode This mode is provided so that the user can calibrate inputs and transfer
output.
When calibrating input, the selected input type is calibrated. Whereas,
transfer output can be calibrated only when the communications unit
(E53-AKF) is set in the controller.

J Selecting modes The following diagram shows the order in which modes are selected.
Power ON
A/M
1 second min. 1 second min.
Level 0 mode Manual mode


1 second min.


1 second min.


1 second min.



Level 1 mode


Level 2 mode


Setup mode






A/M +
1 second min.


A/M
1 second min.


A/M +
1 second min.


1 second min.


1 second min.


1 second min.



Expansion mode


Option mode


Calibration mode

Protect mode

A/M +
1 second min.



F Menu display



• To select the menu display in any of the above modes (excluding the pro-
tect mode and manual mode), press the key for 1 second minimum.

If you select the desired mode using the

or

keys and press the

key, the top parameter in the specified mode is displayed.
• When you have selected the menu display, the previous mode is selected.
For example, if you selected the menu display while in the level 0 mode,

the No.2 display changes to [

] as shown on the left.





F Level 0 to 2
modes









1--8

• Protected modes cannot be selected. Also, the menu display does not
appear when modes are protected up to the level 1 mode.

• If you select [ ] [ ] or [ ] in the menu display, the level 0,
level 1 and level 2 modes, respectively, are selected.
• These modes are selected with control still continuing.


E5AK




1.1 Names of parts




F Setup mode




• If you select [




] [




] [




] or [




] in the menu display, the

F Expansion mode
F Option mode
F Calibration mode



F Protect mode



F Manual mode

setup, expansion, option and calibration modes, respectively, are
selected.
• When these modes are selected, the control is reset. So, control outputs
and auxiliary output are turned OFF. When another mode is selected
while in these modes, reset is canceled.

• To set the controller to the protect mode or to return to the level 0 mode
from the protect mode, press the A/M key and key for 1 second mini-
mun simultaneously.

• To set the controller to the manual mode, press the A/M key for 1 second
minimun in the level 0 to 2 mode. To return to the level 0 mode from the
manual mode, press the A/M key for 1 second minimum.


J Selecting
parameters


• When not in the manual mode, each press of the
parameter.


key switches the

• If you press the

key when at the final parameter, the display returns

to the first parameter.
Parameter Parameter
1 2



Parameter
3



Parameter
n





J Fixing settings





• When you have changed a parameter setting, specify the parameter
using the or keys, and either leave the setting for at least two
seconds or press the key. This fixes the setting.
• When another mode is selected, the content of the parameters before the
mode was selected is fixed.
• When turning the power OFF, you must first fix the settings and param-
eter contents (by pressing the key or selecting another mode). The
settings and parameter contents are sometimes not changed by merely

pressing the

or

keys.

























1--9


E5AK




CHAPTER 1 INTRODUCTION



1.4 About the Communications Function



The E5AK can be provided with a communications function that allows
you to check and set controller parameters from a host computer. If the
communications function is required, add on the communications unit.
For details on the communications function, refer to Chapter 6.

F RS-232C When using the communications function on the RS-232C interface, add
on the communications unit (E53-AK01).

F RS-422 When using the communications function on the RS-422 interface, add on
the communications unit (E53-AK02).

F RS-485 When using the communications function on the RS-485 interface, add on
the communications unit (E53-AK03).












































1--10

E5AK








1.5 About Calibration




1.1 Names of parts

















F Calibrating
inputs








F Calibrating trans-
fer output

F Registering cal-
ibration data




The E5AK controller is calibrated before shipment from the factory. So,
the user need not calibrate the E5AK controller during regular use.

However, if the E5AK controller must be calibrated by the user, use the
parameters provided for user to calibrate temperature input, analog input
(voltage, current) and transfer output.
Also, note that calibration data is updated to the latest value each time the
E5AK controller is calibrated. Calibration data set before shipment from
the factory cannot be returned to after calibration by the user.

The input type selected in the parameter is the item to be calibrated. The
E5AK is provided with the following four calibration parameters.
• Thermocouple
• Platinum resistance thermometer
• Current input
• Voltage input
Two parameters are provided for thermocouple and voltage input.

Transfer output can be calibrated when the communications unit
(E53-AKF) is added on.

When calibrating each item, the calibration data is temporarily regis-
tered. This data can be registered as final calibration data only when all
items have been newly calibrated. So, all items must be temporarily regis-
tered when calibrating the E5AK controller.
When registering data, information regarding whether or not calibration
has been carried out is also registered.

To calibrate these items, the user must prepare separate measuring
devices and equipment. For details on handling these measuring devices
and equipment, refer to the respective manuals.

For details, see Chapter 7 Calibration.

















1--11


E5AK




CHAPTER 1 INTRODUCTION






































































1--12

E5AK









2
CHAPTER 2




CHAPTER 2 PREPARATIONS

PREPARATIONS



This chapter describes the operations you should carry out before turn-
ing the E5AK ON.











2.1 Setting up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
Draw-out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2

Setting up the output unit

. . . . . . . . . . . . . . 2-3

Setting up the option unit . . . . . . . . . . . . . . . 2-4
2.2 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Panel cutout . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5

Mounting

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6

2.3 Wiring Terminals . . . . . . . . . . . . . . . . . . . . . . 2-8

Terminal arrangement

. . . . . . . . . . . . . . . . . 2-8

Precautions when wiring

. . . . . . . . . . . . . . . 2-8

Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8






















2--1


E5AK




CHAPTER 2 PREPARATIONS



2.1 Setting up



• On a standard type controller, set up the output units for control outputs
1 and 2 before mounting the controller.
• On a position-proportional type controller, the relay output unit is
already set. So, this setup operation unnecessary. (Do not replace with
other output units.)
• When setting up the output units, draw out the internal mechanism
from the housing and insert the output units into the sockets for control
outputs 1 and 2.
J Draw-out When drawing out the internal mechanism from the housing, prepare a
phillips screwdriver matched to the size of the screw on the lower part of
the front panel.
(1) Press down on the hook on the top of the front panel and turn the phil-
lips screwdriver to the left to loosen the screw on the lower part of the
front panel.
































(2) Draw out the internal mechanism towards you holding both sides of
the front panel.

Fixing Screw for Tighten this screw by a torque of 0.3 to 0.5 N×m, or approx. 3 to 5 kgf×cm.
Front Panel



2--2

E5AK








J Setting up the output unit




2.1 Setting up


F Before setup


F Procedure


• Check the type of the output unit you are about to set up.
• For details on types of output unit and main specifications, see page 2-9.

(1) Check the positions of the sockets you are about to insert the output
units into as shown in the following diagram.













OUT1
OUT2






Bracket


(2) Insert the output unit for control output 1 into the socket “OUT1”
and the output unit for control output 2 into the socket “OUT2”.
(3) Fasten the output units with the bracket (accessory).


























2--3


E5AK




CHAPTER 2 PREPARATIONS



J Setting up the option unit

F Before setup • Check the type of the option unit you are about to set up.
• For details on types of option unit and main specifications, see Appendix,
Model List (page A-11) and Appendix, Option Unit Ratings and Charac-
teristics (page A-4).
• For details on the relationship between units and terminals, see page
2-8.

F Procedure (1) Remove the power board and option boards in the order shown in the
following diagram.














2

1





(2) Insert the option units into the sockets for options 1 to 3. The follow-
ing diagram shows the relationship between option units and mount-
ing positions.
Option 1
E53- AKB: Event inputs 1/2
E53- AK01: RS- 232C
E53- AK02: RS- 422
Option 2 E53- AK03: RS- 485
E53- AKF: Transfer output
Option 3
E53- AKB: Event inputs 3/4














(3) Mount the option boards and the power board in the order shown.

2--4

E5AK








2.2 Installation




J Dimensions
96j



PV



SV


RMT RSP MANU SUB1
OUT1 OUT2 STOP AT










J Panel cutout

Unit (mm)










120 mm min
92 +0.8
0





























SUB2






E5AK

















13.5
























110 mm min

















100




2.2 Installation





















j





92 +0.8
0

• Recommended panel thickness is 1 to 8
mm.
• Maintain the specified vertical and hori-
zontal mounting space between each con-
troller.
Controllers must not be closely mounted
vertically or horizontally.









2--5


E5AK




CHAPTER 2 PREPARATIONS



J Mounting (1) Insert the E5AK controller into the mounting hole in the panel.
(2) Fit the mounting bracket (accessory) into the fixing slots on the top
and bottom of the rear case.
























(3) Tighten the mounting bracket screws alternately a little at a time
until the ratchet start to slide.



































2--6

E5AK








F Setting up the terminal covers




2.2 Installation

• Fasten the terminal covers (E53-COV0809) to protect terminals.
• E5AK-VV2-500 controller is provided with terminal covers.
• Use E53-COV09 for terminals 1 to 10, and E53-COV08 for terminals 11
to 33.
• Fasten the terminal covers as follows by using the snap pins.














E5AK






E53-COV0809
• To remove the terminal covers, pull the edges of the snap pins.

































2--7


E5AK




CHAPTER 2 PREPARATIONS



2.3 Wiring Terminals




J Terminal arrangement
AC100-240V~
(AC/DC24V )
SOURCE

OUT1

OUT2

SUB1

SUB2



















10
9
8
7
6
5
4
3
2
1



















TRSF





EV3/4



RSP



















30
29
28
27
26
25
24
23
22
21



















31 32










33



















20
19
18
17
16
15
14
13
12
11

















EV1/2
RS232C
RS422
RS485


CT
PTMR

TC
Pt
I
V






J Precautions
when wiring















J Wiring

F Power supply
10 30 31 32 20
9 29 19


TRSF : Transfer output
EV1 to 4 : Event inputs
PTMR : Potentiometer

• Use ducts to separate input leads and power lines in order to protect the
controller and its lines from external noise.
• We recommend using solderless terminals when wiring the controller.
• Tighten the terminal screws using a torque no greater than 0.78 N•m,
or 8 kgf•cm max. Take care not to tighten the terminal screws too tightly.
• Use the following type of solderless terminals for M3.5 screws.

7.2mm max.



7.2mm max.


In the following wiring diagrams, the left side of the terminal Nos. indi-
cates the inside of the controller
• Input power to terminal Nos. 9 and 10. Power specifications are as follows:
AC100-240V , 50/60Hz, 16VA
(AC/DC24V , 50/60Hz, 12VA, 8W)














2--8

8
7
6
5
4
3
2
1

28
27
26
25
24
23
22
21 33

18
17
16
15
14
13
12
11


E5AK








F Sensor input
10 30
31 32










20




2.3 Wiring Terminals



• Connect the sensor input to terminal Nos. 11 to 14 and 33 as follows
according to the input type.

9 29
8 28
7 27

19
18
17

14 14 14
13 13 13
-

+
V

14
13



-

6 26
5 25
4 24

16
15
14

12
11
33


+

12
11
33

12
11
33

-

12
11
33

mA
+

3 23
2 22
1 21 33

13
12
11

Thermocouple Platinum
resistance
thermometer

Voltage input Current input


F Control output
10 30




20


• Terminal Nos. 7 and 8 are for control output 1 (OUT1), and terminal Nos.
5 and 6 are for control output 2 (OUT2). The following diagrams show the

9
8
7
6
5
4
3
2

29
28
27
26
25
24
23
22

31 32

19
18
17
16
15
14
13
12

available output units and their internal equalizing circuits.

1

21 33

11








• With E53-VVV output units, about 2 V is output for one second after the
power is interrupted.
• The following table shows the specifications for each output unit.

Model
E53-R
E53-S

Output Type
Relay
SSR


250 VAC, 5 A
75 to 250 VAC, 1 A

Specifications

E53-Q
E53-Q3
E53-Q4
E53-C3
E53-C3D
E53-V34
E53-V35

Voltage (NPN)
Voltage (NPN)
Voltage (PNP)
4 to 20 mA
0 to 20 mA
0 to 10 V
0 to 5 V

NPN : 12 VDC, 40 mA (with short-circuit protection)
NPN : 24 VDC, 20 mA (with short-circuit protection)
PNP : 24 VDC, 20 mA (with short-circuit protection)
4 to 20 mA, Permissible load impedance: 600 W max., Resolution: Approx. 2600
0 to 20 mA, Permissible load impedance: 600 W max., Resolution: Approx. 2600
0 to 10 VDC, Permissible load impedance: 1 kW min., Resolution: Approx. 2600
0 to 5 VDC, Permissible load impedance: 1 kW min., Resolution: Approx. 2600
With E5AK-PRR2 controllers, relay output (250 VAC, 1 A) is fixed.When
replacing the output unit, use the E53-R. The following diagrams show the
relationship between terminals and open/close relay settings.
8 6

7 5
Open Close








2--9


E5AK




CHAPTER 2 PREPARATIONS



F Auxiliary output • Terminal Nos.3 and 4 are for auxiliary output 1 (SUB1) and terminal

10
9
8
7
6
5
4
3
2

30
29
28
27
26
25
24
23
22

31 32

20
19
18
17
16
15
14
13
12

Nos.1 and 2 are for auxiliary output 2 (SUB2).
• The internal equalizing circuits for the auxiliary outputs are as follows:
4 2

3 1
Auxiliary Auxiliary
output 1 output 2
• Output specifications are as follows:

1

21 33

11

SPST-NO, AC250V, 3A


F CT input/
Potentiometer
10 30 31 32 20
9 29 19


• When using the HBA function on the E5AK-AA2 controller, connect CT
input (CT) to terminal Nos.15 to 17. When monitoring the valve opening
on the E5AK-PRR2 controller, connect the potentiometer (PTMR) to
terminal Nos.15 to 17. Connect each of these inputs as follows:

8
7
6

28
27
26

18
17
16

17
16


CT

17
16

O
W

5
4
3

25
24
23

15
14
13

15
CT input

15C
Potentiometer

2
1

22
21 33

12
11

• For details on CT inputs, see Appendix, About Current transformer.
• For details on the potentiometer, see the Instruction Manual for the
valve connected to the controller. The variable resistance range is 100
W to 2.5 kW


F Remote SP input
10 30 31 32 20
9 29 19


• Connect an input (RSP) to be used as the remote SP to terminal Nos.21
and 22.
• Only 4 to 20 mA inputs can be connected. Connect the input as follows:

8
7
6
5
4
3
2
1

28
27
26
25
24
23
22
21 33

18
17
16
15
14
13
12
11

22

21

+


-



4 to 20 mA





About the power
blocks





The E5AK has independent power supplies for
each of the terminal blocks shown on the right.










B





A







10
9
8
7
6
5
4





B





C







30 31 32 20
29 19
28 18
27 17
26 16
25 15
24 14





C








2--10

E




F

3
2
1

23
22
21 33

13
12
11




D


E5AK








F Event input




2.3 Wiring Terminals



• Connect event inputs 1 and 2 (EV1/2) to terminal Nos.18 to 20, and event

10
9
8
7
6

30
29
28
27
26

31 32

20
19
18
17
16

events 3 and 4 (EV3/4) to terminal Nos.24 to 26. However, note that ter-
minal Nos.18 to 20 cannot be used on controllers having a communica-
tions function.
• Connect the event inputs as follows:
+ +

5
4

25
24

15
14

EV1
EV2

20
19

+

EV3
EV4

26
25

+

3

23

13

COM 18

-

COM 24

-

2
1

22
21 33

12
11

Event input 1 and 2 Event input 3 and 4
Terminals 18 and 24 (COM) are connected internally.
• Use event inputs under the following conditions:
Contact input ON: 1 kW max., OFF: 100 kW min.
No-contact input ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.

• Polarities during no-contact input are as follows:
+ +

EV1
EV2

20
19

+

EV3
EV4

26
25

+

COM 18 -

COM 24


-

Event input 1 and 2

Event input 3 and 4


F Transfer output


• Connect transfer output (TRSF) to terminal Nos. 29 and 30.
• The internal equalizing circuit for transfer output is as follows:
+

4 to 20mA

30

29



-

L







F Communications

• Transfer output specifications are as follows:4 to 20 mA,
Permissible load impedance: 600 W max.,
Resolution: Approx. 2600

• Terminal Nos.18 to 20, 31 and 32 can be used only on controllers having
a communications units (E53-AK01/02/03).
• For details on wiring, see Chapter 6, Using the Communications Func-
tion.
















2--11


E5AK




CHAPTER 2 PREPARATIONS






































































2--12

E5AK









3
CHAPTER 3




CHAPTER 3 BASIC OPERATION

BASIC OPERATION



This chapter describes an actual example for understanding the basic
operation of the E5AK.











3.1 Convention Used in this Chapter . . . . . . . . 3-2
3.2 Setting Input Specifications . . . . . . . . . . . . . 3-4
Input type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4

3.3 Setting Output Specifications

. . . . . . . . . . . 3-6

Output assignments . . . . . . . . . . . . . . . . . . . . 3-6

Direct/reverse operation

. . . . . . . . . . . . . . . . 3-7

Control period . . . . . . . . . . . . . . . . . . . . . . . . . 3-7

3.4 Setting Alarm Type

. . . . . . . . . . . . . . . . . . . . 3-9

Alarm type . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Alarm value . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
Alarm hysteresis . . . . . . . . . . . . . . . . . . . . . . . 3-10
Close in alarm/open in alarm . . . . . . . . . . . . 3-10
3.5 Protect Mode . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12
A/M key protect . . . . . . . . . . . . . . . . . . . . . . . . 3-12

3.6 Starting and Stopping Operation

. . . . . . . . 3-13

3.7 Adjusting Control Operation . . . . . . . . . . . . 3-14

Changing the set point

. . . . . . . . . . . . . . . . . 3-14

Manual operation . . . . . . . . . . . . . . . . . . . . . . 3-14

Auto-tuning (A.T.)

. . . . . . . . . . . . . . . . . . . . . 3-16






3--1


E5AK




CHAPTER 3 BASIC OPERATION



3.1 Convention Used in this Chapter



This chapter describes basic E5AK operations such as how to set up
parameters, start and stop operation, and adjusting control operation.
For more complex control examples, refer to Chapter 4 Applied Operation
and Chapter 5 Parameters.

F Basic Operation The following diagram shows the basic operation flow.






















































3--2

Flow

Power ON


Setting input specifications

Setting output specifications

Setting alarm output

Protecting parameters



Start

Adjustment

Stop


Power OFF




Setup












Operation


E5AK








F Setup




3.1 Convention Used in this Chapter



This description assumes that the controller is operated under the follow-
ing conditions.
• A humidity sensor of output 4 to 20 mA is connected to the controller.
The measuring range of the humidity sensor is set to 10 to 95%.
• A humidifier is controlled by pulse output to maintain humidity at a
constant 60%.
• An alarm is output when the humidity exceeds the upper limit value
(70%) or lower limit value (50%).
• Output unit: relay type (E53-R) for OUT1.

Humidity sensor
Humidifier



Control target
AC100-240V~
(AC/DC24V )










Alarm 1
(deviation


SOURCE

OUT1




SUB1

10
9
8
7
6
5
4
3

30
29
28
27
26
25
24
23

31 32

20
19
18
17
16
15
14
13











-

upper-and lower-limit)

2
1
E5AK-AA2
(OUT1 : E53-R)

22
21



+

33

12
11


4 to 20mA

































3--3


E5AK




CHAPTER 3 BASIC OPERATION



3.2 Setting Input Specifications



J Input type • Set the type No. (0 to 21) in the “input type” parameter. The factory set-
ting is “2: K1 (thermocouple).”
• For details on input types and setting ranges, see page 5-26.

J Scaling • When the voltage input and current input are selected, scaling matched
to the control is required.
• The “scaling upper limit”, “scaling lower limit” and “decimal point”
parameters (setup mode) are use for scaling.
• The “scaling upper limit” parameter sets the physical quantity to be
expressed by the upper limit value of input, and the “scaling lower limit”
parameter sets the physical quantity to be expressed by the lower limit
value of input. The “decimal point” parameter sets the number of digits
past the decimal point.
• The following figure shows scaling example of 4 to 20 mA input. After
scaling, the humidity can be directly read. In this case, the “decimal
point” parameter is set to “1”.
Readout (humidity)


Scaling upper limit
value (95.0%)

Scaling lower limit
value (10.0%)

Input (4 to 20 mA)

0

100%FS

F Input shift

• When temperature input is selected, scaling is not required. This is
because input is treated as the “temperature” as it is matched to the
input type. However, note that the upper and lower limit values of the
sensor can be shifted. For example, if both the upper and lower limit val-
ues are shifted by 1.2_C, the process value (before shift) is regarded as
201.2_C after shift when input is 200_C before shift.
• To set input shift, set shift values in the “input shift upper limit” and
“input shift lower limit” parameters (level 2 mode).
Temperature
Input shift upper limit value
Upper limit value
After shift
Before shift
Input shift lower
Lower limit value limit value

0


100

Input (%FS)


About the tempera-


To switch the temperature unit from “_C” to “_F” for temperature unit, switch the





3--4

ture unit

setting of the _C/_F selection” parameter to [

] from [

].


E5AK









Setting Example











1 second min.




3.2 Setting Input Specifications



In this example, let’s set the parameters as follows:
“input type” = “17 (4 to 20 mA)”
“scaling upper limit value” = “950”
“scaling lower limit value” = “100”
“decimal point” = “1”


(1) Select the menu display, and select [ ] (setup mode) using the
or keys. For details on selecting the menu display, see page
1-8.
(2) Press the key to enter the setup mode. The top parameter in the
setup mode [ ] “input type” is displayed. The parameter default
is “2”.
(3) Press the key until the display indicates “17”.
(4) Press the key to fix the set value. The display changes to [ ]
(“scaling upper limit value” parameter). The parameter default is
“100”.
(5) Press the key until the display indicates “950”.
(6) Press the key to fix the set value. The display changes to [ ]
(“scaling lower limit value” parameter). The parameter default is “0”.
(7) Press the key until the display indicates “100”.
(8) Press the key to fix the set value. The display changes to [ ]
(“decimal point” parameter). The parameter default is “0”.
(9) Press the key until the display indicates “1”.

































3--5

E5AK




CHAPTER 3 BASIC OPERATION



3.3 Setting Output Specifications



Some output specifications are different according to controller type,
standard or position-proportional. The following table summarizes which
output-related parameter settings are supported.


Parameter

Control output 1 assignment
Control output 2 assignment
Auxiliary output 1 assignment
Auxiliary output 2 assignment
Direct/reverse operation
Control period (heat)
Control period (cool)

Standard
Type
F
F
F
F
F
F
F

Position-
proportional
Type


F
F
F

(F Indicates that an output specification is supported.)
J Output assignments
Output assignments are described according to controller type.

F Standard type

• Ten output are supported :
control output (heat)
control output (cool)
alarm outputs 1 to 3
HBA
LBA, and
error 1 (input error)
error 2 (A/D converter error)
error 3 (RSP input error).
These functions are assigned to control outputs 1 and 2, and auxiliary
output 1 and 2.
• Restrictions on assignment destination are placed on some of the out-
puts. The following table shows where outputs may be assigned to.
Assignment Control Output Auxiliary Output
Destination

Output Function

Destination

1

2

1

2

Control output (heat)
Control output (cool)
Alarm 1
Alarm 2
Alarm 3
HBA
LBA
Error 1; Input error
Error 2; A/D converter error
Error 3; RSP input error

F
F
F
F
F
F
F

F
F
F
F
F
F
F




F
F
F
F
F
F
F
F




F
F
F
F
F
F
F
F











3--6

With control output (cool), the conditions for switching from standard control
to heating and cooling control are reached when the output function is assigned
at the cooling side during heating and cooling control.
In other words, heating and cooling control is carried out when control
output (cool) is assigned, and standard control is carried out when out-
put is not assigned. For details on heating and cooling control, see 4.1
Selecting the Control Method (page 4-2).


E5AK








• Factory settings are as follows:




3.3 Setting Output Specifications











F Position-propor-
tional type

control output 1 = Control output (heat)
control output 2 = Alarm 1
auxiliary output 1 = Alarm 2
auxiliary output 2 = Alarm 3.
• Output assignments are set in the “control output 1 assignment”, “con-
trol output 2 assignment”, “aux output 1 assignment” and “aux output
2 assignment” parameters (setup mode).

• Position-proportional type controllers support six output functions.
These are assigned to auxiliary outputs 1 and 2.
• Restrictions on assignment destinations are placed on some of the out-
puts. The following table shows where outputs may be assigned to.
Assignment Control Output Auxiliary Output
Destination

Output Function
Alarm 1
Alarm 2
Alarm 3
Error 1 : Input error

Destination

1

2

1
F
F
F
F

2
F
F
F
F

Error 2 : A/D converter error
Error 3 : RSP input error

F
F

F
F


J Direct/reverse
operation














J Control period


• “Direct operation” (or normal operation) refers to control where the
manipulated variable is increased according to the increase in the pro-
cess value. Alternatively, “reverse operation” refers to control where the
manipulated variable is decreased according to the decrease in the pro-
cess value.
For example, when the process value (PV), is lower than the set point
(SP), in a heating control system, the manipulated variable increases by
the difference between the PV and SP values.
Accordingly, this becomes “reverse operation” in a heating control system.
Alternatively, this becomes “direct operation” in a cooling control system.
• Direct/reverse operation is set in the [ ]“direct/reverse operation”
parameter (setup mode).

• When the output unit is pulse output such as relay output, set the pulse
output cycle (control period). Though a shorter pulse period provides
better control performance, the control period should be set taking the
life expectancy of the output unit into consideration when the output
unit is relay.
• The control period is set in the “control period (heat)” parameter (level
1 mode). Factory setting is “20:20 seconds.”
• The “control period (cool)” output function is not allocated. So, the
“control period (cool)” parameter cannot be set.







3--7


E5AK




CHAPTER 3 BASIC OPERATION



In this example, let’s set the parameters as follows:
Setting Example
“control output 1 assignment” = “control output (heat)”
“control output 2 assignment” = “alarm output 1”
“direct/reverse operation” = “reverse operation”
“control period” = “20 secs”
“run/stop” = “run”
All of the above settings in this example are factory settings. So, in this
example, we are only going to check the parameter settings.


(1) Select the menu display, and select [ ] (setup mode) using the
or keys. For details on selecting the menu display, see page


1 second min.

1-8.
(2) Press the
setup mode [


key to enter the setup mode. The top parameter in the
] “input type” is displayed. In this example, the

parameter setting is “17: 4 to 20 mA.”

(3) Press the

key until [

] (“control output 1 assignment”

parameter) is displayed. The parameter default is [

].

(4) As the setting in this example is to be left as it is, press the

key.

The display changes to [

] (“control output 2 assignment”

parameter). The parameter default is [

].

(5) As the setting in this example is to be left as it is, press the

key

until [

] (“direct/reverse operation” parameter) is displayed.

The parameter default is [

].

1 second min.

(6) As the setting in this example is to be left as it is, press the

or

keys to select [

] (level 1 mode). For details on selecting the menu

display, see page 1-8.

(7) Press the
level 1 mode [

key to enter the level 1 mode. The top parameter in the
] “AT execute/cancel” is displayed.

(8) Press the

key until [

] (“control period” parameter) is dis-


























3--8

1 second min.

played. The parameter default is “20”. As the setting in this example
is to be left as it is, quit key operation.


E5AK








3.4 Setting Alarm Type




3.4 Setting Alarm Type














J Alarm type




• Three alarm outputs are supported: alarms 1 to 3. Of these, only the
alarm assigned as the output can be used.
• Alarm output conditions are determined according to the combination
of the “alarm type”, “alarm value” and “alarm hysteresis” parameter
settings.
• The contact conditions when alarm output is ON can be set to “open”
or “closed” in the “close in alarm/open in alarm” parameter.

• The following table shows the alarm types supported by the E5AK con-
troller and their respective operations.
Alarm Output Operation
Alarm Type

When X is positive
X X

When X is negative

1 Upper-and lower-limit alarm
(deviation)
2 Upper-limit alarm (deviation)

3 Lower-limit alarm (deviation)

ON
OFF
ON
OFF

ON
OFF

SP
X
SP
X
SP
X X

Always ON

ON
OFF

ON
OFF


X
SP
X
SP

4 Upper-and-lower-limit range

ON

Always OFF


5

alarm (deviation)
Upper-and-lower-limit alarm
with standby sequence
(deviation)

OFF
ON
OFF

SP
X X
SP
X


Always OFF





X

6 Upper-limit alarm with
standby sequence (deviation)ONOFF
7 Lower-limit alarm with
standby sequence (deviation)ONOFF

SP
X
SP

ON
OFF
ON
OFF

SP
X
SP

8 Absolute-value upper-limit

ON

X

ON

X

alarm
9 Absolute-value lower-limit

OFF
ON

0


X

OFF

ON


X

0

alarm
10 Absolute-value upper-limit
alarm with standby sequence
11 Absolute-value lower-limit
alarm with standby sequence

OFF
ON
OFF

ON
OFF

0


0

0


X


X

OFF
ON
OFF

ON
OFF


X


X

0

0

0





J Alarm value

• Alarm types are set independently for each alarm in the “alarm 1 to 3”
parameters (setup mode). Factory setting is “2: Upper-limit alarm (devi-
ation)”.
• Alarm values are indicated by “X” in the table above. Alarm output
operation differs according to whether the value of the alarm is positive
or negative.
• Alarm values are set independently for each alarm in the “alarm value
1 to 3” parameters (level 1 mode). Factory setting is “0”.





3--9


E5AK




CHAPTER 3 BASIC OPERATION



J Alarm hysteresis • The hysteresis of alarm outputs when alarms are switched ON/OFF can

be set as follows.
Upper limit alarm


ON


OFF



Alarm hysteresis

Lower limit alarm


ON


OFF



Alarm hysteresis

Alarm value

Alarm value





F Standby
sequence

• Alarm hysteresis is set independently for each alarm in the “alarm 1 to
3 hysteresis” parameters (level 2 mode). Factory setting is “0.02:
0.02%FS”.
• “Standby sequence” is a function for unconditionally turning alarm out-
put OFF when the process value has left the alarm range once and it next
enters the alarm range.
• For example, when the alarm type is set to “deviation lower limit,” gener-
ally the process value is within the alarm range, and alarm output
become ON as it is as the process value when the power is turned ON is
smaller than the set point. However, if the alarm type is set to “deviation
lower limit with standby sequence”, alarm output first becomes ON
when the process value exceeds the alarm setting value to leave the
alarm range and once again falls below the alarm value.

J Close in alarm/open in alarm
• When the controller is set to “close in alarm,” the status of the alarm out-
put function is output as it is. When set to “open in alarm,” the status of
the alarm output function is output inverted.



Close in alarm

Open in alarm

Alarm
ON
OFF
ON
OFF

Output
ON
OFF
OFF
ON

Output LED
Lit
Not lit
Lit
Not lit






F Summary of
alarm operations



















3--10

• Alarm type and close in alarm (normally open)/open in alarm (normally
close) can be set independently for each alarm.
• Close in alarm/open in alarm is set in the “alarm 1 to 3 open in alarm”
parameters (setup mode). Factory setting is [ ] “close in alarm”.
The figure below visually summarizes the above description of alarm
operations (when alarm type is set to “lower limit alarm (deviation) with
standby sequence”):
Alarm type: lower limit alarm (deviation)
with standby sequence
PV
Alarm value
Alarm hysteresis




Time
Standby sequence
canceled Close (ON)
Alarm output Open (OFF)
(close in alarm)


E5AK









Setting Example
















1 second min.












1 second min.








1 second min.




















About the Decimal
Point of the Alarm
Value




3.4 Setting Alarm Type



When a set point for a temperature exceeds 10%, alarm1 will be output.
In this example, let’s set the parameters as follows:
“alarm type 1” = “1: (deviation upper-and lower-limit)”
“alarm value 1” = “10”
“alarm hysteresis” = “0.20”
“close in alarm/open in alarm”= “ : close in alarm”


Meanings of parameters, “alarm histeresis” and “open in alarm/close in
alarm” are the same settings at the shipment, so settings for operations
are omitted.
(1) Select the menu display, and select [ ] (setup mode) using the
or keys. For details on selecting the menu display, see page 1-8.
(2) Press the key to enter the setup mode. The top parameter in the
setup mode [ ] “input type” is displayed. In this example, the
parameter setting is “17: 4 to 20 mA”.
(3) Press the key until [ ] (“alarm type 1” parameter) is dis-
played. The parameter default is “2: deviation upper limit”.
(4) Press the key to return to “1: deviation upper-and lower-limit”.
(5) Select the menu key, and select [ ] (level 1 mode) using the
or keys. For details on selecting the menu display, see page 1-8.
(6) Press the key to enter the level 1 mode. The top parameter in the
level 1 mode [ ] “AT execute/cancel” is displayed.
(7) Press the key until [ ] (“alarm value 1” parameter) is dis-
played.
(8) In this example, the parameter setting is “0.0” so press the key
until “10.0” is displayed.






















The decimal point of the alarm value conforms to the setting of the “decimal point”
parameter (setup mode). In this example, the “decimal point” parameter is set to
“1”. (During temperature input, the decimal point of the alarm value conforms to
the set sensor.)


3--11

E5AK




CHAPTER 3 BASIC OPERATION



3.5 Protect Mode



J Security • This parameter allows you to protect until start of operation parameters
that do not change during operation to prevent unwanted modification.
• The set value of the “security” (protect) parameter specifies the range
of protected parameters.
• When this parameter is set to “0”, parameters are not protected.
• When this parameter is set to “1” to “3”, the number of modes that can
be displayed on the menu display is limited.
When set to “1”, level 0 to 2, setup, expansion and option modes only can
be selected. When set to “2”, only level 0 to 2 modes can be selected. When
set to “3”, only level 0 and 1 modes can be selected.
• When this parameter is set to “4” to “6”, operations in only the level 0
mode can be selected, and the mode is not displayed on the menu display.
• When this parameter is set to “5”, only the “PV/SP” parameter can be
used.
• When this parameter is set to “6”, only the “PV/SP” parameter can be
used. (The set point can not change.)
• Default is “1”.

J A/M key protect • This parameter disables use of the A/M key during operation. For exam-
ple, if you protect use of the A/M key by the “A/M key protect” parameter
(protect mode) during auto operation, the controller cannot be set to the
manual mode, preventing manual operation of the controller during
operation.




Setting Example



• Let’s protect the setup, expansion, option and calibration modes. Set the
parameters as follows:
“security” = “2: Usable only in level 0 to 2 modes”



A/M



(1) Press for 1 second minium the A/M and
controller enters the protect mode.



keys simultaneously, the

(2) In the protect mode, the top parameter in the protect mode “security”

is displayed. The parameter default is “1”. Press the
the parameter setting to “2”.

key to change

(3) Press for 1 second minium the A/M and

keys simultaneously, the


A/M














3--12

display changes to the “PV/SP monitor” parameter (level 0 mode).


E5AK




3.6 Starting and Stopping Operation



3.6 Starting and Stopping Operation



• You can start and stop operation by changing the setting of the “run/
stop” parameter (level 0 mode).
• You can switch the RUN/STOP function up to 100,000 times.
• To stop operation, set the “run/stop” parameter to [ ] (stop). In a
stop state, the “STOP” LED lights.
• Operation cannot be stopped during auto-tuning.

F Manipulated vari- • On a standard type controller, specify the manipulated variable (--5.0 to
able at stop 105.0%) in the “MV at stop” parameter (level 2 mode) to output the
manipulated variable during stop.
Factory-set to “0.0:0.0%”.
• On a position-proportional type controller, you can select either of the
open, close or hold status. In an open status, only control output 1 is ON.
In a close status, only control output 2 is ON. In a hold status, both con-
trol outputs 1 and 2 are OFF. Factory-set to “hold.”


The following example describes the procedure to follow to stop control

Setting Example

during operation of the controller.


(1) Select the menu display, and select [




] (level 0 mode) using the




1 second min.


1-8.

or

keys. For details on selecting the menu display, see page

(2) Press the
played.

key to enter the level 0 mode. The PV and SP are dis-

(3) Press the
(4) Press the

key until [
key to select [

] (“run/stop” parameter) is displayed.
] (stop). The “STOP” LED lights,

and operation stops.

To resume operation, follow the above procedure to select [
The “STOP” LED goes out and operation starts.




] (“run”).














Using Event Input














Using the E53-AKB, run/stop can be selected by event input. For details on how to
use event input, see 4.3 How to Use Event Input, page 4--8.



3--13


E5AK




CHAPTER 3 BASIC OPERATION



3.7 Adjusting Control Operation



J Changing the set • You can change the set point in the “set point” parameter (level 0 mode).
point • However, note that you cannot change the set point when the “security”
parameter (protect mode) is set to “6”.

• To change the set point, press the

or

keys to select the desired






Setting Example












J Manual operation







F Standard type

Process value

value. If you leave the setting for two seconds, the set point is updated
to the new setting.


In the following example, let’s change the temperature set point from
“60_C” to “50_C”.


(1) Select the PV/SP monitor display.
(2) Press the key to change the setting to “50.0: 50.0_C”.







• On standard type controller, the manipulated variable is controlled, and
on a position-proportional type controller, the valve opening is con-
trolled.
• To set manual operation and manually set the manipulated variable or
the valve opening, press for 1 second minimum theA/Mkey. The control-
ler enters the manual mode.
• The process value is displayed on the No.1 display, and the manipulated
variable is displayed on the No.2 display. The manipulated variable
(heat) is also displayed on the bar graph in 10% increments.

Manipulated
variable

• To change the manipulated variable, press the

or

keys. After

Bar graph [MANU] LED















Balance-less,
Bump-less Opera-
tion


3--14

two seconds, the manipulated variable is updated to the new setting.
• Other modes cannot be selected while in the manual mode. To select
other modes, press for 1 second minimum the A/M key. The manual mode
is quit.
• The automatic return of display function does not work while in the
manual mode.
• When switching between manual and auto operation, the manipulated
variable is subject to balance-less, bump-less operation.
• If the power is interrupted during manual operation, manual operation
is resumed at the manipulated variable at power interruption when the
power is reset.
• You can switch the AUTO/MANUAL function up to 100,000 times.

To prevent sudden changes in the manipulated variable when switching between
manual and auto operation, operation is resumed using the value that was active
immediately before operation was switched, and the value is brought gradually
closer to the value immediately after operation was switched.


E5AK




3.7 Adjusting Control Operation



The following diagram summarizes manual operation.
Manipulated variable (%)
Balance-less, bump-less points








Time


Manual

0

Manipulated variable
switched

OFF

ON

A/M
Auto


F Position-proportional type

Power inter-
ruption

• When a potentiometer is connected to the controller, the process value
is displayed on the No.1 display, and the valve opening is displayed on the
No.2 display. The valve opening is also displayed on the bar graph in 10%
increments.
When a potentiometer is not connected to the controller, [----] is dis-
played on the No.2 display, and nothing is displayed on the bar graph.

Potentiometer connected

Potentiometer not connected
Process value Process value
Valve opening Valve opening


Bar graph [MANU] LED
• When you press the


Bar graph [MANU] LED
key, the open side becomes ON. When you press

the

key, the close side becomes ON.

• Other modes cannot be selected while in the manual mode. To select
other modes, press for 1 second minimum the A/M key. The manual mode
is quit.
• The automatic return of display function does not work while in the
manual mode.
• You can switch the AUTO/MANUAL function up to 100,000 times.



















3--15


E5AK




CHAPTER 3 BASIC OPERATION





J Auto-tuning • AT (auto-tuning) cannot be executed while operation is canceled or dur-
(A.T.) ing ON/OFF control.

• When you execute auto-tuning, the optimum PID parameters are auto-
matically set by forcibly changing the manipulated variable to calculate
the characteristics (called the “limit cycle method”) of the control target.
During auto-tuning, the AT LED flashes.
• 40%AT or 100%AT can be selected by the limit cycle of MV change width.
Specify [ ] or [ ], respectively, in the “AT execute/cancel” pa-
rameter (level 1 mode).
• During heating and cooling control and with position-proportional
type, only 100%AT can be executed. (So, [ ] (40%AT) will not be
displayed.)

• To cancel AT execution, specify [

] (“AT cancel”).


F 40%AT












Deviation at start of AT


In order to set the limit cycle of MV change width to 40%, select 40%AT
to execute auto-tuning with fluctuations in the process value kept to a
minimum. However, note that auto-tuning takes longer to execute
compared with 100%AT.
The timing by which limit cycles are generated varies according to wheth-
er or not the deviation (DV) at the start of AT execution is 10% full-scale
or less.

Deviation at start of AT




Set point

execution ≧ 10% full-scale


Limit cycle of MV change
width 40%




Set point

execution < 10% full-scale Limit cycle of MV change width 40% Start of AT execution Deviation 10% full-scale End of AT Time Deviation 10% full-scale Start of AT End of AT execution Time F 100%AT In order to set the limit cycle of MV change width to 100%, select 100% AT to shorten the AT execution time without worrying about fluctuations in the process value. Limit cycle of MV change width 100% Set point Time 3--16 Start of AT execution End of AT E5AK Setting Example In this example, let’s execute 40%AT. 3.7 Adjusting Control Operation (1) Select [ ] (level 1 mode) using the or keys. For details on 1 second min. selecting the menu display, see page 1-8. (2) Press the key to enter the level 1 mode. The top parameter in the setup mode [ ] “AT execute/cancel” is displayed. In this example, the parameter setting is [ ] “AT cancel” (3) Press the key to specify [ ]. (4) The AT LED flashes, and AT execution starts. When the AT LED goes out (end of AT execution), the parameter automatically returns to AT execute [ ] (“AT cancel”). About PID Parame- ters In addition to AT, the E5AK is also provided with fuzzy self-tuning (ST) that allows automatic calculation of the PID parameters suited to the control target. However, note that the ST function op- erates only during standard control by temperature input. For fur- ther information regarding the ST, please see page 5-34 and A-14. When control characteristics are already known, the PID parameters can be set directly to adjust control. PID parameters are set in the “proportional band” (P), “integrated time” (I) and “derivative time” (D) parameters (level 1 mode). For details on the setting ranges of these parameters, see chapter 5 Level 1 Mode (page 5-13). 3--17 E5AK CHAPTER 3 BASIC OPERATION 3--18 E5AK 4 CHAPTER 4 CHAPTER 4 APPLIED OPERATION APPLIED OPERATION This chapter describes each of the parameters required for making full use of the features of the E5AK. Read this chapter while referring to the parameter descriptions in chapter 5. 4.1 Selecting the Control Method . . . . . . . . . . . . 4-2 Heating and cooling control . . . . . . . . . . . . . 4-2 Position-proportional control . . . . . . . . . . . . 4-3 ON/OFF control . . . . . . . . . . . . . . . . . . . . . . . 4-4 4.2 Operating Condition Restrictions . . . . . . . . 4-5 Manipulated variable restrictions . . . . . . . . 4-5 Set point limiter . . . . . . . . . . . . . . . . . . . . . . . 4-6 SP ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6 4.3 How to Use Event Input . . . . . . . . . . . . . . . . 4-8 Event input assignments . . . . . . . . . . . . . . . 4-8 Multi-SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9 Other event input functions . . . . . . . . . . . . . 4-10 4.4 How to Use the Remote SP . . . . . . . . . . . . . . 4-11 Scaling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11 SP mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-11 Remote SP monitor . . . . . . . . . . . . . . . . . . . . 4-12 SP tracking . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12 Operating conditions . . . . . . . . . . . . . . . . . . . 4-12 4.5 How to Use the Heater Burnout Alarm . . . 4-13 Heater burnout detection . . . . . . . . . . . . . . . 4-13 Operating conditions . . . . . . . . . . . . . . . . . . . 4-13 How to calculate the heater burnout set value . . . . . . . . . . . . 4-14 4.6 LBA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15 4.7 How to Use Transfer Output . . . . . . . . . . . . 4-17 4--1 E5AK CHAPTER 4 APPLIED OPERATION 4.1 Selecting the Control Method When selecting the control method, set the parameters according to the following table. (Parameters are factory-set to heating control.) Parameter Control output 1 Control output 2 Direct/Reverse Control assignment assignment operations Method Heating control (Standard) Cooling control (Standard) Control output (heat) Control output (heat) - - Reverse operation Direct operation Heating and cooling control Control output (heat) Control output (cool) Reverse operation J Heating and cooling control F Dead band For details on how to assign outputs, see 3.3 Setting Output Specifications (page 3-6). • When heating and cooling control is selected, the “deadband” and “cool- ing coefficient” parameters can be used. The dead band is set with the set point as its center. The dead band width is the set value of the “dead band” parameter (level 1 mode). Setting a posi- tive value produces a dead band, while setting a negative value produces an overlap band. Dead band: dead Overlap band: dead Output Heating side 0 band width = positive Cooling side PV Set point Output Heating side 0 Set point band width = negative Cooling side PV F Cooling coeffi- cient F Manipulated vari- able at stop Switching with Manual operation 4--2 If the heating and cooling characteristics of the control target greatly dif- fer, preventing satisfactory control characteristics from being obtained by the same PID parameters, adjust the proportional band (P at cooling side) using the cooling coefficient to balance control between the heating and cooling sides. In heating and cooling control, P at the heating or cooling side is calculated by the following formula: Heating side P = P; Cooling side P = cooling coefficient ¢ P • In heating and cooling control, the manipulated variable output that is output when controller operation is stopped is dependent on the set value of the “MV at stop” parameter (level 2 mode) in the same way as for standard control. • However, note that in heating and cooling control, the manipulated vari- able at the cooling side is treated as a negative value for the sake of conve- nience. When the manipulated variable at STOP is a negative value, the manipulated variable is output to only the cooling side, and when a posi- tive value, the manipulated variable is output to only the heating side. The factory setting is “0”. If the controller is operated using the factory setting, the manipulated variable is not output to both the heating and cooling sides. When the overlap band is set, the bumpless function that operates when switching between manual and automatic operation may not work. E5AK J Position-propor- tional control F Travel time F Valve opening monitor F Manipulated vari- able at stop/PV error F Other functions 4.1 Selecting the Control Method • Use the position-proportional type controller for position-proportional control. • On a position-proportional type controller, control output 1 is used for open output, and control output 2 is used for close output. Accordingly, control outputs 1 and 2 cannot be used as output assignments. Special output units are already set on position-proportional type controllers. • On a position-proportional type controller, the following functions are disabled. ST MV limiter P and PD control 40% AT LBA HBA ON/OFF control • The travel time is factory-set to “30 seconds.” • To change the travel time, either set in the “travel time” parameter (option mode), or execute motor calibration in the “motor calibration” parameter (option mode). • The valve opening can be monitored when a potentiometer is connected to the controller. However, be sure to execute motor calibration after connecting the potentiometer. • The monitored valve opening is displayed on the bar graph in 10% incre- ments. • Open, close or hold can be selected as output at stop or PV error. Set these outputs in the “manipulated variable at stop” or “manipulated variable at PV error” parameters (level 2 mode). • Set the dead band in the “position-proportional dead band” parameter (level 1 mode). • Set the open/close hysteresis in the “open/close hysteresis” parameter (level 1 mode). Open/close hysteresis Dead band ON OFF MV- Valve opening -100% 0 100% 4--3 E5AK CHAPTER 4 APPLIED OPERATION J ON/OFF control • Switching between advanced PID control and ON/OFF control is car- ried out by the “PID / ON/OFF” parameter (expansion mode). When this parameter is set to [ ], advanced PID control is selected, and when set to [ ], ON/OFF control is selected. Default is [ ]. F Hysteresis • During position-proportional control, ON/OFF control cannot be selected. • In ON/OFF control, hysteresis is provided in the program when switch- ing between ON and OFF to stabilize operation. The hysteresis width provided during ON/OFF control is simply referred to as “hysteresis.” Control output (heat) and control output (cool) functions are set in the “hysteresis (heat)” and “hysterisis (cool)” parameters, respectively. • In standard control (heating or cooling control), hysteresis can be set only for the heating side. Hysteresis (heat) ON OFF PV Set point • In heating and cooling control, a dead band can be set. So, 3-position con- trol is made possible. Dead band Hysteresis (heat) Hysteresis (cool) ON OFF Heating side Set point Cooling side PV Parameters Symbol Parameter Name: Mode Control output 1 assignment : Setup Control output 2 assignment : Setup Direct/Reverse operation : Setup Dead band : Level 1 Cooling coefficient : Level 1 MV at stop : Level 2 MV at PV error : Level 2 Travel time : Option Motor calibration : Option Positional-proportional dead band : Level 1 Open/close hysteresis : Level 2 Hysteresis (heat) : Level 1 Hysteresis (cool) : Level 1 Description For specifying control method For specifying control method For specifying control method Heating and cooling control Heating and cooling control Manipulated variable when control operation is stopped Manipulated variable when control operation is PV error Position-proportional control Position-proportional control Position-proportional control Position-proportional control ON/OFF control ON/OFF control 4--4 PID / ON/OFF : Expansion ON/OFF control E5AK 4.2 Operating Condition Restrictions 4.2 Operating Condition Restrictions J Manipulated vari- The upper-and lower-limit values of the manipulated variable can be able restrictions restricted by the MV limiter, and the change rate of the manipulated vari- F MV limiter able can be restricted by the MV change rate limiter. The upper-and lower-limit values of the manipulated variable are set in the “MV upper limit” and “MV lower limit” parameters (level 2 mode). When the manipulated variable calculated by the E5AK is outside of the range of the MV limiter, actual outputs are dependent on the set value of these parameters. Output (%) 100 0 MV upper limit value MV lower limit value PV In heating and cooling control, the manipulated variable at the cooling side is treated as a negative value for the sake of convenience. The upper limit is set for the heating side (positive value), and the lower limit is set for the cooling side (negative value) as shown in the following figure. Output (%) 100 MV lower limit value MV upper limit value 0 Heating side Set point Cooling side PV F MV change rate limiter The “MV change rate limit” parameter (level 2 mode) sets the maximum permissible change width per second of the manipulated variable. If a change in the manipulated variable exceeds this parameter setting, the value calculated by the E5AK is reached while changing the value by the per-second value set in this parameter. Output (%) 100 MV change rate limit value 1 second 0 Switching point Time 4--5 E5AK CHAPTER 4 APPLIED OPERATION F Limiter operation The limiters are invalid or cannot be set when any of the following condi- conditions tions occurs: • During ON/OFF control • During ST execution • During AT execution (only by MV change rate limiter) • During manual operation • When operation is stopped • When an error has occurred. • During position-proportional control (manipulated variable limiter only) J Set point limiter The setting range of the set point is limited by the set point limiter. The upper-and lower-limit values of this set point limiter are set in the “Set point upper limit” and “Set point lower limit” parameters (expansion mode), respectively. However, note that when the set point limiter is reset, the set point is forcibly changed to the upper-or lower-limit value of the set point limiter if the set point is out of the limiter range. Also, when the in- put type, temperature unit and scaling (sensor) range are changed, set point limiter is forcibly reset to the scaling (sensor) range. Scaling (sensor) range Set point limiter Setting range SP Changed to upper limit value Input type changed Changed to the new up- per limit value A ○ B × SP Set point Upper-and lower-limit values of the limiter Scaling (sensor) upper-and lower-limit values C B ○ J SP ramp Set point With the SP ramp function, the controller operates according to the value (set point during SP ramp) limited by a change rate, instead of the changed set point when set point is changed. The interval in which the set point during SP ramp is limited is referred to as the “SP ramp”. SP SP ramp SP ramp set value 4--6 Switching point SP ramp time unit Time E5AK F Operation at start 4.2 Operating Condition Restrictions The change rate during the SP ramp is specified by the “SP ramp set value” and “SP ramp time unit” parameters. At the “SP ramp set value” default “0”, the SP ramp function is disabled. The set point changing in SP ramp can be monitored in the “Set point dur- ing SP ramp” parameter (level 0 mode). The limiters are invalid or cannot be set when any of the following condi- tions occurs: If the SP ramp function is enabled when the power is turned ON, and when “run” is switched to from “stop,” process value may reach the set point af- ter SP ramp in the same way as when the set point is changed. In this case, operation is carried out with the process value regarded as the set point before the change was made. The direction of the SP ramp changes according to the relationship be- tween the process value and the set point. PV < SP PV > SP
SP SP


Set point





PV

SP ramp








Power ON


PV


Set point


Time

SP ramp








Power ON



Same change
rate



Time

F Restrictions dur-
ing SP ramp

• Execution of auto-tuning starts after the end of SP ramp.
• When the controller is switched to the manual mode, the set point
changes continuously until SP ramp ends.
• When the controller is in the stop state or an error occurs, the SP ramp
function becomes invalid.



Parameters




Symbol




Parameter Name: Mode
MV upper limit : Level 2
MV lower limit : Level 2
MV change rate limit : Level 2




Description
Manipulated variable restrictions
Manipulated variable restrictions
Manipulated variable restrictions

SP setting upper limit: Expansion SP setting restrictions
SP setting lower limit : Expansion SP setting restrictions

SP ramp set value : Level 2
SP ramp time unit : Level 2

SP changing restrictions
SP changing restrictions














4--7


E5AK




CHAPTER 4 APPLIED OPERATION



4.3 How to Use Event Input



• When using event input, mount the option unit (E53-AKB). Up to two
E53-AKB units can be mounted on the E5AK, and two event inputs can
be used for each E53-AKB unit.
E53-AKB × 1 unit : 2 event inputs
E53-AKB × 2 units : 4 event inputs
• Event inputs can be switched up to 100,000 times.


J Event input • You can choose from the following five event input functions:
assignments Multi-SP
Run/Stop
Remote/Local
Auto/Manual
SP mode
• In the case of the multi-SP function, the number of event inputs (event
input 1 or 2) set in the “multi-SP function” parameter (option mode) are
used. When four event inputs are used, the multi-SP function is auto-
matically assigned to event inputs 1 and 2 for the designated number.
When two event inputs are used, the multi-SP function is automatically
assigned to event inputs 3 and 4 for the designated number.
• Other functions are assigned to event inputs 1 to 4 not used for the mul-
ti-SP function according to the setting of the “event input assignment 1 to
4” parameters (option mode). However, note that “event input assignment
1/2” parameters cannot be used when only one unit of the E53-AKB is
installed.
4 event inputs 2 event inputs

Event input

0

1

2

1

2

3

4

3

4


Multi-SP


Other event input functions


• The following table shows the relationship between the settings and
functions of the “event input assignment 1 to 4” parameters.












4--8


Setting


Function
Event input disabled
ON : Stop /OFF : Run
ON : Remote /OFF : Local
ON : Manual /OFF : Auto
ON : RSP /OFF : LSP


E5AK








F Assignment
example




4.3 How to Use Event Input



• In this example, set four event inputs are used, the multi-SP function to
“2”, and event input 3 to “Run/Stop” and event input 4 to “Auto/
Manual”. Set as follows:
(1) Set “multi-SP function” parameter to “2”
(2) Set “event input assignment 3” parameter to “ ”
(3) Set “event input assignment 4” parameter to “ ”


Event input


1


2


3


4

Multi-SP

Auto/Manual
Run/Stop

J Multi-SP

• Set points 0 to 3 are set as the set point according to event input. How-
ever, note that these parameters can not be set when the multi-SP func-
tion is not selected. The following table shows the relationship between
event inputs and set points 0 to 3.


Multi-SP Function
Event Input
Set Point 0
Set Point 1
Set Point 2
Set Point 3


1
1 (3)*
OFF
ON
-
-



1 (3)*
OFF
ON
OFF
ON


2



2 (4)*
OFF
OFF
ON
ON


* When using 2 event inputs, the multi-SP function is assigned to event
inputs 3 and 4.
• When you have changed the set point in the PV/SP display, the set point
of the currently selected is also simultaneously changed.
• When you have switched between set point 0 to 3, the SP ramp function
works if the SP ramp function is enabled. The following example shows
how the set point changes when you switch from set point 0 to set point 1.



set point 1


set point 0


Event input

SP










OFF


SP
ramp






ON









Time




























4--9


E5AK




CHAPTER 4 APPLIED OPERATION



J Other event input functions
• Switch the parameter settings for each of the run/stop, remote/local and
SP modes.
• The switching operation of auto/manual is the same as that of the A/M
key.
• There is no order of priority in event input and key operations. However,
run/stop or auto/manual event inputs must be set to either of ON or OFF.
So, parameters will always follow event input even if you try to switch
settings by key operation.

F Run/Stop • When event input is set to “ON”, controller operation is stopped and the
“STOP” LED lights. The content of event input is reflected in the “run/
stop” parameter (level 0 mode).

F Remote/Local • This function is supported only when E53-AK01/02/03, the option unit
for serial communications, is installed.
• When event input is set to “ON”, parameters can be written only by
using the communications function, and the “RMT” LED lights. The
content of event input is reflected in the “remote/local” parameter (level
2 mode).

F Auto/Manual • When event input is set to “ON”, the controller is switched for manual
operation, and the “MANU” LED lights.
• Turn event input ON/OFF while the controller is ON.

F SP mode • This function is enabled only when the “SP mode enable” parameter
(option mode) is set to “ON”.
• When event input is set to “ON”, the remote SP (RSP) is taken as the set
point, and the “RSP” LED lights. When event input is set to “OFF”, the
local SP (LSP) is taken as the set point. The content of event input is
reflected in the “SP mode” parameter (level 2 mode). For details on RSP/
LSP, see 4.4 How to Use the Remote SP (page 4-11).

















Parameters
















Symbol
















Parameter Name: Mode

















Application

Multi-SP function

: Option Event input functions

* Event input assignment 1 to 4 : Option Event input functions





4--10

** Set point 0 to 4
* : to ** : to

: Level 1 Multi-SP


E5AK








4.4 How to Use the Remote SP




4.4 How to Use the Remote SP








J Scaling




• Taking a remote SP input (4 to 20 mA) as the set point is referred to as
the “remote SP” function. The remote SP function is enabled only when
the “remote SP (RSP) enable” parameter (option mode) is set to “ON”.
• Remote SP upper-and lower-limit values can be set by scaling.
• Inputs within the range 4 to 20 mA (-10 to 110%) are allowed as remote
SP inputs. Inputs not within this range are regarded as out-of-range
input values. In this case, input is clamped at the remote SP lower or
upper limit values, and the “RSP” LED blinks.
• If the output function “RSP input error” is assigned for when an out-of-
range remote SP is input, the “RSP input error” output is turned ON.
Control output also switches to the setting of the “MV at PV error”
parameter.
• Set the upper limit value in the “remote SP upper limit” parameter and
the lower limit value in the “remote SP lower limit” parameter (option
mode).
RSP (%)
Out-of-range input
(blinks of upper-and lower-limit values)
Upper limit value





Lower limit value
Input (mA)
4 20

2.4 (-10%)

21.6 (-110%)


F Relationship with
set point limiter


• When the “Set point upper limit” or “Set point lower limit” parameters
are changed, the remote SP upper-and lower-limit values are forcibly
changed to the set poimt upper-and lower-limit values. The following
example shows how the remote SP upper-and lower-limit values are
changed when the set point upper limit value is changed from A to B.
Set point limiter
RSP scaling range
A

Before change

Set point
Upper limit value
changed from A to B


Changed to
upper limit value



Upper-and lower-limit values of the limiter
RSP scaling upper-and lower-limit values


B


Set point


J SP mode
LSP


RSP





SP mode


• The set point held internally by the E5AK controller is referred to as the
“local SP (LSP).”
• If the multi-SP function is enabled, set points 0 to 3 are enabled for use
as the local SP.
• Use the “SP mode” parameter to switch between the remote SP and local
SP. When the SP mode parameter is set to “ ” (remote SP), the

RSP enable

“RSP” LED lights. When the SP mode parameter is set to “
controller is in the local SP mode.

”, the



4--11


E5AK




CHAPTER 4 APPLIED OPERATION



J Remote SP • In the remote SP mode, the remote SP can be monitored on the No.2 dis-

monitor

J SP tracking

play for PV/SP. In the local SP mode, the remote SP can be monitored in
the “remote SP monitor” parameter.
• When the local SP is switched to from the remote SP when the SP track-
ing function is enabled, the local SP is changed so that the remote SP
value is held at the SP value used immediately before switching.
To use the SP tracking function, set the “SP tracking” parameter to
“ON”.
• The following figure shows how SP tracking works when the SP mode
is switched.

RSP input
LSP1
LSP2

RSP2





SP mode LSP





RSP





LSP














J Operating
conditions


(1) When the remote SP is switched to when the set point is “LSP1”, the
SP is switched to “RSP2”.
(2) The SP shifts according to remote SP input.
(3) When the local SP is switched to, the set point becomes “LSP2” if the
SP tracking function is enabled. If this function is disabled, the SP
will be switched to “LSP1”.
• When the local SP is switched to the remote SP, the SP ramp will operate
if the SP ramp function is enabled.

• When the SP function is set to “ON”, the “SP mode” parameter is forci-
bly changed to [ ] and the local SP is taken as the set point.
• During auto-tuning, remote SP input is not accepted. Auto-tuning is
executed on the set point at the start of auto-tuning.
• Remote SP is not subject to the standby sequence reset conditions.












Parameters








4--12












Symbol












Parameter Name: Mode
Remote SP enable : Option
Remote SP upper limit : Option
Remote SP lower limit : Option
SP mode : Level 2
SP tracking : Option













Application
Remote SP function
RSP scaling
RSP scaling
LSP/RSP switching
LSP/RSP switching


E5AK




4.5 How to Use the Heater Burnout Alarm



4.5 How to Use the Heater Burnout Alarm



• On a standard type controller, the HBA (heater burnout alarm) function
can be used only when the assignment destination of the output function
“control output (heat)” is set to pulsed output.
• When using the HBA function, assign output function “heater burnout
(HB) alarm” to auxiliary outputs 1 or 2.

J Heater burnout • Heater burnout detection works as follows.
detection (1) Connect the current transformer (CT) to terminal Nos.15 and 17, and

To E5AK
CT terminal












F HBA





CT




Heater wire

insert the heater lead through the CT hole.
(2) When current flows through this lead, the current transformer gener-
ates AC current proportional to the current value. The E5AK mea-
sures this AC current to calculate the current flowing to the heater.
(3) If heater is burned out, the current measured at the current trans-
former decreases. This value is compared with the value set as the
heater burnout set value and is output as the heater burnout alarm.
• Set the heater burnout set value in the “heater burnout alarm” parame-
ter. To check the current value of the current transformer, use the
“heater current monitor” parameter.
• When you are not using the HBA function, set the “heater burnout
alarm” parameter to “0.0 (disabled)”.
• When the HBA latch function is set to “ON”, the heater burnout alarm

latch/release






J Operating
conditions

is held until either of the following measures is taken:
a Set the heater burnout set value to “0.0”.
b Reset the controller.
(Turn the controller’s power OFF then back ON again.)
• To enable the HBA latch function, set the “HBA latch” parameter to
“ON”.
• Turn the heater power supply ON at the same time as or before turning
the E5AK power supply ON. If the heater power supply is turned ON
after turning the E5AK power supply On, the heater burnout alarm is
output.
• Control is continued even when the heater burnout alarm is output.
(That is, the controller attempts to control the heater as if the heater
burnout alarm has not occurred.) So, remedy the condition such as
repairs which are caused by the heater burnout alarm.
• The heater burnout alarm is detected only if the control output is contin-
uously ON for 190 ms or more.
• The rated current value may sometimes differ slightly from the actual
current value flowing to the heater. Check the current value in an actual
operating status in the “heater current monitor” parameter.
• If there is little difference between the current in a normal status and the
current in a burnout status, detection may become unstable. On a heater
of current 10.0 A or less, maintain a difference of 1.0 A or more. On a
heater of current 10.0 A or more, maintain a difference of 2.5 A or more.
• Heater burnout alarm function cannot be used when controlling the
heater by a phase control method or by a cycle control method. Also,
3-phase heaters cannot be used.
When detecting heater burnout on a 3-phase heater, use the K2CU-FVVA-VGS
(with gate input terminal). (For details, see the respective data sheet.)


4--13


E5AK




CHAPTER 4 APPLIED OPERATION



J How to calculate • Calculate the set value nby the following formule:
the heater burn- Set value = (current value at normal operation + current value at burnout)

out set value


























F Examples of use

2
• Set the current value at burnout when two or more heaters are con-
nected to the CT to the value at the time that the heater having the small-
est current value burns out (the value when one of the heaters burns out
with all heaters at the same current).
• Make sure that the following condition is satisfied:
Heater of current 10.0 A or less
Current value at normal operation -- current value at heater burn-
out ≧ 1 A
When resultant current is less than 1 A, detection is unstable.
Heater of current 10.0 A or more
Current value at normal operation -- current value at heater burn-
out ≧ 2.5 A
When resultant current is less than 2.5 A, detection is unstable.
• The setting range is 0.1 to 49.9 A. Heater burnout is not detected when
the setting is “0.0” or “50.0”. When the setting is “0.0”, the heater burn-
out alarm is set to “OFF”, and when the setting is “50.0”, the heater
burnout alarm is set to “ON”.
• Set the total current value at normal heater operation to 50 A or less.
When set to 55.0 A or more, [ ] is displayed in the “heater current
monitor” parameter.


Example 1 : when using a 200 VAC, 1 kW heater

Heater


1KW

Control output



AC200V

Current at normal operation = 1000
200 = 5A (< 10A) Current at heater burnout = 0A Set value =5+0 E5AK 17 CT 15 2 = 2.5A Example 2 : when using three 200 VAC, 1 kW heaters Heater Control output Current at normal operation = 1000 200 ×3 = 15A (≧ 10A) 1KWx3 CT AC200V Current at burnout of one heater = 1000 15+10 200×2 = 10A Set value = 2 = 12.5A E5AK Parameters 4--14 17 15 Symbol (current at normal operation--current at heater burnout = 15 -- 10 = 5A (≧ 2.5A) Parameter Name: Mode Application Heater current monitor : Level 1 Heater current value monitor Heater burnout : Level 1 Heater burnout detection Heater burnout latch : Option Heater burnout detection alarm latch E5AK 4.6 LBA F LBA detection time F LBA detection width F LBA detection example 4.6 LBA • The LBA (Loop Break Alarm) function can be used only on standard type controllers. • The LBA function can be used only when assigned as an output. Also, the LBA function does not work when a memory error or A/D converter error results. • LBA (Loop Break Alarm) is a function for judging that an error has occurred somewhere on the control loop and outputting an alarm when the process value does not change with the manipulated variable at a maximum or minimum state. Accordingly, the LBA function can be used as a means for detecting a malfunctioning control loop. • Normally, when output is set to maximum or minimum, the process value rises or falls after the dead time has elapsed. LBA is output if the process value does not change in the predicted direction after a fixed amount of time has elapsed. This fixed amount of time is the “LBA detec- tion time.” • LBA operation sometimes becomes unstable when the process value fluctuates considerably due to the control characteristics. The LBA detection width is provided so that changes with respect to output can be correctly detected. Changes smaller than the detection width due to LBA detection timing are not regarded as changes. • The following example describes what happens when a heater burnout at maximum output. LBA detection time LBA detection time PV LBA detection width Output Time Heater burnout LBA=ON • LBA judgment is carried out at each LBA detection time from the point of maximum output. In above figure, the process value (PV) is changing greatly at the 1st judgment timing, so LBA remains OFF. • At the 2nd judgment timing, the process value increases as indicated by the broken line of the process value is normal. This means that the change width exceeds the LBA detection width, and LBA output remains OFF. • If the heater burns out at the point shown in the above figure, the process value “decreases.” Accordingly, it is judged that “the process value is not changing in the increasing direction” at the 2nd judgment timing and the LBA output becomes ON. 4--15 E5AK CHAPTER 4 APPLIED OPERATION F Setting the LBA • The LBA detection time is automatically set by auto-tuning (except in detection time heating and cooling control). • If the optimum LBA detection time cannot be obtained by auto-tuning, set the time in the “LBA detection time” parameter (level 2 mode). F Determining the • Calculate the LBA detection time as follows: LBA detection (1) Set output to maximum. time (2) Measure the time it takes for the input change width to reach the LBA detection width (default: 0.2 % full-scale). (3) Take a value twice that of the measurement time as the LBA detection time. Measurement time Tm PV 0.2%FS Output Time LBA detection time = Tm x 2 (4) In the case of ON/OFF operation, set the LBA detection time to a val- ue longer than the control period. Parameters Symbol Parameter Name: Mode AT Execute/Cancel : Level 1 LBA detection time : Level 2 Application Automatic setting of LBA detec- tion time Setting of LBA detection time 4--16 LBA detection width : Expansion Changing of LBA detection width E5AK 4.7 How to Use Transfer Output 4.7 How to Use Transfer Output F Transfer output type F Transfer output scaling • When using transfer output, add on the communications unit (E53-AKF). • You can select the following data items in the “transfer output type” parameter (option mode) as the transfer outputs: Set point Set poing during SP ramp Process value Manipulated variable (heat) Manipulated variable (cool), and Valve opening. However, note that heating/cooling side manipulated variables can be output only standard type controllers, and valve opening can be output on position-proportional type controllers • If the output assignment is changed when either ”manipulated variable (heat)” or ”manipulated variable (cool)” parameter is selected, the default ”set point” is returned to. • These transfer outputs can be scaled according to the settings of the “transfer output upper limit” and “transfer output lower limit” param- eters before output. Setting of an upper limit value smaller than the lower limit value is allowed, so reverse scaling can also be carried out. Also, the scale can be enlarged by the upper-and lower-limit width speci- fied for each data item. The following example shows scaling of the read- ing side manipulated variable. Transfer output (mA) 20 4 Reverse scaling Transfer output (mA) 20 4 Manipu- Enlarged scale Manipulated Transfer output upper limit: 0 Transfer output lower limit: 100 lated variable (%) 0 Transfer output lower limit: 10 Transfer output upper limit: 80 100 variable (%) 4--17 E5AK CHAPTER 4 APPLIED OPERATION • If “input type”, “scaling upper/lower limit”, “SP limitter upper/lower limit”, or “_C/_F selection” parameters is changed when “set point”, “set point during SP ramp”, or “process value” parameter is selected, each of the “transfer output upper limit” and “transfer output lower limit” parameters are forcibly changed to their respective upper or lower limit values. SP limitter Transfer type scaling range A Change value Set point Change upper limit value A to B. Limitter upper limit change value Limitter upper/lower limit values B Set point Parameters Symbol Transfer type scaling upper/lower limit values Parameter Name: Mode Application 4--18 Transfer output type : Option Transfer output upper limit : Option Transfer output lower limit : Option Transfer output designation Transfer output scaling Transfer output scaling E5AK 5 CHAPTER 5 PARAMETERS CHAPTER 5 PARAMETERS This chapter describes the parameters of the E5AK. Use this chapter as a reference guide. Conventions Used in this Chapter . . . . . . . . . . . . 5-2 Protect Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3 Manual Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5 Level 0 Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6 Level 1 Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-10 Level 2 Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-18 Setup Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-25 Expansion Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-32 Option Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-37 Calibration Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-46 5--1 E5AK CHAPTER 5 PARAMETERS Conventions Used in this Chapter J The meaning of icons used in this chapter Describes the functions of the parameter. Function Describes the range and defaults of the parameter setting. Comment Used for monitor-dedicated parameters. Describes the range of the monitor values. Monitor Describes a procedure using parameters in operating instructions. Example of use Describes related parameters and items. See Describes models of the E5AK or option units supporting the parameter being described. Model J About parameter display On the E5AK controller, only parameters that can be used are displayed. These parameters are displayed only when the “Conditions of Use” on the right of the parameter heading are satisfied. However, note that the settings of protected parameters are still valid, and are not displayed regardless of the conditions of use. 5--2 AT Execute/cancel Conditions of Use The control er must be in operation. E5AK Protect Mode • The protect mode is for disabling (protecting) the functions of the menu key or A/M key. Before changing parameters in this mode, first make sure that protecting the menu key or A/M key will not cause any problems in operation. • To select this mode, press the A/M key and key simultaneously for 1 second mini- mum. To exit this mode, press the A/M key and key down again simultaneously for 1 second minimum. • The following table shows the parameters supported in this mode and the page where the parameter is described. Symbol Security Parameter Name Page 5-3 Security [A/M] key protect 5-4 Function Comment • This parameter specifies which parameters are protected. However, note that the protect mode and manual mode cannot be protected. • When this parameter is set to “0” to “3”, only the modes indicated by the “f” mark in the table below can be selected on the menu display. For example, when this param- eter is set to “2”, only level 0 to 2 modes can be selected. Set value Mode Calibration Option Expansion Setup Level 2 Level 1 Level 0 0 1 2 3 4 5 6 f f f f f f f f f f f f f f f f f f f f * See • When this parameter is set to “4” to “6”, operations in only the level 0 mode can be selected, and the mode is not displayed on the menu display. • When this parameter is set to “5”, only the “PV/SP” parameter in the level 0 mode can be used. • When this parameter is set to “6”, only the “PV/SP” parameter in the level 0 mode can be used. (The set point cannot change.) • Default is “1”. (Only the calibration mode is protected.) F Related article 3.5 Protect Mode (page 3-12) 5--3 E5AK CHAPTER 5 PARAMETERS Protect Mode [A/M] key protect • Invalidate the function of the key. In other words, you cannot switch between the Function auto and manual operations by key operation. • [ ] : A/M key protect ON • [ ] : A/M key protect canceled Comment • Default = [ F Related article ] 5--4 See 3.5 Protect Mode (page 3-12) E5AK Manual Mode • In this mode, manual operations are possible, and the “MANU” LED lights. • When this mode is selected, the manipulated variable that was active immediately before the mode was switched to is output. When changing the manipulated variable, change it using the or keys. If this mode is switched to during auto-tuning, auto-tuning is canceled. • To select this mode when in the level 0 to 2 modes, press the A/M key for 1 second mini- mum. To exit this mode, press the A/M key for 1 second minimum. The mode changes to the level 0 mode. • “Manual MV” is the only parameter available in this mode. Manual MV • Sets the manipulated variable for manual operation or the valve opening. On a standard type controller when you press the or keys, the manipulated variable is Function changed. On a position-proportional type controller when you press the key, the open side becomes ON, and when you press the key, the close side becomes ON. • On a standard type controller, the process value is displayed on the No.1 display and the manipulated variable is displayed on the No.2 display. The manipulated variable on the heating side is also displayed on the bar graph in 10% increments. Process value Manipulated variable Bar graph [MANU] LED • When a potentiometer is connected on a position-proportional type controller, the process value is displayed on the No.1 displayed, and the valve opening is displayed on the No.2 display. The valve opening is also displayed on the bar graph in 10% incre- ments. When a potentiometer is not connected to the controller, [----] is displayed on the No.2 display, and nothing is displayed on the bar graph. Potentiometer connected Potentiometer not connected Process value Process value Valve opening Valve opening Bar graph [MANU] LED Bar graph [MANU] LED • On standard type controllers, the manual MV is held when the power is interrupted. • Standard type Comment Control Method Standard Heating and cooling Setting Range -5.0 to 105.0 -105.0 to 105.0 Unit % % Default 0 0 • Position-proportional type Control Method Monitor Range Unit Position-proportional F Related article -10.0 to 110.0 % See 3.7 Adjusting Control Operation (page 3-14) 5--5 E5AK CHAPTER 5 PARAMETERS Level 0 Mode • The parameters in this mode can be used only when the “security” parameter (pro- tect mode) is set to “0” to “4”. • The “PV/SP” parameter can be used when the “security” parameter is set to “5” or “6”. However, note that the SP cannot be changed when it is set to “6”. • This mode is used for monitoring the process value, set point and manipulated vari- able during operation, and for checking and setting the SP setting value. It is also used for starting and stopping controller operation. • To select this mode when in the levels 1 and 2, setup, expansion, option and calibra- tion modes, press the key for 1 second minimum. The display changes to the menu display. If you select [ ] then press key for 1 second minimum, the controller enters the level 0 mode. • To select parameters in this mode, press the key. To change parameter settings, use the or keys. • The following table shows the parameters supported in this mode and the page where the parameter is described. Symbol PV/SP Parameter Name Page 5-6 PV/SP Remote SP monitor Set point during SP ramp MV monitor (heat) MV monitor (cool) Vavle opening monitor Run/Stop 5-7 5-8 5-8 5-8 5-9 5-9 Function 5--6 • The process value is displayed on the No.1 display, and the set point is displayed on the No.2 display. The set point can be set. • Either of the local SP or remote SP is displayed as the set point depending on the SP mode. In the remote SP mode, the set point is only monitored. Local SP mode Remote SP mode Process value Set point Monitor only [RSP] LED not lit [RSP] LED lit • The selected set point is linked when the multi-SP function is in use in the local SP mode. For example, when set point 1 is selected, set point 1 is displayed on the No.2 display, and the setting of the “set point 1” parameter (level 1 mode) also is changed when the value of set point 1 is changed. • The decimal point position is dependent on the selected sensor during temperature input and on the results of scaling during analog input. E5AK • Process value Monitor Range Level 0 Mode Unit Comment Scaling lower limit -10%FS to scaling upper limit +10%FS EU During temperature input, the range of the currently selected sensor is taken as the monitor range. • Set point Setting Range/Monitor Range Local SP : Local SP lower limit to local SP setting upper limit Remote SP: Remote SP lower limit to remote SP upper limit F Related article 3.7 Adjusting Control Operation (page 3-14) F Related parameters Unit EU EU Default 0 - See Function Monitor See “Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode) “SP setting upper limit” “SP setting lower limit” (expansion mode) “SP mode” (level 2 mode) “Remote SP enable” “Remote SP upper limit” “Remote SP lower limit” (option mode) Remote SP monitor Conditions of Use The controller must be in the local SP mode with the remote SP function enabled. • Monitors remote SP in the local SP mode. Monitor Range Unit Remote SP lower limit to Remote SP upper limit EU F Related article 4.2 Operating Condition Restrictions/SP ramp (page 4-6) F Related parameters “SP mode” (level 2 mode) “Remote SP enable” “Remote SP lower limit” “Remote SP upper limit” (option mode) 5--7 E5AK CHAPTER 5 PARAMETERS Level 0 Mode Set point during SP ramp • Monitors the set point during SP ramp Conditions of Use The remote SP function must be enabled. When the remote SP function is disabled, this function can be used only when the SP ramp function is enabled. Function Monitor See Function • Matches the set point of the “PV/SP” parameter when the set point is not during SP ramp . Moniter Range Unit Local SP : Local SP setting lower limit to local SP setting upper limit EU Remote SP : Remote SP lower limit to remote SP upper limit EU F Related article 4.2 Operating Condition Restriction/SP ramp (page 4-6) F Related parameters “PV/SP” (level 0 mode) “SP ramp time unit” “SP ramp set value” (level 2 mode) “Set point upper limit” “Set point lower limit” (expansion mode) “SP mode” (level 2 mode) “Remote SP enable” “Remote SP upper limit” “Remote SP lower limit” (option mode) MV monitor (heat) Conditions of Use Control must be standard control or heat- ing and cooling control. MV monitor (cool) • This parameter cannot be set. • Monitors the manipulated variable on the heating or cooling side. • The manipulated variable in a standard control system is checked in the “MV moni- tor (heat)” parameter. • The “MV monitor (cool)” parameter can be used only during heating and cooling con- trol. • MV monitor (heat) 5--8 Monitor Model Control Standard Heating and cooling • MV monitor (cool) Control Heating and cooling E5AK-AA2 AC100-240 E5AK-AA2 AC/DC24 Monitor Range -5.0 to 105.0 0.0 to 105.0 Monitor Range 0.0 to 105.0 Unit % % Unit % E5AK Valve opening monitor Level 0 Mode Conditions of Use Control must be position-proportional con- trol Function Monitor See Model Function • Monitors the valve opening during position-proportional control. Moniter Range Unit -10 to +110 EU F Related article 4.1 Selecting the Control Methed/Position-proportional control (page 4-3) E5AK-PRR2 AC100-240 E5AK-PRR2 AC/DC24 Run/Stop • This parameter is used for checking the operating status of the controller, and for specifying start and stop of operation. • When the “run/stop” function is assigned to event input, “stop” is set when event in- put is ON, and “run” is set when event input is OFF. There is no order of priority in key operations. • To start operation, set this parameter to [ ] press the or keys. To stop Example of use operation, set this parameter to [ LED lights. • Default is [ ] F Related article ]. When operation is stopped, the “STOP” See 3.6 Starting and Stopping Operation (page 3-13) 5--9 E5AK CHAPTER 5 PARAMETERS Level 1 Mode • The parameters in this mode can be used only when the “security” parameter (pro- tect mode) is set to “0” to “3”. • This mode contains the main parameters for adjusting control. These parameters include parameters for executing AT (auto-tuning), setting the alarm values, setting the control period, and setting PID parameters. • To select this mode when in the levels 0 and 2, setup, expansion, option and calibra- tion modes, press the key for 1 second minimum. The display changes to the menu display. If you select [ ] then press the key for 1 second minimum, the controller enters the level 1 mode. • To select parameters in this mode, press the key. To change parameter settings, use the or keys. • The following table shows the parameters supported in this mode and the page where the parameter is described. 5--10 Symbol Parameter Name AT Execute/Cancel Set point 0 Set point 1 Set point 2 Set point 3 Alarm value 1 Alarm value 2 Alarm value 3 Proportional band Integral time Derivative time Cooling coefficient Dead band Position-proportional dead band Manual reset value Hysteresis (heat) Hysteresis (cool) Control period (heat) Control period (cool) Heater current monitor Heater burnout Page 5-11 5-11 5-11 5-11 5-11 5-12 5-12 5-12 5-12 5-12 5-12 5-13 5-14 5-14 5-15 5-15 5-15 5-16 5-16 5-17 5-17 E5AK AT Execute/Cancel Level 1 Mode Conditions of Use The controller must be in operation, con- trol must be advanced PID control, and ST must be set to OFF. Function • Selects the limit cycle of MV change width (40% or 100%) for execution. After AT execution, the “PID” and the “LBA detection time” (LBA: Loop Break Alarm) param- eters are set automatically. • During heating and cooling control or position-proportional control, only 100%AT can be executed. • When this parameter is selected, the setting becomes [ ]. • To execute 40%AT, select [ ], and to execute 100%AT, select [ ]. During Example of use See execution of auto-tuning, the AT LED flashes. However, note that during heating and cooling control or position-proportional control, [ ] is not displayed. • When AT execution ends, the parameter setting automatically returns to [ ]. F Related article 3.7 Adjusting Control Operation (page 3-16) F Related parameters “Run/Stop” (level 0 mode) “Proportional band” “Integral time” “Derivative time” (level 1 mode) “LBA detection time” (level 2 mode) Set point 0 Set point 2 Set point 1 Set point 3 Conditions of Use The controller must be in the local SP mode with the multi-SP function enabled. Function • Switches set points 0 to 3 by event input for use as the set point (local SP). • Of set points 0 to 3, the number of valid set points is designated by the “multi-SP func- tion” parameter. • The following table shows the relationship between event input and the selected parameter. Multi-SP Function Event Input Set Point 0 Set Point 1 Set Point 2 Set Point 3 1 1 OFF ON - - 1 OFF ON OFF ON 2 2 OFF OFF ON ON • When the set point has been changed, the setting of whichever is selected in event input, “set point 0” to “set point 3”, is linked and changed. • The decimal point position is dependent on the selected sensor during temperature input and on the results of scaling during analog input. 5--11 E5AK CHAPTER 5 PARAMETERS Level 1 Mode Setting Range Unit Default Comment See Set point lower limit to Set point upper limit F Related article 4.3 How to Use Event Input (page 4-8) F Related parameters EU 0 Model Function “Multi-SP function” “Remote SP enable” (option mode) “Set point” (level 0 mode) “SP mode” (level 2 mode) “Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode) F Option unit E53-AKB Alarm value 1 Conditions of Use Alarms must be assigned as outputs. For Alarm value 2 example, if alarm outputs 1 and 2 only are assigned as outputs, the “alarm value 3” Alarm value 3 parameter cannot be used. • This parameter is used for monitoring or changing the alarm values of alarm outputs 1 to 3. • During temperature input, the decimal point position is dependent on the currently selected sensor, and during analog input on the results of scaling. Comment Setting Range -1999 to 9999 F Related article Unit EU Default 0 5--12 See 3.4 Setting Alarm Type (page 3-9) F Related parameters “Input type” “Scaling upper limit” “Scaling lower limit” Decimal point” “Control output 1 assignment” “Control output 2 assignment” “Auxiliary output 1 assign- ment” “Auxiliary output 2 assignment” “Alarm 1 type” “Alarm 2 type” “Alarm 3 type” “Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” (setup mode) “Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode) “Standby sequence reset method” (expansion mode) E5AK Proportional band Integral time Derivative time Level 1 Mode Conditions of Use Control must be advanced PID control, and ST must be set to OFF. Function • Sets the PID parameters. However, note that the PID parameter settings are changed to optimum values when auto-tuning is executed, and self-tuning is selected. Parameter Proportional band Setting Range 0.1 to 999.9 Unit %FS Default 10.0 Comment Integral time Derivative time 0 to 3999 (see note1) Second 0 to 3999 Second 233 40 See Function note1 : During position-proportional control, the setting range become 1 to 3999s. F Related parameter “AT Execute/Cancel” (level 1 mode) Cooling coefficient Conditions of Use The control must be either heating and cooling control, or advanced PID control. • In heating and cooling control, P at the cooling side is calculated by the following for- mula: Cooling side P = cooling coefficient ¢ P Comment Setting Range 0.01 to 99.99 F Related article Unit None Default 1.00 See Model 4.1 Selecting the Control Method (page 4-2) F Related parameter “Proportional band” (level 1 mode) E5AK-AA2 AC100-240 E5AK-AA2 AC/DC24 5--13 E5AK CHAPTER 5 PARAMETERS Level 1 Mode Dead band Conditions of Use The control system must be heating and cooling control. Function • Sets the output dead band width in a heating and cooling control system. A negative setting sets an overlap band. Comment Setting Range -19.99 to 99.99 F Related article Unit %FS Default 0.00 See Model 4.1 Selecting the Control Method (page 4-2) E5AK-AA2 AC100-240 E5AK-AA2 AC/DC24 Position-proportional Conditions of Use dead band Control must be position-proportional con- trol Function • Sets the output hold width during position-proportional control (ON/OFF switching point for open and close output). Open/close hysteresis Dead band ON OFF MV- Valve opening -100% 0 100% Comment Setting Range 0.1 to 10.0 F Related article Unit % Default 2.0 5--14 See Model 4.1 Selecting the Control Method/Position-proportional Control (page 4-3). F Related parameter “Open/close hysteresis” (Level 2 mode) E5AK-PRR2 AC100-240 E5AK-PRR2 AC/DC24 E5AK Manual reset value Level 1 Mode Conditions of Use The control must be either standard con- trol or advanced PID control, ST must be set to OFF, and the “integral time” parame- ter must be set to “0”. Function • Sets the required manipulated variable to remove offset during stabilization of P or PD control. Comment Model Setting Range 0.0 to 100.0 E5AK-AA2 AC100-240 E5AK-AA2 AC/DC24 Hysteresis (heat) Hysteresis (cool) Unit % Default 50.0 Conditions of Use The control system must be ON/OFF con- trol. Function • Sets the hysteresis for ensuring stable operation at ON/OFF switching. • In standard control, use the “hysteresis (heat)” parameter. The “hysteresis (cool)” parameter cannot be used. • In heating and cooling control, the hysteresis can be set independently for heating and cooling. Use the “hysteresis (heat)” parameter to set the heating side hysteresis, and use the “hysteresis (cool)” parameter to set the cooling side hysteresis. Comment Parameter Hysteresis (heat) Hysteresis (cool) F Related article Setting Range 0.01 to 99.99 0.01 to 99.99 Unit %FS %FS Default 0.10 0.10 See Model 4.1 Selecting the Control Method/ON/OFF control (page 4-4) F Related parameters “Control output 1 assignment” “Control output 2 assignment” (setup mode) “PID / ON/OFF” (expansion mode) E5AK-AA2 AC100-240 E5AK-AA2 AC/DC24 5--15 E5AK CHAPTER 5 PARAMETERS Level 1 Mode Control period (heat) Control period (cool) Conditions of Use Relay or voltage output must be set as the outputs, and the control must be set to advanced PID control, standard control or heating and cooling control. Function • Sets the pulse output period. Set the control period taking the control characteristics and life expectancy of the controller into consideration. • In standard control, use the “control period (heat)” parameter. The “control period (cool)” parameter cannot be used. • In heating and cooling control, the control period can be set independently for heat- ing and cooling. Use the “control period (heat)” parameter to set the heating side con- trol period, and use the “contrlo period (cool)” parameter to set the cooling side con- trol period. Comment Parameter Control period (heat) Control period (cool) F Related article Setting Range 1 to 99 1 to 99 Unit Second Second Default 20 20 5--16 See Model 3.3 Setting Output Specifications (page 3-6) F Related parameters “Control output 1 assignment” “Control output 2 assignment” (setup mode) E5AK-AA2 AC100-240 E5AK-AA2 AC/DC24 E5AK Heater current monitor Level 1 Mode Conditions of Use The HBA output function must be assigned. Function • Measures the current value of the heater from CT input. Monitor Range Unit 0.0 to 55.0 A Monitor • [ ] is displayed when 55.0 A is exceeded. See Model Function F Related article 4.5 How to Use the Heater Burnout Alarm (page 4-13) F Related parameters “Heater burnout” (level 1 mode) “HBA latch” (option mode) E5AK-AA2 AC100-240 E5AK-AA2 AC/DC24 Heater burnout Conditions of Use The HBA output function must be assigned. • Outputs the heater burnout alarm when the heater current value falls below this parameter setting. • When the set value is “0.0”, the heater burnout alarm is “OFF”. When the set value is “50.0”, the heater burnout alarm is “ON”. Comment Setting Range 0.0 to 50.0 F Related article Unit A Default 0.0 See Model 4.5 How to Use the Heater Burnout Alarm (page 4-13) F Related parameters “Heater current monitor” (level 1 mode) “HBA latch” (option mode) E5AK-AA2 AC100-240 E5AK-AA2 AC/DC24 5--17 E5AK CHAPTER 5 PARAMETERS Level 2 Mode • The parameters in this mode can be used only when the “security” parameter (pro- tect mode) is set to “0” to “2”. • This mode contains the auxiliary parameters for adjusting control. These parame- ters include parameters for limiting the manipulated variable and set point, parame- ters for switching between remote and local operation, and parameters for setting the LBA (Loop Break Alarm), alarm hysteresis, and input digital filter values. • To select this mode when in the levels 0 and 1, setup, expansion, option and calibra- tion modes, press the key for 1 second minimum. The display changes to the menu display. If you select [ ] using the key then press the key for 1 second minimum, the controller enters the level 2 mode. • To select parameters in this mode, press the key. To change parameter settings, use the or keys. • The following table shows the parameters supported in this mode and the page where the parameter is described. 5--18 Symbol Parameter Name Remote/Local SP mode SP ramp time unit SP ramp set value LBA detection time MV at stop MV at PV error MV upper limit MV lower limit MV change rate limit Input digital filter Open/close hysteresis Alarm 1 hysteresis Alarm 2 hysteresis Alarm 3 hysteresis Input shift upper limit (temperature) Input shift lower limit (temperature) Page 5-19 5-19 5-20 5-20 5-21 5-21 5-21 5-22 5-22 5-22 5-23 5-23 5-24 5-24 5-24 5-24 5-24 E5AK Remote/Local Level 2 Mode Conditions of Use The communications function must be in use. Function • Switches between remote and local operation. • To change the parameter setting during remote operation, use the communications function. To change the parameter setting during local operation, change the setting on the E5AK controller. You can check the parameter setting by both communications and on the E5AK con- troller regardless of whether the controller is switched to remote or local operation. • When the event input to which “remote/local” is assigned is ON, the controller switches to the remote mode. When the event input is OFF, the controller switches to the local mode. Setting Range Default Comment [ ]: remote / [ ]: local [ ] See Model Function F Related article Chapter 6 Using the Communications Function F Related parameters “Communication stop bit” “Communication data length” “Communication parity” “Communication baud rate” “Communication unit No.” “Event input assignment 1” “Event input assignment 2” “Event input assignment 3” “Event input assign- ment 4” (option mode) F Option units E53-AK01/02/03 SP mode Conditions of Use The remote SP function must be enabled and ST must be set to OFF. • Switches between remote SP and local SP. • Switches the SP to the remote SP when an event input to which the “SP mode” has been assigned is ON. Switches the SP to the local SP when an event input to which the “SP mode” has been assigned is OFF. Setting Range Default Comment [ ]: Remote SP/[ ]: Local SP See F Related article 4.4 How to Use the Remote SP (page 4-11) F Related parameters “Remote SP enable” “Event input assignment 1” “Event input assignment 2” “Event input assignment 3” “Event input assignment 4” (option mode) 5--19 E5AK CHAPTER 5 PARAMETERS Level 2 Mode SP ramp time unit SP ramp set value Conditions of Use ST must be set to OFF. Function • Specifies the change rate during SP ramp operation. Set the maximum permissible change width per unit of time (minute or hour) as the “SP ramp set value”. However, note that when set to “0”, the SP ramp function is disabled. • The time unit and SP ramp set value are independent of each other. For example, when setting “30 per minute”, set the “SP ramp set value” parameter to “30” and the “SP ramp time unit” parameter to [ ] (“minute”). However, if you change the time unit only to [ ] (“hour”), the set time becomes “30 per hour.” • During temperature input, the decimal point position of the SP ramp set value is dependent on the currently selected sensor, and during analog input on the results of scaling. Comment Parameter SP ramp time unit [ SP ramp set value Setting Range ]: minute/ [ ]: hour 0 to 9999 Unit None EU Default 0 5--20 See During temperature input, the range of the currently selected sensor it taken as the setting range for the “SP ramp set value” parameter. F Related article 4.2 Operating Condition Restrictions/SP ramp (page 4-6) F Related parameters “Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode) E5AK LBA detection time Level 2 Mode Conditions of Use The LBA (Loop Break Alarm) function must be assigned as an output. Function • This parameter is automatically set by AT execution (excluding AT execution in a ON/OFF control). • The LBA is output if the change width of the process value falls below 0.2 %full-scale of the time preset to this parameter when the manipulated variable is set in the “MV upper limit” or “MV lower limit” parameters. • The LBA function is disabled when this parameter is set to “0”. Comment Setting Range 0 to 9999 F Related article 4.4 LBA (page 4-9) Unit Second Default 0 See Function 7.3 How to Use Error Output (page 7-5) F Related parameters “AT Execute/Cancel” (level 1 mode) “Control output 1 assignment” “Control output 2 assignment” “Auxiliary output 1 assignment” (setup mode) MV at stop Conditions of Use Advanced PID control MV at PV error • The “MV at stop” parameter sets the manipulated variable when operation stops on a standard type controller. On a position-proportional type controller, this parameter sets the action (close/hold/open) when operation stops. • The “MV at PV error” parameter sets the manipulated variable when an input error occurs. On a position-proportional type controller, this parameter sets the action (close/hold/open) when an input error occurs. • Standard type Comment Control Method Standard Heating and cooling Setting Range -5.0 to 105.0 -105.0 to 105.0 Unit % % Default 0 0 The manipulated variable at the cooling side during heating and cooling control is expressed as a negative value. • Position-proportional type [ ]: Hold/[ Setting Range ]: Open/[ ]: Close Unit None Default F Related articles MV at stop : 3.6 Starting and Stopping Operation (page 3-13) See MV at PV error : 8.2 How to Use the Error Display (page 8-3) 5--21 E5AK CHAPTER 5 PARAMETERS Level 2 Mode MV upper limit MV lower limit MV change rate limit Conditions of Use The control must be advanced PID con- trol, and ST must be set to OFF. Function Comment • The “MV upper limit” and “MV lower limit” parameters set the upper and lower lim- its of the manipulated variable. When the manipulated variable calculated by the E5AK controller is outside of the upper-and lower-limit range, the upper limit or lower limit set to these parameters is output, respectively. However, note that these parameters are disabled during position-proportional con- trol. • The “MV change rate limit” parameter sets the maximum permissible change width per second of the manipulated variable (on the position-proportional control, valve opening). If a change in the manipulated variable (on the position-proportional con- trol, valve opening) causes this parameter setting to be exceeded, the calculated value is reached while changing the value by the per-second value set in this parameter. This function is disabled when the set value is “0.0”. • MV upper limit The setting ranges during standard control and heating and cooling control are dif- ferent. Also, the manipulated variable at the cooling side during heating and cooling control is expressed as a negative value. Control Method Standard Heating and cooling • MV lower limit Setting Range MV lower limit +0.1 to 105.0 0.0 to 105.0 Unit % % Default 105.0 105.0 The setting ranges during standard control and heating and cooling control are dif- ferent. Also, the manipulated variable at the cooling side during heating and cooling control is expressed as a negative value. Control Method Standard Heating and cooling • MV change rate limit Setting Range 0.0 to 100.0 F Related article Setting Range -5.0 to MV upper limit -0.1 -105.0 to 0.0 Unit Default % 0.0 Unit % % Default -5.0 -105.0 5--22 See 4.2 Operating Condition Restrictions/Manipulated variable restrictions (page 4-5) E5AK Input digital filter Level 2 Mode Function • Sets the time constant of the input digital filter. The following figures shows the effect on data after passing through the digital filter. PV before passing through filter A PV after passing through filter 0.63A Time constant Input digital filter Time Comment Setting Range 0 to 9999 Unit Second Default 0 Open/close hysteresis Conditions of Use Control must be position-proportional con- trol. Function • Provides hysteresis at ON/OFF switching of open or close output in position-propor- tional control. Comment Setting Range 0.1 to 20.0 F Related article Unit % Default 0.8 See Model 4.1 Selecting the Control Method/Position-proportional Control (page 4-3) E5AK-PRR2 AC100-240 E5AK-PRR2 AC/DC24 5--23 E5AK CHAPTER 5 PARAMETERS Level 2 Mode Alarm 1 hysteresis Alarm 2 hysteresis Alarm 3 hysteresis Conditions of Use Alarms must be assigned as outputs. For example, if alarm outputs 1 and 2 only are assigned as outputs, the “alarm 3 hystere- sis” parameter cannot be used. Function • This parameter is for checking the hysteresis of alarm outputs 1 to 3. Comment Setting Range 0.01 to 99.99 F Related article Unit %FS Default 0.02 See 3.4 Setting Alarm Type (page 3-9) F Related parameters “Alarm 1 type” “Alarm 2 type” “Alarm 3 type” “Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” (setup mode) “Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode) Input shift upper limit Conditions of Use The input type must be set to temperature Input shift lower limit input (thermocouple or platinum resis- tance thermometer). Function • Sets each of the shift amounts for the input shift upper and lower limit values. Comment Setting Range -199.9 to 999.9 F Related article Unit _C or _F Default 0.0 5--24 See 3.2 Setting Input Specifications (page 3-4) F Related parameter “Input type” (setup mode) E5AK Setup Mode • The parameters in this mode can be used only when the “security” parameter (pro- tect mode) is set to “0” and “1”. • This mode contains the parameters for setting the basic specifications of the E5AK controller. These parameters include parameters for specifying the input type, scal- ing, output assignments, and direct/reverse operation. • To select this mode when in the levels 0 to 2, expansion, option and calibration modes, press the key for 1 second minimum. The display changes to the menu display. If you select [ ] using the key then press the key for 1 second mini- mum, the controller enters the setup mode. • To select parameters in this mode, press the key. To change parameter settings, use the or keys. • The following table shows the parameters supported in this mode and the page where the parameter is described. Symbol Input type Parameter Name Page 5-26 Scaling upper limit Scaling lower limit Decimal point _C/_F selection Parameter initialize Control output 1 assignment Control output 2 assignment Auxiliary output 1 assignment Auxiliary output 2 assignment Alarm 1 type Alarm 1 open in alarm Alarm 2 type Alarm 2 open in alarm Alarm 3 type Alarm 3 open in alarm Direct/Reverse operation 5-27 5-27 5-27 5-28 5-27 5-28 5-28 5-29 5-29 5-30 5-31 5-30 5-31 5-30 5-31 5-31 5--25 E5AK CHAPTER 5 PARAMETERS Setup Mode Input type • Sets the sensor type by the code. Function • Set the code according to the following table. Default is “2: K1 thermocouple”. Set value Input Type Comment 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 JPt -199.9 to 650.0 (_C) /-199.9 to 999.9 (_F) Pt -199.9 to 650.0 (_C) /-199.9 to 999.9 (_F) K1 -200 to 1300 (_C) /-300 to 2300 (_F) K2 0.0 to 500.0 (_C) /0.0 to 900.0 (_F) J1 -100 to 850 (_C) /-100 to 1500 (_F) J2 0.0 to 400.0 (_C) /0.0 to 750.0 (_F) T -199.9 to 400.0 (_C) /-199.9 to 700.0 (_F) E 0 to 600 (_C) /0 to 1100 (_F) L1 -100 to 850 (_C) /-100 to 1500 (_F) L2 0.0 to 400.0 (_C) /0.0 to 750.0 (_F) U -199.9 to 400.0 (_C) /-199.9 to 700.0 (_F) N -200 to 1300 (_C) /-300 to 2300 (_F) R 0 to 1700 (_C) /0 to 3000 (_F) S 0 to 1700 (_C) /0 to 3000 (_F) B 100 to 1800 (_C) /300 to 3200 (_F) W 0 to 2300 (_C) /0 to 4100 (_F) PLII 0 to 1300 (_C) /0 to 2300 (_F) 4 to 20mA 0 to 20mA 1 to 5V 0 to 5V 0 to 10V Platinum resistance thermometer Thermocouple Current input Voltage input 5--26 See F Related article 3.2 Setting Input Specifications (page 3-4) F Related parameters When input type is set to temperature input: “_C/_F selection” (setup mode) When input type is set to voltage input or current input: “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode) E5AK Scaling upper limit Conditions of Use Setup Mode Scaling lower limit Decimal point The input type must be set to analog input (voltage or current input). Function • This parameter can be used only when voltage input or current input is selected as the input type. • When voltage input or current input is selected as the input type, scaling is carried out. Set the scaling upper limit in the “scaling upper limit” parameter and the scaling lower limit in the “scaling lower limit” parameter. • The “decimal point” parameter specifies the decimal point position of parameters (set point, etc.) whose unit is set to EU (Engineering Unit). • Scaling upper limit, Scaling lower limit Parameter Setting Range Unit Default Comment See Scaling upper limit Scaling lower limit +1 to 9999 Scaling lower limit -1999 to scaling upper limit -1 • Decimal point : default : 0 Set Value Setting Example 0 0 digits past decimal point 1234 1 1 digit past decimal point 123.4 2 2 digits past decimal point 12.34 3 3 digits past decimal point 1.234 F Related article 3.2 Setting Input Specifications (page 3-4) F Related parameter “Input type” (setup mode) Parameter initialize EU EU 100 0 Function • Returns parameter settings to their defaults. However, note that the following parameters are not affected by execution of this parameter: “input type”, “scaling upper limit”, “scaling lower limit”, “decimal point” and “_C/_F selection”. • When this parameter is selected, [ ] (“no”) is first displayed. To initialize parame- Example of use ters, press the key to specify [ ] (“yes”). 5--27 E5AK CHAPTER 5 PARAMETERS Setup Mode _C/_F selection Conditions of Use The input type must be set to temperature input (thermocouple or platinum resis- tance thermometer). Function Comment See • This parameter can be used when thermocouple or platinum resistance thermometer is selected as the input type. • Set the temperature input unit to either of “_C” or “_F”. Setting Range Default : _C / : _F F Related article 3.2 Setting Input Specifications (page 3-4) F Related parameter “Input type” (setup mode) Control output 1 Conditions of Use assignment The control must be standard control or Control output 2 assignment heating and cooling control. Function • Assigns the output functions to either of control output 1 or 2. • The following seven output functions can be assigned as outputs: Control output (heat), Control output (cool), Alarms 1 to 3, HBA, and LBA. • Errors 1, 2 and 3 cannot be assigned as outputs. • When the output function assigned to control output 1 is ON, the “OUT1” LED lights. However, note that the OUT1 LED does not light when control output (heat) or control output (cool) are assigned to linear outputs such as current and voltage. • When the output function assigned to control output 2 is ON, the “OUT2” LED lights. Symbol Function Control output Control output Comment Defaults: (heat) (cool) Alarm 1 Alarm 2 Alarm 3 HBA LBA “Control output 1” = [ F Related article ], “Control output 2” = [ ] 5--28 See Model 3.3 Setting Output Specifications (page 3-6) F Related parameters • Alarm-related parameters • Heating and cooling related parameter “LBA detection time” (level 2 mode) E5AK-AA2 AC100-240 E5AK-AA2 AC/DC24 E5AK Auxiliary output 1 assignment Auxiliary output 2 assignment Setup Mode Function • Assigns output functions to either of auxiliary output 1 or 2. • The following eight output functions can be assigned as outputs: Alarms 1 to 3, HBA, LBA, Error 1 (input error), Error 2 (A/D converter error), and Error 3 (remote SP input error). • Control output (heat) and control output (cool) cannot be assigned as outputs. • Error 3 can be assigned only when the remote SP function is enabled. • When the output function assigned to auxiliary output 1 or auxliary output 2 is ON, the “SUB1” or “SUB2” LED lights. Symbol Function Alarm 1 Alarm 2 Alarm 3 HBA LBA Error 1 Error 2 Error 3 Comment Defaults: “Auxiliary output 1”= [ F Related article ], “Auxiliary output 2”= [ ] See 3.3 Setting Output Specifications (page 3-6) F Related parameter • Alarm-related parameter “LBA detection time” (level 2 mode) 5--29 E5AK CHAPTER 5 PARAMETERS Setup Mode Alarm 1 type Alarm 2 type Alarm 3 type Conditions of Use Alarms must be assigned as outputs. For example, if alarm outputs 1 and 2 only are assigned as outputs, the “alarm 3 type” parameter cannot be used. Function • “Alarm 1 to 3 type” parameters specify the operation of the alarm by the one of the set values in the following table. For details of operation at an alarm, see page 3-9. Comment Set Value 1 2 3 4 5 6 Settings Upper-and lower-limit alarm (deviation) Upper-limit alarm (deviation) Lower-limit alarm (deviation) Upper-and lower-limit range alarm (deviation) Upper-and lower-limit alarm with standby sequence (deviation) Upper-limit alarm with standby sequence (deviation) Set Value 7 8 9 10 11 Settings Lower-limit alarm with standby sequence (deviation) Absolute-value upper-limit alarm Absolute-value lower-limit alarm Absolute-value upper-limit alarm with standby sequence Absolute-value lower-limit alarm with standby sequence 5--30 See Defaults: 2 (Deviation upper limit) F Related article 3.4 Setting Alarm Type (page 3-9) F Related parameters “Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode) “Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode) “Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” “Control output 1 assignment” “Control output 2 assignment” “Auxiliary output 1 assign- ment” “Auxiliary output 2 assignment” (setup mode) E5AK Alarm 1 open in alarm Conditions of Use Setup Mode Alarm 2 open in alarm Alarm 3 open in alarm • Selects the output states of alarms 1 to 3. Alarms must be assigned as outputs. For example, if alarm outputs 1 and 2 only are assigned as outputs, the “alarm 3 open in alarm” parameter cannot be used. Function • When the controller is set to “close in alarm,” the status of the alarm output function is output as it is. When set to “open in alarm,” the status of the alarm output function is output inverted. The following table shows the relationship between alarm output functions, output and output LEDs. Close in alarm Open in alarm Setting Range Alarm ON OFF ON OFF Output ON OFF OFF ON Default Output LED Lit Not lit Lit Not lit Comment [ ] : Close in alarm/ [ ]:Open in alarm [ ] See Function F Related article 3.4 Setting Alarm Type (page 3-9) F Related parameters “Alarm value 1” “Alarm value 2” “Alarm value 3” (level 1 mode) “Alarm 1 hysteresis” “Alarm 2 hysteresis” “Alarm 3 hysteresis” (level 2 mode) “Alarm 1 open in alarm” “Alarm 2 open in alarm” “Alarm 3 open in alarm” “Control output 1 assignment” “Control output 2 assignment” “Auxiliary output 1 assignment” “Auxiliary output 2 assignment” (setup mode) Direct/Reverse operation • “Direct operation” (or normal operation) refers to control where the manipulated variable is increased according to the increase in the process value. Alternatively, “reverse operation” refers to control where the manipulated variable is increased according to the decrease in the process value. Setting Range Default Comment [ ] : Reverse operation/ [ ]:Direct operation [ ] See F Related article 3.3 Setting Output Specifications/Direct/reverse operation (page 3-7) 5--31 E5AK CHAPTER 5 PARAMETERS Expansion Mode • The parameters in this mode can be used only when the “security” parameter (pro- tect mode) is set to “0” and “1”. • This mode contains the parameters for setting expanded functions. These parame- ters include parameters for setting ST (self-tuning), setting the SP setting limiter, selecting advanced PID and ON/OFF control, specifying the standby sequence reset method, and automatic return of display mode. • To select this mode when in the levels 0 to 2, setup, option and calibration modes, press the key for 1 second minimum. The display changes to the menu display. If you select [ ] using the key then press the key for 1 second mini- mum, the controller enters the expansion mode. • To select parameters in this mode, press the key. To change parameter settings, use the or keys. • The following table shows the parameters supported in this mode and the page where the parameter is described. 5--32 Symbol Parameter Name Set point upper limit Set point lower limit PID / ON/OFF ST ST stable range a AT calculated gain Standby sequence reset method Automatic return of display mode AT hysteresis LBA detection width Page 5-33 5-33 5-33 5-34 5-34 5-34 5-35 5-35 5-36 5-36 5-36 E5AK Set point upper limit Set point lower limit Expansion Mode Function • Limits the upper and lower limits of the set point. When the set point exceeds the set- tings of the “Set point upper limit” and “Set point lower limit” parameters, the E5AK controller regards the settings of the “Set point upper limit” and “Set point lower limit” parameters as the set points. • When the input type is changed to temperature input, the set point upper and lower limits are changed to the upper and lower limits of the currently selected sensor. And when the input type is changed to analog input, the set point upper and lower limits are changed to the scaling upper and lower limits. • During temperature input, the decimal point position is dependent on the currently selected sensor, and during analog input on the results of scaling. Parameter Setting Range Unit Default Comment SP setting upper limit SP setting lower limit SP setting lower limit +1 to scaling upper limit Scaling lower limit to SP setting upper limit -1 EU EU 1300 -200 See Function During temperature input, the range becomes the range of use of the selected sensor instead of the scaling upper and lower limit values. F Related article 4.2 Operating Condition Restrictions (page 4-5) F Related parameters “Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode) PID / ON/OFF Condition of Use Control must be standard control or heat- ing and cooling control. • Selects advanced PID control or ON/OFF control. Setting Range Default Comment [ ] : advance PID/ [ ] :ON/OFF [ ] See Model F Related article 4.1 Selecting the Control Method/ON/OFF control (page 4-4) F Related parameters “Hysteresis (heat)” “Hysteresis (cool)” (level 1 mode) E5AK-AA2 AC100-240 E5AK-AA2 AC/DC24 5--33 E5AK CHAPTER 5 PARAMETERS Expansion Mode ST ST stable range Conditions of Use The input type must be set to temperature input, and the control must be standard control and advanced PID control. Function • When the “ST” parameter is set to “ON”, the self-tuning (ST) function is active. Dur- ing operation of the ST function, the power on the load side connected to the control output must be turned ON at the same time or before start of E5AK operation. • The “ST stable range” parameter sets the stable range width during self-tuning. However, note that this parameter cannot be used when the “ST” parameter is set to “OFF”. Parameter Setting Range Unit Default Comment ST ST stable range F Related article [ ]: ST function OFF/[ 0.1 to 999.9 ]: ST function ON None [ _C or _F 15.0 ] See Fuzzy self-tuning (page A-14) F Related parameters “Input type” (setup mode) “PID / ON/OFF” (expansion mode) a • Usually use the default value. Conditions of Use The control must be advanced PID con- trol, and ST must be set to OFF. Function • Sets advanced PID-control parameter a. Comment Setting Range 0.00 to 1.00 F Related parameter Unit None Default 0.65 5--34 See “PID / ON/OFF” (expansion mode) E5AK AT calculated gain • Usually use the default value. Expansion Mode Conditions of Use The control must be advanced PID con- trol, and ST must be set to OFF. Function • Sets the gain when adjusting the PID parameters by auto-tuning. • To give priority to response, decrease the set value of this parameter. To give priority to stability, increase the set value of this parameter. Comment Setting Range 0.1 to 10.0 F Related parameters Unit None Default 1.0 See Function Comment See “AT Execute/Cancel” (level 1 mode) “PID / ON/OFF” (expansion mode) Standby sequence reset method • Selects the conditions for enabling reset after the standby sequence of the alarm has been canceled. • Condition A: Control started (including power ON), and alarm value, input shift value or set point (except for changing SP mode or during Remote SP) changed. • Condition B: Power ON Setting Range Default 0: Condition A / 1: Condition B 0 F Related parameters “Alarm 1 type” “Alarm 2 type” “Alarm 3 type” (setup mode) 5--35 E5AK CHAPTER 5 PARAMETERS Expansion Mode Automatic return of display mode • If you do not operate any of the controller keys for the time set in this parameter when in levels 0 to 2 modes, the display automatically returns to the PV/SP display. Function • When this parameter is set to “0”, this function is disabled. • This parameter is invalid while the menu is displayed. Comment Setting Range 0 to 99 AT hysteresis Unit Second Default 0 Conditions of Use The control must be advanced PID con- trol, and ST must be set to OFF. Function • Usually use the default value. • The levels of limit cycle operations during AT execution are given hysteresis at event ON/OFF switching. This parameter sets this hysteresis width. Comment Setting Range 0.1 to 9.9 Unit %FS Default 0.2 LBA detection width Conditions of Use The LBA (Loop Break Alarm) function must be assigned as an output. Function • This parameter can be used when LBA is assigned as an output. • When the change width of the manipulated variable is below the width set in this parameter, the controller regards this as detection of an LBA. Comment 5--36 Setting Range 0.0 to 999.9 Unit %FS Default 0.2 E5AK Option Mode • The parameters in this mode can be used only when the “security” parameter (pro- tect mode) is set to “0” and “1”. • You can select this mode only when the option unit is set in the controller. In this mode, you can set the communications conditions, transfer output and event input parameters to match the type of option unit set in the controller. • To select this mode when in the levels 0 to 2, setup, expansion and calibration modes, press the key for 1 second minimum. The display changes to the menu display. If you select [ ] using the key then press the key for 1 second mini- mum, the controller enters the option mode. • To select parameters in this mode, press the key. To change parameter settings, use the or keys. • The following table shows the parameters supported in this mode and the page where the parameter is described. Symbol Parameter Name Multi-SP function Event input assignment 1 Event input assignment 2 Event input assignment 3 Event input assignment 4 Communication stop bit Communication data length Communication parity Communication baud rate Communication unit No. Transfer output type Transfer output upper limit Transfer output lower limit HBA latch Motor calibration Travel time PV dead band Remote SP enable Remote SP upper limit Remote SP lower limit SP tracking Page 5-38 5-39 5-39 5-39 5-39 5-40 5-40 5-40 5-40 5-40 5-41 5-41 5-41 5-42 5-42 5-43 5-43 5-44 5-44 5-44 5-45 5--37 E5AK CHAPTER 5 PARAMETERS Option Mode Multi-SP function Conditions of Use The event input function must be in use. Function • This parameter specifies the number of event inputs when switching set points (SP) 0 to 3. • When set to “0”, the set point cannot be switched by event input. • When this parameter is set to “1”, set points 0 and 1 can be used. When set to “2”, set points 0 to 3 can be used. Comment Setting Range 0 to 2 F Related article Unit None Default 2 5--38 See Model 4.3 How to Use Event Input (4-8) F Related parameter “Event input assignment 1” (option mode) F Option unit E53-AKB E5AK Event input assignment 1 Event input assignment 2 Option Mode Event input assignment 3 Event input assignment 4 Conditions of Use Event input other than the multi-SP func- tion must be specified when the event input function is in use. Function • When one E53-AKB unit is mounted, only “Event input assignment 3” and “Event input assignment 4” can be used. • This parameter specifies event input other than the multi-SP function. The following four functions can be specified: Run/Stop, Remote/Local, Auto/Manual, SP mode. The Remote/Local function can be used on E53-AK01/02/03 option units. The SP mode functions can be used only when the ”Remote SP enable” parameter is ON. • Event input (Run/Stop, Manual/Auto, and SP mode) is disabled while the menu is dis- played. It is also disabled in set up, expantion, option and calibration modes. Comment Symbol • Default Function Not specified Run/Stop Remote/Local Manual/Auto SP mode Event Input Operation Event input disabled ON: Stop/OFF: Run ON: Remote/OFF: Local ON: Manual/OFF: Auto ON: Remote SP/OFF: Local SP E53-AKB×1 E53-AKB×2 See Event input assignment 1 Event input assignment 2 Event input assignment 3 Event input assignment 4 F Related article 4.3 How to Use Event input (page 4-8) F Related parameters - - Model “remote SP enable” “multi-SP function” (option mode) F Option unit E53-AKB 5--39 E5AK CHAPTER 5 PARAMETERS Option Mode Communication stop bit Communication data length Communication parity Communication baud rate Communication unit No. Conditions of Use The communications function must be in use. Function • These parameters set the communications conditions. Make sure that the stop bit, data length, parity and baud rate of the host computer and the E5AK controller are matching. These parameters are valid when the power is turned ON again or when level 0 to 2 modes are switched. • When connecting two or more E5AK controllers to the host computer, set unit Nos. that will not conflict with the unit Nos. of other controllers. • “Communication stop bit” parameter Comment Setting Range 1, 2 Unit Bits Default 2 • “Communication data length” parameter Setting Range 7, 8 Unit Bits Default 7 • “Communication parity” parameter Setting Default [ ]: None/ [ ]:Even/[ ]:Odd [ ] • “Communication baud rate” parameter Setting Range Unit Default 1.2, 2.4, 4.8, 9.6, 19.2 kbps 9.6 • “Communication unit No.” parameter Setting Range 0 to 99 F Related article Unit None Default 0 5--40 See Model Chapter6 USING THE COMMUNICATIONS FUNCTION F Related parameter “Remote/Local” (level 2 mode) F Option unit E53-AK01/02/03 E5AK Transfer output type Transfer output upper limit Transfer output lower limit Option Mode Conditions of Use The transfer output function must be in use. Function • These parameters set the transfer output conditions. • The “transfer output type” parameter selects one of the following as the transfer out- put type, and assigns this to transfer output: Set point, Set point during SP ramp, Process value, Manipulated variable (heat) (standard type), Manipulated variable (cool) (This can selected only during heating and cooling control on a standard type controller.), Valve opening (position-propor- tional control) • The “transfer output upper limit” and “transfer output lower limit” parameters are used for scaling of transfer output. The setting range varies according to this output data. Also, a lower limit value larger than the upper limit value may be set. • During temperature input, the decimal point position of the set point, set point dur- ing SP ramp or process value is dependent on the currently selected sensor, and dur- ing analog input on the results of scaling. [ Transfer output Type ] Set point Transfer Output Lower Limit to Transfer Output Upper Limit Set point lower limit value to Set point upper limit value Comment [ [ [ [ [ ] Set point during SP ramp Set point lower limit value to Set point upper limit value ] Process value Scaling lower limit to scaling upper limit ] Manipulated variable (heat) -5.0% to 105.0% (Standard control), 0.0 to 105.0% (heating and cooling control) ] Manipulated variable (cool) 0.0% to 105.0% ] Valve opening -10.0 to 110.0% See Model • Default : [ ] • The output ranges of the set point, set point during SP ramp or process value when temperature input is selected are the ranges supported by the selected sensor. • When you have selected the “manipulated variable (heat)” parameter, the transfer output lower limit during heating and cooling control becomes “0.0”. F Related article 4.7 How to Use Transfer Output (page 4-17) F Option unit E53-AKF 5--41 E5AK CHAPTER 5 PARAMETERS Option Mode HBA latch Conditions of Use The HBA output function must be assigned. Function • When this parameter is set to ON, the heater burnout alarm is held until either of the following conditions is satisfied: a Set the heater burnout set value to “0.0”. b Reset the controller. (Turn the controller’s power OFF then back ON again.) Setting Range Default Comment [ ]: Enabled/[ F Related article ]: Disabled [ ] See Model Function Example of use See Model 5--42 4.5 How to Use the Heater Burnout Alarm (page 4-13) F Related parameters “Control output assignment 1” “Control output assignment 2” “Auxiliary output assignments 1” “Auxiliary output assignments 2” (setup mode) E5AK-AA2 AC100-240 E5AK-AA2 AC/DC24 Motor Calibration Conditions of Use The control must be position-proportion control. • Executes motor calibration. Be sure to execute this parameter when monitoring the valve opening. (Displays cannot be switched while motor calibration is being executed.) • The “travel time” parameter is also reset when this parameter is executed. • The default setting is “ ”. • Motor calibration is executed when “ ” is selected. • After motor calibration is completed, the setting automatically returns to “ ”. F Related article 4.1 Selecting the Control Method/Position-proportional Control (page 4-3) F Related parameter “Travel time” (option mode) E5AK-PRR2 AC100-240 E5AK-PRR2 AC/DC24 E5AK Travel Time Option Mode Conditions of Use The control must be position-proportion control. Function • Sets the time from valve fully opened to valve fully closed. • The travel time is automatically set when the “motor calibration” parameter is executed. Comment Setting Range 1 to 999 F Related article Unit Second Default 30 See Model Function 4.1 Selecting the Control Method/Position-proportional Control (page 4-3) F Related parameter “Motor Calibration” (option mode) E5AK-PRR2 AC100-240 E5AK-PRR2 AC/DC24 PV dead band Conditions of Use The control must be position-proportion control. • Sets a band within which valve will not move. Set point PV dead band Process value • This function is for use to reduce valve movement, but consequently reduces control performance within the PV deadband. • The decimal point is dependent on scaling. Comment Setting Range 0 to 9999 F Related parameters Unit EU Default 0 See Model “Input type” “Scaling upper limit” “Scaling lower limit” “Decimal point” (setup mode) E5AK-PRR2 AC100-240 E5AK-PRR2 AC/DC24 5--43 E5AK CHAPTER 5 PARAMETERS Option Mode Remote SP enable Conditions of Use ST must be OFF. Function • When this parameter is set to “ON”, the remote SP and local SP can be switched for use. (That is, to the SP mode can be specified.). Also, the “set point during SP ramp” parameter is enabled at all times. • When this parameter is set to “OFF”, only the local SP can be used. The set point dur- ing SP ramp is enabled only when the SP ramp function is enabled. Setting Range Default Comment [ ]: Enabled/[ F Related article ]: Disabled [ ] See Function 5--44 4.4 How to Use the Remote SP (page 4-11) F Related parameters “Set point during SP ramp” (level 0 mode) “SP mode” (level 2 mode) Remote SP upper limit Conditions of Use The remote SP function must be enabled. Remote SP lower limit • Sets the remote SP upper and lower limit values. The upper limit value is the equiva- lent to 20 mA, and the lower limit value is equivalent to 4 mA. Set the upper limit value in the “remote SP upper limit” parameter and the lower limit value in the “remote SP lower limit” parameter. RSP (%) Upper limit value Lower limit value Input (mA) 4 20 • When the “SP setting upper limit” or “SP setting lower limit” parameters are changed, the remote SP upper and lower limit values are forcibly changed to the SP setting upper and lower limit values. E5AK Option Mode Parameter Setting Range Unit Default Comment See Remote SP upper limit SP setting lower limit to SP setting upper limit Remote SP lower limit SP setting lower limit to SP setting upper limit F Related article 4.4 How to Use the Remote SP (page 4-11) F Related parameters “Decimal point” (setup mode) EU EU 1300 -200 “SP setting upper limit” “SP setting lower limit” (expansion mode) “Remote SP enable” (option mode) SP tracking enable Conditions of Use The remote SP function must be enabled. Function • Specifies the operation when the remote SP mode is switched to the local SP mode. • When this parameter is set to “ON”, the local SP is changed to the remote SP value used immediately before switching. • When this parameter is set to “OFF”, the local SP is not influenced by the remote SP. Setting Range Default Comment [ ]: Enabled/[ F Related article ]: Disabled [ ] See 4.4 How to Use the Remote SP (page 4-11) F Related parameters “Set point during SP ramp” (level 0 mode) “SP mode” (level 2 mode) 5--45 E5AK CHAPTER 5 PARAMETERS Calibration Mode • The parameters in this mode can be used only when the “security” parameter (pro- tect mode) is set to “0”. When selecting this mode for the first time after the E5AK has left the factory, return the “security” parameter to “0”. • This mode contains the parameters for user calibration of inputs and outputs. Only parameters relating to input types specified in the “input type” parameter (setup mode) can be used. Also, related output parameters can be used only when the com- munications unit (E53-AKF) is added on. • To select this mode when in the levels 0 to 2, setup, expansion and option modes, press the key for 1 second minimum. The display changes to the menu display. If you select [ ] using the key then press the key for 1 second minimum, 5--46 the controller enters the calibration mode. • For details on parameters in the calibration mode, see Chapter 7 Calibration. E5AK CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6 CHAPTER 6 USING THE COMMUNICATIONS FUNCTION This chapter mainly describes communications with a host computer and communications commands. 6.1 Outline of the Communications Function . . . . . . . . . . 6-2 Outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2 Transfer procedure . . . . . . . . . . . . . . . . . . . . . 6-2 Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-2 6.2 Preparing for Communications . . . . . . . . . . 6-3 Cable connections . . . . . . . . . . . . . . . . . . . . . . 6-3 Setting the communications specifications 6-4 6.3 Command Configuration . . . . . . . . . . . . . . . . 6-5 6.4 Commands and Responses . . . . . . . . . . . . . . 6-6 Reading/writing parameters . . . . . . . . . . . . . 6-6 Issuing special commands . . . . . . . . . . . . . . . 6-10 6.5 How to Read Communications Error Information . . . . . . . . . . . . . . . . . . . . . 6-12 End code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-12 Undefined error . . . . . . . . . . . . . . . . . . . . . . . . 6-13 6.6 Program Example . . . . . . . . . . . . . . . . . . . . . . 6-14 How to use programs . . . . . . . . . . . . . . . . . . . 6-14 Program list (language: IBM PC COMPATIBLE MACHINE) . . . . . 6-15 Examples of use . . . . . . . . . . . . . . . . . . . . . . . . 6-16 6--1 E5AK CHAPTER 6 USING THE COMMUNICATIONS FUNCTION 6.1 Outline of the Communications Function J Outline The communications function allows you to monitor and set E5AK parameters by a program prepared and running on a host computer con- nected to the E5AK controller. This chapter describes operations as viewed from the host computer. When using the communications function, the option unit for RS-232C, RS-422 or RS-485 communications must be added on. The E5AK commu- nications function allows you to carry out the following: • Reading/writing of parameters; • Operation instructions; and • Selecting the setting level. The communications function assumes the following conditions: • Writing of parameters is possible in during remote operation. Also, parameters cannot be written during execution of auto-tuning; • Writing parameters are provided with a setting level. Writing conditions are as follows depending on the setting level: Setting level 1: No restrictions Setting level 0: Writing of parameters in the setup, expansion and option modes only is prohibited. • For details on switching between setting levels, see page 6-11. • The “run/stop”, “remote/local” and “AT execute/cancel” parameters are set aside from other parameters as special commands for instructing operations. J Transfer The host computer sends a “command frame” to the controller, and the procedure controller returns a “response frame” corresponding to the content of the command sent by the host computer. In other words, a response frame is returned for each command frame sent. The following diagram shows command frame/response frame opera- tions. Host computer E5AK Command frame Response frame Command frame J Interface 6--2 The host computer carries out communications conforming to the RS-232C, RS-422 or RS-485 interface specifications. Option units supporting the RS-232C, RS-422 and RS-485 specifications are as follows: • Option units E53-AK01 (RS-232C) E53-AK02 (RS-422) E53-AK03 (RS-485) E5AK 6.2 Preparing for Communications 6.2 Preparing for Communications For details on wiring when using the communications, see Chapter 2 Prep- arations. J Cable connections F RS-232C • Only one controller can be connected to the host computer. • The cable length should not exceed 15 meters. • Use shielded twisted-pair cables (AWG28 or more) for the cables. 25 pins 9 pins E5AK E5AK IBM-PC/XT IBM-PC/AT DE-25 DE-25 Female Female DTE (SD) TXD (RD) RXD (RS) RTS (CS) CTS (DR) DSR (SG) COMMON (ER) DTR 2 3 4 5 6 7 20 RS-232C No. 20 SD 19 RD 18 SG DTE (RD) RXD (SD) TXD (ER) DTR (SG) COMMON (DR) DSR (RS) RTS (CS) CTS 2 3 4 5 6 7 8 RS-232C No. 20 SD 19 RD 18 SG FG 1 F RS-422 FG 1 • Up to 32 controllers including a computer can be connected to the host computer. • The total cable length should not exceed 500 meters. • Use shielded twisted-pair cables (AWG28 or more) for the cables. • Attach terminators to the controllers at both ends of a series of control- lers connected in an open configuration. For example, in the following configuration, connect the terminator to the host unit and unit No.30, and do not connect terminators to unit Nos.0 to 29. • Use terminators having a resistance of 240 W (1/2 W). The total resis- tance of both ends should be at least 100 W Host computer RS-422 RDA RDB SDA SDB SG FG Shielded cable E5AK (No.0) RS-422 No. 32 SDA 31 SDB 19 RDA 20 RDB 18 SG TerminatorX2 (240 W 1/2 W) E5AK (No.30) RS-422 No. 32 SDA 31 SDB 19 RDA 20 RDB 18 SG 6--3 E5AK CHAPTER 6 USING THE COMMUNICATIONS FUNCTION F RS-485 • Up to 32 controllers including a computer can be connected to the host computer. • The total cable length should not exceed 500 meters. • Use shielded twisted-pair cables (AWG28 or more) for the cables. • Attach terminators to the controllers at both ends of a series of control- lers connected in an open configuration. For example, in the following configuration, connect the terminator to the host unit and the unit No.30, and do not connect terminators to unit Nos.0 to 29. • Use terminators having a resistance of 120W (1/2 W). The total resis- tance of both ends should be at least 54W . Host computer RS-485 - + FG Shielded cable A < B : Mark A > B : Space





E5AK (No.0)
RS-485
No.
32 A
31 B
19 A
20 B





Terminator
(120W 1/2W)
E5AK (No.30)
RS-485
No.
32 A
31 B
19 A
20 B





J Setting the com-
munications
specifications







F Communications
parameters





Match the communications specifications of the host computer and E5AK
controller. When two or more controllers are connected to the host com-
puter, make sure that the communications specifications of all controllers
are the same.
This section describes how to set the communications specifications of the
E5AK controller. For details on the host computer, see the relevant manual
supplied with the host computer.


Set the communications specifications of the E5AK in the controller’s
communications parameters. The communications parameters are set on
the front panel of the E5AK controller.
The following table shows the communications parameters (option mode)
provided on the E5AK controller and their respective settings.


Parameter/Symbol
Unit No.




0 to 99


Setting




0 to 99


Set Value

Baud rate

1.2/2.4/4.8/9.6/19.2 (kbps) 1.2/2.4/4.8/ 9.6 /19.2

Bit length
Parity
Stop bit

7/8 (bit)
None/even/odd
1/2

7 /8

1/ 2


/


/




6--4

Inverted items are factory-settings.


E5AK








6.3 Command Configuration




6.3 Command Configuration




Command configuration is as follows and are paired with a response.



Command




@

2B 1B 2B
Unit Command
No. code

Command type

4B
Data

2B
FCS





*

2B


CR




Response
End code = 00





@


2B 1B 2B
Unit Command
No. code


2B
End
code

No data sections in the read commands.
4B 2B 2B
Data FCS
* CR





Response
End code = 00






@


• “@”

Command type

2B 1B 2B 2B
Unit Command End
No. code code

Command type



2B
FCS






*



2B


CR

The start character. This character must be inserted before the leading
byte.
• Unit No.
Specifies the “unit No.” of the E5AK. If there are two or more transmis-
sion destinations, specify the desired destination using “unit No.”
• Command type
Specifies the command type by codes “1” to “3”: parameter read, param-
eter write and special commands.
• Command code
Specifies the command for each command type. With parameter read/
write commands, this becomes the parameter No.
• Data
Specifies the set value or setting content. In the parameter read com-
mand, set dummy data “0000”. In the response, this is inserted only
when the end code is “00”.
• End code
Sets the communication results. For details on the types and meanings
of end codes, see 6.5 How to Read Communications Error Information
(page 6-12).
• FCS (Frame Check Sequence)
Set the frame check results from the start character to the data section.
For details on the frame check, see 6.6 Program Example (page 6-14).
• “*” “CR (Carriage Return) code”
Indicates the end (terminator) of the command or response block.





6--5


E5AK




CHAPTER 6 USING THE COMMUNICATIONS FUNCTION



6.4 Commands and Responses



This section describes commands and response in detail. The conventions
used in this section and data restrictions are as follows:
• Data is expressed in 1-byte units and in ASCII code.
• When the read or write data is a numerical value, the data to be set must
conform to the following conditions:
(1) The decimal point “.” is not indicated in fractions.
(2) The leftmost bit of minus numerical data must be expressed as
follows:
[example]
10.0=[0100], -150.0=[A500], -15=[F015]

J Reading/writing parameters
F Reading parameters
2B 2B 4B 2B 2B

Command


@

Unit
No.



1

Parameter
No.



X X X X

FCS



*



CR





Response


F Writing parameters





@


2B
Unit
No.



2B





1


2B
Parameter
No.



2B


2B
End
code









4B


4B
Read data




2B

X: Any value acceptable
2B 2B
FCS
* CR


2B

Command


@

Unit
No.


2B



2

Parameter
No.


2B

Write data



2B






4B

FCS



*



CR

2B






2B


Response


@

Unit
No.


2

Parameter
No.

End
code

Write data

FCS



*



CR





















6--6

Reading or writing of the parameters of a specified controller is executed.
• Writing is possible only during remote operation.
• Reading is impossible during executing auto-tuning.
• The following are set aside as special commands. For details, see page
6-10.
“run/stop”, “remote/local”, “AT execute/cancel”
• For details on parameters in each setting level, see the tables on pages
6-7 and 6-9.


E5AK




6.4 Commands and Responses





Parameter No.
00





Parameter
PV monitor





Data Setting and Monitor Range
*1 Scaling lower limit -10% to scaling upper limit +10% *2





Mode

86

04
42
24
14
01
10
11
12
13
02
03
41
19
20
21
22
09
87

23
06
43
07
08
17
18

SP monitor during SP *1
ramp
MV monitor (heat) *1
MV monitor (cool) *1
Remote SP monitor *1
Valve opening monitor *1
Set point
Set point 0
Set point 1
Set point 2
Set point 3
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time
Cooling coefficient
Dead band
Position-proportional dead
band
Manual reset value
Hysteresis (heat)
Hysteresis (cool)
Control period (heat)
Control period (cool)
Heater current monitor *1
Heater burnout alarm

SP lower limit to SP upper limit
-5.0 to 105.0
0.0 to 105.0
Scaling lower limit to scaling upper limit
-10.0 to 110.0
SP lower limit to set point upper limit
SP lower limit to SP upper limit
SP lower limit to SP upper limit
SP lower limit to SP upper limit
SP lower limit to SP upper limit
-1999 to 9999
-1999 to 9999
-1999 to 9999
0.1 to 999.9
0 to 3999
0 to 3999
0.01 to 99.99
-19.99 to 99.99
0.1 to 10.0
0.0 to 100.0
0.01 to 99.99
0.01 to 99.99
1 to 99
1 to 99
0.0 to 55.0
0.0 to 50.0



*3

















*4




L l



















Level 1

*1 Possible only during reading
*2 During temperature input, the range becomes the range of use of the selected sensor.
*3 During heating and cooling control, the range becomes 0.0 to 105.0.
*4 During position-proportional control, the range becomes 1 to 3999.
















About invalid
parameters
















Currently, if a command is used for invalid parameters (parameters that do not sat-
isfy the conditions of use in Chapter 5), the “undefined” error (end code: 1C) is out-
put.


6--7


E5AK




CHAPTER 6 USING THE COMMUNICATIONS FUNCTION




Parameter No. Parameter Data Setting Range
44 SP ramp time unit 0: Minutes, 1: Hours
45 SP ramp set value 0 to 9999
46 LBA detection time 0 to 9999









Mode

47
48
50
49
51
56
88
25
26
52
53
54
57
59
58
60
30
61
62
63
64
65
66
67
68
69
70
71

MV at stop
MV at PV error
MV upper limit
MV lower limit
MV change rate limit
Input digital filter
Open/close hysteresis
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 3 hysteresis
Input shift upper limit
Input shift lower limit
Input type
Scaling upper limit
Scaling lower limit
Decimal point
_C/_F selection
Control output 1 assignment
Control output 2 assignment
Auxiliary output 1 assignment
Auxiliary output 2 assignment
Alarm 1 type
Alarm 1 open in alarm
Alarm 2 type
Alarm 2 open in alarm
Alarm 3 type
Alarm 3 open in alarm
Direct/Reverse operation

-5.0 to 105.0
-5.0 to 105.0
MV lower limit +0.1 to 105.0
-5.0 to MV upper limit -0.1
0.0 to 100.0
0 to 9999
0.1 to 20.0
0.01 to 99.99
0.01 to 99.99
0.01 to 99.99
-199.9 to 999.9
-199.9 to 999.9
0 to 21
Scaling lower limit +1 to 9999
-1999 to scaling upper limit -1
0 to 3
0 : _C, 1 : _F
0 to 6
0 to 6
2 to 9
2 to 9
1 to 11
0: closed in alarm, 1: open in alarm
1 to 11
0: closed in alarm, 1: open in alarm
1 to 11
0: closed in alarm, 1: open in alarm
0: Reverse operation, 1: Direct operation

*1
*1
*2
*3












*4






*5
*5
*5
*5
*6


*6


*6







Level 2





















Setup

*1 During heating and cooling control, the range becomes -105 to 105.0. During position-proportional control, you can select between
*1 0: Hold/1: Open/2: Close. (Default is 0: Hold.)
*2 During heating and cooling control, the range becomes 0.0 to 105.0.
*3 During heating and cooling control, the range becomes -105.0 to 0.0
*4 See page 5-26.
*5 0: Control output (heat), 1: Control output (cool), 2: to 4: Alarms 1 to 3, 5: HBA, 6: LBA, 7 to 9: Errors 1 to 3
*6 See page 5-30.













6--8


E5AK




6.4 Commands and Responses





Parameter No.
28
27
72
73
34
35
85
37
36
93
55
74
77
78
79
81
80
82
89
38
29





Parameter
Set point upper limit
Set point lower limit
PID / ON/OFF
ST
ST stable range width
a
AT calculated gain
Standby sequence reset method
Automatic return of display mode
AT hysteresis
LBA detection width
Multi-SP function
Event input assignment 3
Event input assignment 4
Transfer output type
Transfer output upper limit
Transfer output lower limit
HBA latch
Travel time
PV dead band
Remote SP enable





Data Setting Range
*1 Set point lower limit +1 to scaling upper limit
*1 Scaling lower limit to Set point upper limit -1
0: Advanced PID, 1: ON/OFF
0 : OFF, 1 : ON
0.1 to 999.9
0.00 to 1.00
0.1 to 10.0
0, 1
0 to 99
0.1 to 9.9
0.0 to 999.9
0 to 2
- 1 to 3
- 1 to 3
0 to 5



0: OFF, 1: ON
1 to 999
0 to 9999
0: Enabled, 1: Disabled
















*2






*3
*3
*4
*4
*4





Mode







Expansion
















Option

91
90
39

Remote SP upper limit
Remote SP lower limit
SP tracking

SP setting lower limit to SP setting upper limit
SP setting lower limit to SP setting upper limit
0: OFF, 1: ON

*1 During temperature input, the range becomes the range of use of the selected sensor instead of the scaling upper/lower limit values
*2 See page 5-35.
*3 - -1: No specification, 0: Run/Stop, 1: Remote/Local, 2: Auto/Manual, 3: SP mode
*4 The following table shows the output ranges of the Transfer output lower and upper limits.



Transfer output Type
0: Set point


Transfer Output Lower Limit to
Transfer Output Upper Limit
Set point lower limit value to Set point upper limit value

1: Set point during SP ramp Set point lower limit value to Set point upper limit value

2: Process value

Scaling lower limit to scaling upper limit

3: Manipulated variable (heat) -5.0% to 105.0% (Standard control), 0.0 to 105.0% (heat-
ing and cooling control)
4: Manipulated variable (cool) 0.0% to 105.0%

5: Valve opening

-10.0 to 110.0%
















6--9


E5AK




CHAPTER 6 USING THE COMMUNICATIONS FUNCTION



J Issuing special commands
2B 2B










4B










2B










2B

Command

Unit Command
No. code

Instruction code FCS

@


2B

3


2B


2B


4B

*

CR
2B


2B


Response


@

Unit
No.


3

Command
code

End
code

Instruction code FCS



*



CR






































F Command List

The following functions are issued as special commands.
• Run/Stop (number of writings: 100000 operations)
Runs or stops programs. This command cannot be issued in setting level 1.
• Remote/Local (number of writings: 100000 operations)
Selects remote operation or local operation.
• RAM Write mode (number of writings: 100000 operations)
In the RAM mode, the local SP (set point and set points 0 to 3) are saved
to RAM, and in the backup mode, the local SP is saved to EEPROM.
• RAM data Save
When this command is issued, set points are saved to EEPROM.
• AT Execute/Cancel
Executes or cancels auto-tuning. This command cannot be issued in set-
ting level 1.
• SP mode (number of writings: 100000 operations)
Switches between local SP (LSP) and remote SP (RSP). This command
cannot be issued in setting level 1.
• Move to setting level 1
Issue this command when writing parameters in the setup, expansion
and option modes. On the E5AK, the parameter switches to the top
parameter “input type” of the setup mode, and control is stopped.
• Software reset
Resets E5AK operation by communications. A response is not returned
to this command. Also, communications with the E5AK cannot be car-
ried out for five seconds after reset.
• Status
Monitors the status of the E5AK. Two command groups are available,
A and B, depending on the command code. The response is returned in
bit units to the command code (4B) of the response frame. For details on
the monitoring details of each group, see page 6- -11.
Command No. Command Command Code

00
02
05
06
07
08

Run/Stop
Remote/Local
RAM write mode
RAM data save
AT Execute/Cancel
SP mode

0000: Run, 0001: Stop
0000: Local, 0001: Remote
0000: Backup, 0001: RAM
0000:
0000: Cancel, 0001: 40% AT execu-
tion, 0002: 100% AT execution
0000: LSP, 0001: RSP

09

Move to setting level 1 0000:








6--10

11
14

Software reset
Status

0000:
0000: A group, 0001: B group


E5AK








F A group




6.4 Commands and Responses

Bit

Description

[1]

[0]

0 Heating side output
1 Cooling side output
2 Alarm output 1
3 Alarm output 2
4 Alarm output 3
5 LBA output
6 HBA output
7 Run/Stop
8 Auto/Manual
9 Remote/Local
10 SP mode
11 Auto-tuning
12
13
14 Event input 3
15 Event input 4
*1 Always “OFF” at linear output

*3 ON
*4 ON
ON
ON
ON
ON
ON
Stop
Manual
Remote
RSP
AT exection


ON
ON

OFF
OFF
OFF
OFF
OFF
OFF
OFF
Run
Auto
Local
LSP
OFF


OFF
OFF

*1
*1
*2
*2
*2
*2
*2





F B group

*2 Always “OFF” when output is not assigned
*3 During position-proportional control, output is Open.
*4 During position-proportional control, output is Close.


Bit Description [1]
0 Setting level 1
1 RAM write mode RAM
2 Control output 1 type Linear
3 Control output 2 type Linear








0
Backup
Pulse
Pulse






[0]

4 EEPROM

RAM¸EEPROM RAM = EEPROM

5 Input error
6 A/D converter error
7 CT overflow
8 CT hold
9 Potentiometer error
10 RSP input error
11
12
13
14
15

ON
ON
ON
ON
ON
ON

OFF
OFF
OFF
OFF
OFF
OFF










About Setting Levels










To return to setting level 0 from setting level 1, issue the “software reset” command.
If the parameter write command is issued for the setup and expansion modes in set-
ting level 0, an error occurs, and the end code (0D = Command cannot be executed)
is returned.


6--11


E5AK




CHAPTER 6 USING THE COMMUNICATIONS FUNCTION



6.5 How to Read Communications Error Information



The result of communications on the E5AK can be checked by the end code in the response frame. Use this
end code to remedy errors that may occur.
J End code Communications are normal when the end code in the response is “00”.
If the end code is not “00”, this indicates that an error other that is not an
undefined error has occurred. The end code format is as follows and does
not contain a data area.




@

2B 1B 2B
Unit Command
No. code

2B
End
code

2B
FCS




*

2B


CR

Command type

End code 0D Code name Command cannot be executed

F Description





F Action

• Writing was carried out during local operation.
• Writing was carried out during executing auto-tuning.
• An attempt was made to execute 40%AT during heating and cooling con-
trol or position-proportional control.
• An attempt was made to switch run/stop in setting level 1.
• An attempt was made to execute AT in setting level 1.
• Issue the parameter read or write commands in conditions other than above.

End code 10 Code name Parity error

F Description
F Action

Parity check error was detected in the received data.
Check the communications condition. If the communications condition of
the host computer and E5AK controller match, then a probable cause is
a problem in the communications circuit of one or both of the host com-
puter and E5AK controller.


End code 11 Code name Framing error

F Description
F Action

Stop bit cannot be detected.
Check the communications condition. If the communications condition of
the host computer and E5AK controller match, then a probable cause is
a problem in the communications circuit of one or both of the host com-
puter and E5AK controller.



End code 13 Code name FCS error

F Description
F Action

About the unit No.




6--12

The FCS (Frame Check Sequence) do not match.
Check the FCS program.

Responses are not returned unless the target unit for communications and the unit
No. in the command match.


E5AK




6.5 How to Read Communications Error Information




End code 14 Code name Format error

F Description The received command length does not match the length defined in the
frame format.

F Action Check the communications condition. If the communications condition of
the host computer and E5AK controller match, then a probable cause is
a problem in the communications circuit of one or both of the host com-
puter and E5AK controller.


End code 15 Code name Setting range error

F Description Numerical values or code values in the data are not within the setting
range.

F Action Check the parameter and read or write data of special commands.


J Undefined error




@

2B
Unit
No.

2B


I C

2B
FCS





*

2B


CR


F Description



F Action


• An undefined header code has been received.
• A currently invalid parameter (e.g. the scaling command during temper-
ature input) has been received.

• Check the parameter No.



























6--13


E5AK




CHAPTER 6 USING THE COMMUNICATIONS FUNCTION



6.6 Program Example




J How to use programs
The program described below is for obtaining corresponding response frame data when
some of the command frame data is input.
The input format is as follows. The FCS and terminator are automatically generated,
and need not be input.




@

2B 1B 2B
Unit Command
No. code
Command type

4B
Data

2B
FCS





*

2B


CR


Input data


Automatically
generated


The output format is as follows. The content of the response frame is displayed as it is.




@

2B 1B 2B
Unit Command
No. code

2B
End
code

4B
Data

2B
FCS





*

2B


CR




F Procedure

Command type

(1) Read the program.
(2) Enter “RUN”.
(3) When “send data:” is displayed, enter the command data (from @ to the command
string).
(4) The content of the response frame is displayed following “receive data:”.

F Conditions when running a program
• Set the communications condition as follows:
Baud rate : 9600 bps
Bit length : 7 bits

Parity

: Even
















6--14

Stop bit : 2
• Make sure that the communications cable is properly connected.


E5AK




6.6 Program Example



J Program list (language: IBM PC COMPATIBLE MACHINE)



1000 ’
1010 ’ PROGRAM : E5AK Communication Program
1020 ’ For IBM PC COMPATIBLE MACHINE
1050 ’
1060 ’ RS-232C SPEED: 9600BPS, PARITY: EVEN, DATA: 7, STOP: 2
1070 OPEN ”COM: 9600, E, 7, 2, CD0, CS0, DS0, RB256, RS ”FOR RANDAM AS #1 LEN=256
1080 REPEAT
1090 ’ Make Command
1100 PRINT ”send data : ” ;
1110 INPUT SEND$
1120 ’ FCS calculation
1130 FCS=0
1140 FOR IFCS=1 TO LEN (SEND$)
1150 FCS=FCS XOR ASC (MID$ (SEND$, IFCS, 1))
1160 NEXT
1170 FCS$=RIGHT$ (”0”+HEX$ (FCS), 2)
1180 ’ Send data to communication port
1190 PRINT #1, SEND$+FCS$+”*”
1200 ’ Receive data from communication port
1210 RECCNT=0: TMP$=””
1220 DRECLOOP:
1230 IF LOC (1) <> 0 THEN DREC1
1240 RECCNT=RECCNT+1
1250 IF RECCNT=5000 THEN *DRECERR ELSE DRECLOOP
1260 ‘DREC1
1270 TMP$=TMP$+INPUT$ (LOC (1), #1)
1280 IF RIGHT$ (TMP&, 1)=CHR$ (13) THEN DRECEND
ELSE RECCNT=0: GOTO DRECLOOP
1290 DRECERR:
1300 TMP$=”No response !!”
1310 DRECEND:
1320 RECV$=TMP$
1330 PRINT ”response: ”; RECV$
1340 ’ Repeat to make Command
1350 ’ GOTO REPEAT
1360 ’ END
1370 CLOSE #1
1380 END












6--15

E5AK




CHAPTER 6 USING THE COMMUNICATIONS FUNCTION



J Examples of use
F Set the unit No. to “00”
• In the following examples, data is shown in individual blocks to make the examples
easier to understand. However, when actually creating programs, do not leave spaces
between frame items. Also, response are displayed without spaces between frame
items.

F Set the set point to “300.0”
• Input data
@ 00 2 01 3000
300.0
Set point
Write parameter
• Response
@ 00 2 01 00 3000 (FCS) *
Normal end

F Start running
• Input data
@ 00 3 00 0000
Run
Run/Stop
Special command
• Response
@ 00 3 00 00 0000 (FCS) *
Normal end

F Monitor process value
• Input data
@ 00 1 00 0000
Dummy data
Monitor process value
Read parameter
• Response
@ 00 1 00 00 2000 (FCS) *
Process value = 2000
Normal end










6--16

E5AK









7
CHAPTER 7
CALIBRATION




CHAPTER 7 CALIBRATION




This chapter describes procedures for each calibration operation.
Read this chapter only when the controller must be calibrated.












7.1 Structure of Parameters












. . . . . . . . . . . . . . . . 7-2

7.2 Calibrating Thermocouple
7.3 Calibrating Platinum
Resistance Thermometer
7.4 Calibrating Current Input

. . . . . . . . . . . . . . 7-4

. . . . . . . . . . . . . . . 7-7
. . . . . . . . . . . . . . 7-9

7.5 Calibrating Voltage Input . . . . . . . . . . . . . . . 7-10
7.6 Checking Indication Accuracy . . . . . . . . . . . 7-12

































7--1


E5AK




CHAPTER 7 CALIBRATION



7.1 Structure of Parameters



• To calibrate the E5AK controller, select [














] in the menu display to

select the calibration mode. [

] is displayed.

• However, note that [

] may not be displayed on the menu display

when, for example, the user is calibrating the E5AK controller for the

first time. If this happens, [

] is displayed by changing the “secu-

rity” parameter (protect mode) to “0”.
• The parameters in the calibration mode are configured as follows.

Platinum resistance
Thermocouple thermometer Current input Voltage input



Thermocouple 1














Transfer output



Thermocouple 2















Only when transfer
output function is
supported



0 to 5V 1 to 5V 0 to 10V
















Thermocouple 1 : K1/J1/L1/E/N/W/PLII
Thermocouple 2 : K2/J2/L2/R/S/B/T/U
Platinum resistance

Data save

thermometer

: JPt100/Pt100




• To select the desired parameter, press the
played in the following order:




key. Parameters are dis-

Calibration of inputs ® Calibration of transfer output ®
Saving of calibration data
If the E5AK controller does not support the transfer output function,
calibration of transfer output is automatically deleted from the calibra-
tion procedure as follows:
Calibration of inputs ® Saving of calibration data
• Only inputs that have been set in the “input type” parameter (setup
mode) can be calibrated. To temporarily save data for each of the calibra-

tion parameters, press the

key for 1 second.

• Transfer output can be calibrated only when the communications unit
(E53-AKF) is set in the controller. To adjust data items, press the

or

keys.








7--2

• The data save menu is displayed only when all calibration items have
temporarily been saved.
• After calibrating input, you must always check indication accuracy. For
details, see page 7-12.


E5AK








F Calibration item
menu
Calibration item
parameter
Process value




F Calibration save
mark



calibration save mark




7.1 Structure of Parameters



• Parameters are displayed on the No.1 display, and the process value is
displayed in Hexadecimal on the No.2 display.
• Normally, the process value changes by several digits. The process value
flashes, for example, when a sensor error causes the process value to
stray from the calibration target range.
• When the process value display is flashing, the process value is not saved
as data even if the key is pressed.

• Once the E5AK controller has been calibrated by the user, [ ] is pre-
ceded by the “.” mark when the calibration mode is selected.






















































7--3

E5AK




CHAPTER 7 CALIBRATION



7.2 Calibrating Thermocouple



• Calibrate according to the type of thermocouple, thermocouple 1 group
(K1, J1, L1, E, N, W, PLII) and thermocouple 2 group (K2, J2, L2, R, S,
B, T, U).
• When calibrating, do not cover the bottom or top of the controller. Also,
do not touch the input terminals (Nos. 11 and 12) and compensating con-
ductor on the E5AK controller.

F Preparations
AC100-240V ~
(AC/DC24V )

SOURCE

10
9
8
7
6
5
4
3
2
1
















DMM

30
29
28
27
26
25
24
23
22
21

31 32










33

20
19
18
17
16
15
14
13
12
11















Compensating
conductor







STV

Cold junction
compensator
0_C/32_F


















Connecting the
Cold Junction Con-
ductor

• Set the cold junction compensator to 0_C. However, make sure that
internal thermocouples are disabled (tips are open).
• In the above figure, STV refers to a standard DC current/voltage source,
and DMM refers to a precision digital multimeter.
However, note that DMM is required only when the transfer output
function is supported.
• Use the compensating conductor selected thermocouple. However, note
that when thermocouple R, S, E, B, W or PLII is used, the cold junetion
compensator and the compensating conductor can be substituted with
the cold junction compensator and the compensating conductor for
thermocouple K.


Correct process values cannot be obtained if you touch the contact ends of the com-
pensating conductor during calibration of a thermocouple. Accordingly, short
(enable) or open (disable) the tip of the compensating conductor inside the cold junc-
tion compensator as shown in the figure below to create a contact or non-contact
state for the cold junction compensator.
Cold junction Cold junction
compensator compensator
Short
E5AK E5AK

control er

0°C/32°F

control er

0°C/32°F

Open





7--4


Compensating conductor


Compensating conductor


E5AK








F Calibration:
thermocouple 1




7.2 Calibrating Thermocouple



This example describes how to calibrate a thermocouple when the transfer
output function is supported. If the transfer output function is not sup-
ported, skips steps (7) to (10).
(1) When [ ] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) First, calibrate the main input. Press the key to display [ ]
(50mV calibration display). Set STV output to 50mV. When the value
on the No.2 display has stabilized (changes of several digits max.),
press the key to temporarily save the calibration data.
(3) Press the key to display [ ] (0mV calibration display). Set
STV output to 0mV. When the value on the No.2 display has stabilized
(changes of several digits max.), press the key to temporarily save
the calibration data.
(4) Next, calibrate the cold junction compensator. Press the key to
display [ ] (310mV calibration display). Set STV output to
310mV. When the value on the No.2 display has stabilized (changes of
several digits max.), press the key to temporarily save the calibra-
tion data.
(5) Press the key to display [ ] (0mV calibration display). Set
STV output to 0mV. When the value on the No.2 display has stabilized
(changes of several digits max.), press the key to temporarily save
the calibration data.
(6) Finally, calibrate the bias compensation value. Disconnect the STV,
and enable the thermocouple of the cold junction compensator. When
carrying this out, make sure that the wiring on the STV is discon-
nected.
Make sure that the cold junction compensator is set to 0_C and press
the key. The display changes to [ ] (calibration display for the
bias compensation value). When the value on the No.2 display has sta-
bilized (changes of several digits max.), press the key to tempo-
rarily save the calibration data.
(7) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (11). Press the key. The dis-
play changes to [ ] (20mA calibration display).
(8) Set the output to 20mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “20mA”.
(9) Press the key. The display changes to [ ] (4mA calibration
display).
(10) Set the output to 4mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “4mA”.
(11) Press the key until the display changes to the data save display.
Press the key. The No.2 display changes to [ ], and two
seconds later the calibration data is saved to internal memory. If you
press the key when the No.2 display reads [ ], the calibration
data is invalidated.
(12) This completes calibration of the thermocouple 1 group. Press the
key to return the display to [ ].


7--5

E5AK




CHAPTER 7 CALIBRATION



F Calibration:
thermocouple 2
































































7--6








This example describes how to calibrate a thermocouple when the transfer
output function is supported. If the transfer output function is not sup-
ported, skips steps (7) to (10).
(1) When [ ] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.
(2) First, calibrate the main input. Press the key to display [ ]
(20mV calibration display). Set STV output to 20mV. When the value
on the No.2 display has stabilized (changes of several digits max.),
press the key to temporarily save the calibration data.
(3) Press the key to display [ ] (0mV calibration display). Set
STV output to 0mV. When the value on the No.2 display has stabilized
(changes of several digits max.), press the key to temporarily save
the calibration data.
(4) Next, calibrate the cold junction compensator. Press the key to
display [ ] (310mV calibration display). Set STV output to
310mV. When the value on the No.2 display has stabilized (changes of
several digits max.), press the key to temporarily save the calibra-
tion data.
(5) Press the key to display [ ] (0mV calibration display). Set
STV output to 0mV. When the value on the No.2 display has stabilized
(changes of several digits max.), press the key to temporarily save
the calibration data.
(6) Finally, calibrate the bias compensation value. Disconnect the STV,
and enable the thermocouple of the cold junction compensator. When
carrying this out, make sure that the wiring on the STV is discon-
nected.
Make sure that the cold junction compensator is set to 0_C and press
the key. The display changes to [ ] (calibration display for
the bias compensation value). When the value on the No.2 display has
stabilized (changes of several digits max.), press the key to tempo-
rarily save the calibration data.
(7) Next, calibrate the transfer output function. If the transfer output
function is not supported, skip to step (11). Press the key. The dis-
play changes to [ ] (20mA calibration display).
(8) Set the output to 20mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “20mA”.
(9) Press the key. The display changes to [ ] (4mA calibration
display).
(10) Set the output to 4mA by the or keys while monitoring the
voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “4mA”.
(11) Press the key until the display changes to the data save display.
Press the key. The No.2 display changes to [ ], and two
seconds later the calibration data is saved to internal memory. If you
press the key when the No.2 display reads [ ], the calibration
data is invalidated.
(12) This completes calibration of the thermocouple 2 group. Press the
key to return the display to [ ].

E5AK




7.3 Calibrating Platinum Resistance Thermometer



7.3 Calibrating Platinum Resistance Thermometer



F Preparation
AC100-240V~
(AC/DC24V )

SOURCE

10 30
9 29
8 28
7 27
6 26
5 25
4 24
3 23
2 22
1 21


DMM

31 32










33

20
19
18
17
16
15
14
13
12
11











6-dial









F Calibration

• Use leads of the same thickness when connecting to the platinum resis-
tance thermometer.
• In the above figure, 6-dial refers to a precision resistance box, and DMM
stands for a digital multimeter. However, note that the DMM is required
only when the transfer output function is supported.
• Connect (short) the leads from terminal Nos. 11 and 12.
This example describes how to calibrate a platinum resistance thermome-
ter when the transfer output function is supported. If the transfer output
function is not supported, skips steps (7) to (10).
(1) When [ ] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.

(2) First, calibrate the main input. Press the

key to display [

]

(300W calibration display). Set the 6-dial to 300W. When the value on
the No.2 display has stabilized (changes of several digits max.), press

the

key to temporarily store the calibration data.

Short terminal
Nos.11 to 13

(3) Press the

key to switch [

] (0W calibration) display. Short






Change wiring.

terminal No. 11 to 13. When the value on the No.2 display has stabi-
lized (changes of several digits max.), press the key to temporarily
store the calibration data.
(4) Next, calibrate the B-B’ input. Change the wiring as follows.
15
14
13

12
11

6-dial


Short terminal
Nos.11 to 13

Make the connection across terminals 11 and 12 and the 6-dial as
short as possible. Short terminals 11 and 13.

(5) Press the

key to display [

] (10W calibration display). Set the

Cont’d on next page

6-dial to 10W.. When the value on the No.2 display has stabilized
(changes of several digits max.), press the key to temporarily
store the calibration data.

7--7


E5AK




CHAPTER 7 CALIBRATION



From previous page









(6) Press the









key to display [









] (0W calibration display, Short ter-

minal Nos. 11 to 13. When the value on the No.2 display has stabilized

(changes of several digits max.), press the
store the calibration data.

key to temporarily

(7) Next, calibrate the transfer output function. If the transfer output

function is not supported, skip to step (11). Press the
play changes to [ ] (20mA calibration display).

key. The dis-

(8) Set the output to 20mA by the

or

keys while monitoring the

voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “20mA”.

(9) Press the
display).

key. The display changes to [

] (4mA calibration

(10) Set the output to 4mA by the

or

keys while monitoring the

voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “4mA”.

(11) Press the

key until the display changes to the data save display.

Press the

key. The No.2 display changes to [

], and two

seconds later the calibration data is saved to internal memory. If you

press the

key when the No.2 display reads [

], the calibration

data is invalidated.
(12) This completes calibration of the platinum resistance thermometer.






































7--8

Press the

key to return the display to [

].


E5AK








7.4 Calibrating Current Input




7.4 Calibrating Current Input




F Preparation




AC100-240V~
(AC/DC24V )
SOURCE






10
9
8
7
6
5
4
3
2
1




















DMM






30 31 32 20
29 19
28 18
27 17
26 16
25 15
24 14
23 13
22 12
21 33 11
+

STV















-

F Calibration

• In the above figure, STV refers to a standard DC current/voltage source,
and DMM refers to a precision digital multimeter. However, note that
the DMM is required only when the transfer output function is sup-
ported.
This example describes how to calibrate a current input when the transfer
output function is supported. If the transfer output function is not sup-
ported, skips steps (4) to (7).
(1) When [ ] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.

(2) Press the

key. The display changes to [

] (20mA calibration

display). Set the STV output to 20mA. When the value on the No.2 dis-
play has stabilized (changes of several digits max.), press the key
to temporarily store the calibration data.

(3) Press the

key. The display changes to [

] (0mA calibration

display). Set the STV output to 0 mA. When the value on the No.2 dis-
play has stabilized (changes of several digits max.), press the key
to temporarily store the calibration data.
(4) Next, calibrate the transfer output function. If the transfer output

function is not supported, skip to step (8). Press the
play changes to [ ] (20mA calibration display).

key. The dis-

(5) Set the output to 20mA by the or

keys while monitoring the

voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “20mA”.

(6) Press the
display).

key. The display changes to [

] (4mA calibration

(7) Set the output to 4mA by the

or

keys while monitoring the

voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “4mA”.

(8) Press the

key until the display changes to the data save display.

Press the

key. The No.2 display changes to [

], and two

seconds later the calibration data is saved to internal memory. If you

press the

key when the No.2 display reads [

], the calibration

data is invalidated.
(9) This completes calibration of current input. Press the
return the display to [ ].


key to



7--9


E5AK




CHAPTER 7 CALIBRATION



7.5 Calibrating Voltage Input



F Preparation
AC100-240V~
(AC/DC24V )
10

















30

















31 32

















20

SOURCE

9
8
7
6
5
4
3
2
1














DMM

29
28
27
26
25
24
23
22
21










33

19
18
17
16
15
14
13
12
11






+


-










STV







F Calibration:
0 to 5 V, 1 to 5 V

• In the above figure, STV refers to a standard DC current/voltage source,
and DMM refers to a precision digital multimeter. However, note that
the DMM is required only when the transfer output function is sup-
ported.
This example describes how to calibrate voltage input when the transfer
output function is supported. If the transfer output function is not sup-
ported, skips steps (4) to (7).
(1) When [ ] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.

(2) Press the

key. The display changes to [

] (5 V calibration dis-

play). Set the STV output to 5V. When the value on the No.2 display

has stabilized (changes of several digits max.), press the
temporarily store the calibration data.

key to

(3) Press the

key. The display changes to [

] (0V calibration dis-

play). Set the STV output to 0V. When the value on the No.2 display

has stabilized (changes of several digits max.), press the
temporarily store the calibration data.

key to

(4) Next, calibrate the transfer output function. If the transfer output

function is not supported, skip to step (8). Press the
play changes to [ ] (20mA calibration display).

key. The dis-

(5) Set the output to 20mA by the

or

keys while monitoring the

voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “20mA”.

(6) Press the
display).

key. The display changes to [

] (4mA calibration

(7) Set the output to 4mA by the

or

keys while monitoring the




Cont’d on next page

7--10

voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “4mA”.


E5AK




7.5 Calibrating Voltage Input




From previous page




(8) Press the
Press the




key until the display changes to the data save display.
key. The No.2 display changes to [ ], and two

seconds later the calibration data is saved to internal memory. If you

press the

key when the No.2 display reads [

], the calibration

data is invalidated.
(9) This completes calibration of voltage input (0 to 5V, 1 to 5V). Press the

key to return the display to [

].








F Calibration :
0 to 10V








This example describes how to calibrate voltage input when the transfer
output function is supported. If the transfer output function is not sup-
ported, skips steps (4) to (7).
(1) When [ ] is displayed, the 30-minute timer is displayed on the
No.2 display and counts down. This timer serves as a guide for the
aging time when aging is required.

(2) Press the

key. The display changes to [

] (10V calibration

display). Set the STV output to 10V. When the value on the No.2 dis-

play has stabilized (changes of several digits max.), press the
to temporarily store the calibration data.

key

(3) Press the

key. The display changes to [

] (0V calibration dis-

play). Set the STV output to 0V. When the value on the No.2 display

has stabilized (changes of several digits max.), press the
temporarily store the calibration data.

key to

(4) Next, calibrate the transfer output function. If the transfer output

function is not supported, skip to step (8). Press the
play changes to [ ] (20mA calibration display).

key. The dis-

(5) Set the output to 20mA by the

or

keys while monitoring the

voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “20mA”.

(6) Press the
display).

key. The display changes to [

] (4mA calibration

(7) Set the output to 4mA by the

or

keys while monitoring the

voltage on the digital multimeter. In the example on the left, the dis-
play indicates that the value two digits smaller than before calibra-
tion is “4mA”.

(8) Press the

key until the display changes to the data save display.

Press the

key. The No.2 display changes to [

], and two

seconds later the calibration data is saved to internal memory. If you

press the

key when the No.2 display reads [

], the calibration

data is invalidated.
(9) This completes calibration of voltage input (0 to 10V). Press the

key to return the display to [

].




7--11


E5AK




CHAPTER 7 CALIBRATION



7.6 Checking Indication Accuracy



• After calibrating input, make sure that you check indication accuracy to
make sure that the E5AK controller has been correctly calibrated.
• Operate the E5AK controller in the PV/SP monitor (level 0 mode) mode.
• Check the indication accuracy at the upper and lower limits and mid-
point.

F Thermocouple • Preparation
The following figure shows the required device connection. Make sure
that the E5AK controller and cold junction compensator are connected
by a compensating conductor for the input type that is to be used during
actual operation.
AC100-240V ~
(AC/DC24V )

SOURCE

10 30
9 29
8 28
7 27
6 26
5 25
4 24
3 23
2 22
1 21



• Operation

31 32










33

20
19
18
17
16
15
14
13
12
11














Compensation
conductor








Cold junction
compensator












STV




F Platinum resis-
tance thermome-
ter

Make sure that the cold junction compensator is at 0_C, and set STV out-
put to the voltage equivalent to the starting power of the check value.

• Preparation
The following figure shows the required device connection.
AC100-240V ~
(AC/DC24V )

SOURCE












• Operation

10
9
8
7
6
5
4
3
2
1

30
29
28
27
26
25
24
23
22
21

31 32










33

20
19
18
17
16
15
14
13
12
11











6-dial




7--12

Set the 6-dial to the resistance equivalent to the check value.


E5AK








F Current input








• Preparation




7.6 Checking Indication Accuracy

The following figure shows the required device connection.
AC100-240V~
(AC/DC24V )

SOURCE
















• Operation

10 30
9 29
8 28
7 27
6 26
5 25
4 24
3 23
2 22
1 21

31 32










33
+

STV

20
19
18
17
16
15
14
13
12
11










-



F Voltage input

Set the STV to the current value equivalent to the check value.

• Preparation
The following figure shows the required device connection.
AC100-240V ~
(AC/DC24V )

SOURCE

10 30
9 29
8 28
7 27
6 26
5 25
4 24
3 23

31 32

20
19
18
17
16
15
14
13








+





• Operation

2
1

22
21


33

12
11


-


STV

Set the STV to the voltage value equivalent to the check value.




















7--13


E5AK




CHAPTER 7 CALIBRATION






































































7--14

E5AK









8
CHAPTER 8




CHAPTER 8 TROUBLESHOOTING

TROUBLESHOOTING



This chapter describes how to find out and remedy the cause if the E5AK
does not function properly.











8.1 Initial Checks . . . . . . . . . . . . . . . . . . . . . . . . . . 8-2
8.2 How to Use the Error Display . . . . . . . . . . . 8-3
8.3 How to Use Error Output . . . . . . . . . . . . . . . 8-5

8.4 Checking Operation Restrictions

. . . . . . . . 8-6




































8--1


E5AK




CHAPTER 8 TROUBLESHOOTING



8.1 Initial Checks



If trouble occurs, first of all check the following.
(1) Power supply
Make sure that the power supply is ON. Also, make sure that the
power supply is within the rated voltage range.
(2) Wiring
Make sure that all cables are properly connected.
(3) Communications condition
When communicating using the RS-232C, RS-422 or RS-485 commu-
nications interfaces, make sure that the baud rate and other commu-
nications condition settings on the host computer and E5AK control-
ler are matching, and are within the permissible ranges.

If there appears to be nothing wrong after checking the E5AK controller,
and the same phenomenon continues, check the controller in more detail,
for example, on the error display.








































8--2

E5AK








8.2 How to Use the Error Display




8.2 How to Use the Error Display















F Meaning

F Action




When an error has occurred, the No.1 display alternately indicates error
codes together with the current display item.
This section describes how to check error codes on the display, and the
actions you must be taken to remedy the problem.


Input error

Input is in error.

Check the wiring of inputs, disconnections, and shorts, and check the in-
put type.


F Operation at
error


For control output functions, output the manipulated variable matched to
the setting of the “MV at PV error” parameter (level 2 mode). Alarm out-
put functions are activated when the upper limit is exceeded.






F Meaning

F Action



Memory error

Internal memory operation is in error.

First, turn the power OFF then back ON again. If the display remains the
same, the E5AK controller must be repaired. If the display is restored to
normal, then a probable cause can be external noise affecting the control
system. Check for external noise.


F Operation at
error


Control output functions turn OFF (2mA max. at 4 to 20mA output, and
output equivalent to 0% in case of other outputs). Alarm output functions
turn OFF.






F Meaning

F Action



A/D converter error

Internal circuits are in error.

First, turn the power OFF then back ON again. If the display remains the
same, the E5AK controller must be repaired. If the display is restored to
normal, then a probable cause can be external noise affecting the control
system. Check for external noise.


F Operation at
error


Control output functions turn OFF (2mA max. at 4 to 20mA output, and
output equivalent to 0% in case of other outputs). Alarm output functions
turn OFF.

8--3


E5AK




CHAPTER 8 TROUBLESHOOTING




Calibration data error

This error is output only during temperature input, and is displayed for
two seconds when the power is turned ON.

F Meaning Calibration data is in error.

F Action Must repair.

F Operation at Both control output functions and alarm output functions operate. How-
error ever, note that readout accuracy is not assured.



Display range over


F Meaning Though not an error, this is displayed when the process value exceeds the
display range when the control range (setting range ±10%) is larger than
the display range (-1999 to 9999).
• When less than “-1999” [ ]
• When greater than “9999” [ ]

F Operation Control continues, allowing normal operation.


Motor calibration error (Displayed on the No. 2 Display)


F Meaning Motor calibration has ended with an error.

F Action First, correctly connect the wiring for the potentiometer, open output, and
close output.
Execute the motor calibration again.

F Operation proce-
dure







F Operation at When motor calibration is executed, open output will operate and then
error close output will operate. However, as the value is incorrect, the result
turns out to be an error.

8--4

E5AK








8.3 How to Use Error Output




8.3 How to Use Error Output











F LBA













F Input errors




F A/D converter
error




F Remote SP input
error




The E5AK controller allows you to assign error output to terminals as out-
puts.
For details on output assignments, see 3.3 Setting Output Specifications
(page 3-6).

• LBA (Loop Break Alarm) can be used as a means for detecting loop
breaks when the control loop is not functioning normally. For details, see
page 4-15.
• LBA allows you to detect the following errors:
(1) Heater burnout
(2) Output error (contact weld, damaged transistors, etc.)
(3) Sensor error (constant input values, etc.)
• If you use the LBA function, set the loop break detection time matched
to the control characteristics in the “LBA detection time” parameter
(level 2 mode).

• If you assign error 1 as the output, an error can be output to auxiliary
output 1 or auxiliary output 2 when input is in error. When this error
occurs, remedy by following the description for “Input error” (page 8-3).

• If you assign error 2 as the output, an error can be output to auxiliary
output 1 or auxiliary output 2 when the A/D converter is in error. When
this error occurs, remedy by following the description for “A/D converter
error” (page 8-3).

• If you assign error 3 as the output, an error can be output to auxiliary
output 1 or auxiliary output 2 when the remote SP input error occurs
while the remote SP function is enabled. For details on error displays
and meanings, see Chapter 4 Applied Operation/4.4 How to Use the
Remote SP (page 4-11).
• When an error occurs, check the state of the remote SP connection. If the
lead is broken or disconnected, the remote SP scaling lower limit is dis-
played blinking on the PV/SP display or remote SP monitor display.

















8--5


E5AK




CHAPTER 8 TROUBLESHOOTING



8.4 Checking Operation Restrictions



With the E5AK controller, auto-tuning or self-tuning sometimes do not
operate depending on the way functions are combined. The table below
summarizes the main operating restrictions.
If the E5AK controller is not operating properly, first check whether oper-
ating conditions violate the restrictions in this table.

Inoperable or Invalid Functions
Restriction


At analog input

ST Execution AT Execution Limiter Function
¢

Other

At heating and
cooling control
At position-pro-
portional control
At ON/OFF
control
ST = ON

At AT execution
At stop

¢

¢

¢



-
¢

40%AT

40% AT

¢

¢


¢



Manipulated variable ON/OFF control

Manipulated variable
MV change rate
Manipulated variable SP ramp function
MV change rate
MV change rate Parameter setting
Manipulated variable
MV change rate






































8--6

Items marked by a “x” indicates combinations of conditions not acceptable during ST or AT execution.
Items marked by “--” are impossible combinations.


E5AK











APPENDIX





















SPECIFICATIONS




APPENDIX






























. . . . . . . . . . . . . . . . . . . . . . . . . A-2

ABOUT CURRENT TRANSFORMER (CT) . . . A-5

CONTROL BLOCK DIAGRAM

. . . . . . . . . . . . . . A-6

SETTING LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8
MODEL LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-11

PARAMETER OPERATIONS LIST

. . . . . . . . . . A-12

FUZZY SELF-TUNING

. . . . . . . . . . . . . . . . . . . . . A-14

X FORMAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-17
ASCII CODE LIST . . . . . . . . . . . . . . . . . . . . . . . . . . A-20





























A--1


E5AK




APPENDIX



SPECIFICATIONS



J Ratings

AC100-240V type
Supply Voltage AC100-240V , 50/60 Hz
Power Consumption 16VA
Oprating Voltage Range 85% to 110% of rated supply voltage

















AC/DC24V type
AC/DC24V , 50/60Hz
12VA, 8W


Main Input


Sub-Input

Control Output
Auxiliary Output
Control Method
Setting Method
Indication Method
Other Functions

Thermocouple : K, J, T, E, L, U, N, R, S, B, W, PLII
Platinum resistance thermometer : JPt100, Pt100
Voltage input : 4 to 20mA, 0 to 20mA (Input impedance 150W)
Current input : 1 to 5V, 0 to 5V, 1 to 10V (Input impedance 1MW)
CT input: E54-CT1, E54-CT3
Potentiometer: 100Ω to 2.5kΩ
Remote SP input: 4 to 20mA (Input impedance 150Ω)
According to output unit (see “Output Unit Ratings and Characteristics”)
SPST-NO, 3A at 250 VAC (resistive load)
Advanced PID or ON/OFF control
Digital setting using front panel keys
7-segment digital display, Bar graph and LEDs
According to option unit (see ”Option Unit Ratings and Characteristics”)

*1, *2

Ambient Temperature Operating : -10°C to 55°C (with no icing)/3-year warranty period: -10°C to 50°C

Ambient Humidity

Storage : -25°C to 65°C (with no icing)
35% to 85%

*1 Thermocouple W is W/Re5-26.
*2 The following table shows the setting ranges and indication ranges for each of the inputs.

Input Setting Range




Indication Range

JPt100
Pt100
K1

-199.9 to 650.0(_C) /-199.9 to 999.9(_F)
-199.9 to 650.0(_C) /-199.9 to 999.9(_F)
-200 to 1300(_C) /-300 to 2300(_F)

-199.9 to 735.0(_C) /-199.9 to 999.9(_F)
-199.9 to 735.0(_C) /-199.9 to 999.9(_F)
-350 to 1450(_C) /-560 to 2560(_F)

K2

0.0 to 500.0(_C)

/0.0 to 900.0(_F)

-50.0 to 550.0(_C) /-90.0 to 990.0(_F)

J1

-100 to 850(_C)

/-100 to 1500(_F)

-195 to 945(_C)

/-260 to 1660(_F)

J2

0.0 to 400.0(_C)

/0.0 to 750.0(_F)

-40.0 to 440.0(_C) /-75.0 to 825.0(_F)

T

-199.9 to 400.0(_C) /-199.9 to 700.0(_F)

-199.9 to 460.0(_C) /-199.9 to 790.0(_F)

E
L1

0 to 600(_C)
-100 to 850(_C)

/0 to 1100(_F)
/-100 to 1500(_F)

-60 to 660(_C)
-195 to 945(_C)

/-110 to 1210(_F)
/-260 to 1660(_F)

L2

0.0 to 400.0(_C)

/0.0 to 750.0(_F)

-40.0 to 440.0(_C) /-75.0 to 825.0(_F)

U
N

-199.9 to 400.0(_C) /-199.9 to 700.0(_F)
-200 to 1300(_C) /-300 to 2300(_F)

-199.9 to 460.0(_C) /-199.9 to 790.0(_F)
-350 to 1450(_C) /-560 to 2560(_F)

R
S

0 to 1700(_C)
0 to 1700(_C)

/0 to 3000(_F)
/0 to 3000(_F)

-170 to 1870(_C) /-300 to 3300(_F)
-170 to 1870(_C) /-300 to 3300(_F)

B

100 to 1800(_C)

/300 to 3200(_F)

-70 to 1970(_C)

/10 to 3490(_F)

W
PLII

0 to 2300(_C)
0 to 1300(_C)

/0 to 4100(_F)
/0 to 2300(_F)

-230 to 2530(_C) /-410 to 4510(_F)
-130 to 1430(_C) /-230 to 2530(_F)








A--2

4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
0 to 10V

One of following ranges depending on results of
scaling
-1999 to 9999
-199.9 to 999.9
-19.99 to 99.99
-1.999 to 9.999

-10 to 110% of setting range. Note, however that
max. value is -1999 to 9999


E5AK








J Characteristics











Thermocouple:




SPECIFICATIONS



Indication Accuracy




Hysteresis
Proportional Band (P)
Integral (reset) Time (I)

(±0.3% of indication value or ± 1°C, whichever greater) ± 1 digit max. (*1)
Platinum resistance thermometer:
(±0.2% of indcation value or± 0.8°C whichever greater)± 1 digit max.
Analog input: ±0.2%± 1 digit max.
CT input: 5%FS 1 digit max.
Potentiometer: 5%FS 1 digit max.
Remote SP: 0.2%FS 1 digit max.
0.01 to 99.99%FS (in units of 0.01%FS)
0.1 to 999.9% FS (in units of 0.1%FS)
0 to 3999 s (in units of 1 second)












(*2)

Derivative (rate) Time (D) 0 to 3999 s (in units of 1 second)

Control Period
Manual Reset Value
Alarm Setting Range
Sampling Period
Insulation Resistance
Dielectric Strength

1 to 99 s (in units of 1 second)
0.0 to 100.0% (in units of 0.1%)
-1999 to 9999 or -199.9 to 999.9 (decimal point position dependent on input type
or result of scaling)
Temperature input: 250 ms, Analog input: 100 ms, Sub-input : 1s
20 MW min. (at 500 VDC)
2000 VAC, 50/60Hz for 1 min (between terminals of different polarities)

Vibration

Malfunction 10 to 55 Hz, 10 m/s2 (approx.1G) for 10 min each in X, Y, and Z directions

Resistance Destruction 10 to 55 Hz, 20 m/s2 (approx.2G) for 2hrs each in X, Y, and Z directions


Shock Resis-

Malfunction 200 m/s2min. (approx.20G), 3 times each in 6 directions (100 m/s2 (approx.10G)

tance

tance

applied to the relay)
Destruction 300 m/s2 min. (approx.30G), 3 times each in 6 directions

Weight

Enclosure Ratings

Memory Protection

Approx. 450 g, mounting bracket: approx. 65 g
Front panel: NEMA4 for indoor use (equivalent to IP66)
Rear case: IEC standard IP20
Terminals: IEC standard IP00
Non-volatile memory (number of writings:100000 operations)

*1The indication accuracy of the K1, T, and N thermocouples at a temperature of -100°C or less is ±2°C ±1 digit maximum. The
indication accuracy of the U, L1 and L2 thermocouples at any temperature is ±2°C ±1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400°C or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200°C or less is ±3°C ±1 digit maximum.
The indication accuracy of the W thermocouple is ±1 digit max. of whichever is the greater of ±0.3% or ±3°C of the indicated
value.
The indication accuracy of the PLII thermocouple is ±1 digit max. of whichever is the greater of ±0.3% or ±2°C of the indicated
value.
*2On a position-proportional control type, 1 to 3999.
F Heter Burnout Alarm

Max. heater current

Single-phase 50 A VAC (see note 1)

Heater current value display accuracy 5%FS 1 digit max.

Heater burnout alarm setting range
Min. detection ON time

0.1 to 49.9 A (in units of 0.1 A) see note 2)
190 ms (see note 3)

Note: 1. Use the K2CU-FVVA-VGS (with gate input terminals) for the detection of three-phase heater burnout.
2. The heater burnout alarm is always OFF if the alarm is set to 0.0A and always ON if the alarm is set to 50.0A.
3. No heater burnout detection or heater current value measurement is possible if the control output (heat) is ON for less
than 190ms.





A--3


E5AK




APPENDIX



J Output Unit Ratings and Characteristics
Ratings and characteristics conform to the output unit mounted on the
controller. For details on the ratings of the output unit, see page 2--9.
The relay output unit is already mounted on the E5AK-PRR2. When
replacing the output unit, use the E53-R.

J Option Unit Ratings and Characteristics

Contact input ON: 1 kW max., OFF: 100 kW min.
Event inputs
No-contact input ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mAmax.
Interface :RS-232C, RS-422 or RS-485
Transmission method :Half-duplex


















































A--4

Communications


Transfer output

Synchronization method :Start-stop synchronization (asynchronous method)
Baud rate :1.2/2.4/4.8/9.6/19.2 kbps
4 to 20 mA, Permissible load impedance: 600 W max. Resolution: Approx. 2600


E5AK




ABOUT CURRENT TRANSFORMER (CT)



ABOUT CURRENT TRANSFORMER (CT)



F Specifications
Item Specifications

Type

E54-CT1

E54-CT3

Max.continuous current 50A
Dielectric Strength AC 1000V (1min)
Vibration Resistance 50Hz, 98m/s2 [10G]

120A (*1)

Weight
Accessory

Approx. 11.5g
-

Approx. 50g
Armature (2)
Plug (2)



F Dimensions

*1 The maximum continuous current of the E5AK is 50 A.

E54-CT1



















E54-CT3






























j

21
15









40




30


30






f5.8




















f12














2-f3.5

2.8





















f2.36












30






2-M3 depth 4

















A--5


E5AK




APPENDIX



CONTROL BLOCK DIAGRAM



J Standard type

Temperature
input

Digital filter

Input shift
Set point
limiter


SP mode
LSP
SP ramp


RSP

















Analog input


Digital filter

Scaling


Input type


Process
value

RSP enable




ON/OFF
control

Process/function

Control

Data



















D



Control mode


PID control


MV change
rate limiter

MV limiter











Error


Stop


Manual

Control method




ON/OFF control
3-position control
Heating Cooling
side side















MV at
PV error

MV at stop


Manual MV

































D



Control mode


PID control


MV change
rate limiter

MV limiter

Dead band
Heating Cooling
side side

























Error


Stop


Manual










A--6

DStop

Manipulated
variable at
heating side

DStop

Manipulated
variable at
cooling side


E5AK








J Position-proportional type








Set point
limiter


SP mode
LSP



RSP
RSP enable







Process/function

Control
























SP ramp












Open side











Temperature
input

Digital filter


Input shift










PID control


MV change
rate limiter

Position-
proportional
dead band




CONTROL BLOCK DIAGRAM






Analog input


Digital filter


Scaling


Input type


Process
value












Close side


Data


Error


Stop


Manual


Open
output


Operation at
PV error

Operation at
stop

Manual
operation


Error


Stop


Manual


Close
output




































A--7


E5AK




APPENDIX



SETTING LIST


Mode Parameter Name
Security
Protect
[A/M] key protect
Manual Manual MV












Setting Range
0 to 6
ON/OFF
-5.0 to 105.0
















*1












Unit Default
None 1
None OFF
% 0.0












Remarks












Setting

Level 0

Set point
Run/Stop
AT Execute/Cancel

Set point lower limit to Set point upper limit EU
Run/Stop None
OFF/AT-1/AT-2 None

0
RUN
OFF During running













Level 1

Set point 0
Set point 1
Set point 2
Set point 3
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time

Set point lower limit to Set point upper limit
Set point lower limit to Set point upper limit
Set point lower limit to Set point upper limit
Set point lower limit to Set point upper limit
-1999 to 9999
-1999 to 9999
-1999 to 9999
0.1 to 999.9
0 to 3999
0 to 3999

EU
EU
EU
EU
EU
EU
EU
%FS
sec
sec

0
0
0
0
0
0
0
10.0
233
40

Multi-SP
Multi-SP
Multi-SP
Multi-SP

Cooling coefficient

0.01 to 99.99

None

1.00 At heating and

Dead band

-19.99 to 99.99

%FS

cooling control
0.00 At heating and

Position-proportional
dead band
Manual reset value
Hysteresis (heat)
Hysteresis (cool)

0.1 to 10.0
0.0 to 100.0
0.01 to 99.99
0.01 to 99.99

%
%
%FS
%FS

cooling control
2.0 At position-propor-
tional control
50.0
0.10
0.10 At heating and

Control period (heat)

1 to 99

sec

20

cooling control

Control period (cool)
Heater burnout
Remote/Local
SP mode
SP ramp time unit
SP ramp set value

1 to 99
0.0 to 50.0
RMT/LCL
RSP/LSP
M(Minutes) / H(Hours)
0 to 9999

sec
A
None
None
None
EU
20
At heating and
cooling control
0.0 Heater burnout
detection
LCL Communications
unit setting
LSP
M
0






Level 2

LBA detection time
MV at stop
MV at PV error
MV upper limit
MV lower limit
MV change rate limit
Input digital filter
Open/close hysteresis
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 3 hysteresis
Input shift upper limit
Input shift lower limit

0 to 9999
-5.0 to 105.0
-5.0 to 105.0
MV lower limit + 0.1 to 105.0
-5.0 to MV upper limit -0.1
0.0 to 100.0
0 to 9999
0.1 to 20.0
0.01 to 99.99
0.01 to 99.99
0.01 to 99.99
-199.9 to 999.9
-199.9 to 999.9

*1
*1
*2
*3

Sec
%
%
%
%
%/sec
sec
%
%FS
%FS
%FS
°C/°F
°C/°F

0
0.0
0.0
105.0
-5.0
0.0
0
0.8
0.02
0.02
0.02
0.0 Temperature input
0.0 Temperature input

*1 During heat and cooling control, the lower limit becomes -105.0%.
During position-proportional control, the setting becomes HOLD, OPEN or CLOS.
*2 During heat and cooling control, the setting range becomes 0.0 to 105.0%.
*3 During heat and cooling control, the setting range becomes -105.0 to 0.0%.

A--8


E5AK




SETTING LIST





Mode





Parameter Name
Input type





Setting Range
0 to 21





Unit Default
None 2





Remarks





Setting

Scaling upper limit

Scaling lower limit +1 to 9999 *4

EU

-100 Analog input

Scaling lower limit
Decimal point

-1999 to SP setting upper limit -0.1 *4
0 to 3

EU
None

0
0

Analog input
Analog input

_C/_F selection
Parameter initialize

_C/_F
Yes/No

None
None

_C Temperature input
NO

Control output 1 assignment Heat/Cool/Alarm 1/Alarm 2/Alarm 3

None HEAT

/HBA/LBA
Control output 2 assignment Heat/Cool/Alarm 1/Alarm 2/Alarm 3

None

AL-1

/HBA/LBA
Auxiliary output 1 assignment Alarm 1/Alarm 2/Alarm 3/HBA/LBA/

None

AL-2

Setup

S.ERR/E333/RSER
Auxiliary output 2 assignment Alarm 1/Alarm 2/Alarm 3/HBA/

None

AL-3

Alarm 1 type

LBA/S.ERR/E333/RSER
1 to 11

None

2

Output assignment
needed

Alarm 1 open in alarm

N-O/N-C

None

N-O Output assignment

Alarm 2 type

1 to 11

None

2

needed
Output assignment
needed

Alarm 2 open in alarm

N-O/N-C

None

N-O Output assignment

Alarm 3 type

1 to 11

None

2

needed
Output assignment
needed

Alarm 3 open in alarm

N-O/N-C

None
N-O
Output assignment
needed

Direct/Reverse operation
Set point upper limit

OR-R/OR-D
Set point lower limit +1 to scaling

None OR-R
None 1300 *4

upper limit

*2

Set point lower limit

Scaling lower limit to Set point upper

None

-200 *4




Expan-
sion




E
sion

PID/ON/OFF
ST
ST stable range
a
AT calculated gain
Standby sequence reset set-
ting method
Automatic return of display
mode
AT hysteresis
LBA detection width

limit -1
PID / ON/OFF
OFF/ON
0.1 to 999.9
0.00 to 1.00
0.1 to 10.0
0/1
0 to 99
0.1 to 9.9
0.0 to 999.9

*2

None
None
°C/°F
None
None
None
Sec
%FS
%FS

PID
OFF
15.0 ST=ON
0.65
1.0
0
0
0.2
0.2

*4 When temperature input is selected, the sensor range selected in the “input type” parameter (setup mode) corresponds to the scal-
ing upper and lower limit value.























A--9


E5AK




APPENDIX




Mode














Option









Parameter Name
Multi-SP function
Event input assignment 1
Event input assignment 2
Event input assignment 3
Event input assignment 4
Communication stop bit
Communication data length
Communication parity
Communication baud rate
Communication unit No.
Transfer output type
Transfer output upper limit
Transfer output lower limit
HBA latch
Motor calibration
Travel time
PV dead band
Remote SP enable
Remote SP upper limit
Remote SP lower limit
SP tracking









Setting Range
0 to 2
NON/STOP/RMT/MAN/RSP
NON/STOP/RMT/MAN/RSP
NON/STOP/RMT/MAN/RSP
NON/STOP/RMT/MAN/RSP
1/2
7/8
None/Even/Odd
1.2/2.4/4.8/9.6/19.2
0 to 99
SP/SP-M/PV/O/C-O/V-M
*5
*5
ON/OFF
ON/OFF
1 to 999
0 to 9999
ON/OFF
SP setting lower limit to SP setting
upper limit
SP setting lower limit to SP setting
upper limit
ON/OFF









Unit Default
None 0
None NON
None NON
None STOP
None MAN
bits 2
bits 7
None EVEN
kbps 9.6
None 0
None SP
*5 *5
*5 *5
None OFF
None OFF
Sec 1
EU 0
None OFF
EU 1300
EU -200
None OFF









Remarks









Setting

*5 Set the transfer output type parameter according to the following table.


SP

Transfer Output Type
:Set point

Transfer Output Lower Limit to Transfer Output Upper Limit
Set point lower limit to Set point upper limit

SP-M :Set point during SP ramp Set point lower limit to Set point upper limit

PV
O

:Process value
:Manipulated variable
(heat)

Scaling lower limit to scaling upper limit
-5.0 to 105.0%

C-O :Manipulated variable
(cool)
V-M :Value opening
D Default : SP

0.0 to 105.0%

-10.0 to 110.0%
























A--10

D The output ranges of the SP setting, set point or process value when temperature input is selected are the ranges supported
by the selected sensor.
D When the heating side manipulated variable or cooling side manipulated variable is selected, the transfer output lower limit in
a heating and cooling control becomes “0.0”.


E5AK








MODEL LIST


Description
Base unit













Type Name
E5AK-AA2 AC100-240















Standard model













Specification




MODEL LIST

E5AK-AA2-500 AC100-240
E5AK-AA2 AC/DC24
E5AK-AA2-500 AC/DC24
E5AK-PRR2 AC100-240

Standard model with terminal cover
Standard model
Standard model with terminal cover
Position-proportional model

E5AK-PRR2-500 AC100-240 Position-proportional model with terminal cover




Option unit






Output unit











Terminal cover

E5AK-PRR2 AC/DC24
E5AK-PRR2-500 AC/DC24
E53-AKB
E53-AK01
E53-AK02
E53-AK03
E53-AKF
E53-R
E53-S
E53-Q
E53-Q3
E53-Q4
E53-C3
E53-C3D
E53-V34
E53-V35
E53-COV0809

Position-proportional model
Position-proportional model with terminal cover
Event input
Communication (RS-232C)
Communication (RS-422)
Communication (RS-485)
Transfer output
Relay
SSR
Pulse (NPN) DC12V
Pulse (NPN) DC24V
Pulse (PNP) DC24V
Linear (4 to 20mA)
Linear (0 to 20mA)
Linear (0 to 10V)
Linear (0 to 5V)
for E5AK




























A--11


E5AK




APPENDIX



PARAMETER OPERATIONS LIST


• Switching to modes other than manual or protect mode is carried out by mode selection in the menu
display.
• The figure below shows all parameters in the order that they are displayed. Some parameters are
not displayed depending on the protect mode setting and conditions of use.
Power ON
A/M
1 second min. 1 second min.
Level 0 mode Manual mode


1 second min.


1 second min.


1 second min.



Level 1 mode


Level 2 mode


Setup mode






A/M +
1 second min.


A/M
1 second min.


A/M +
1 second min.















Level 0

PV/SP
Remote SP monitor


1 second min.


1 second min.


1 second min.


Expansion
mode

Option mode

Calibration
mode




Level 1

AT Execute/Cancel
Set point 0

Protect mode

A/M +
1 second min.


Parameters in a mode can be
switched by the key. The param-
eter following the last parameter is the
top parameter.



Level 2

Remote/Local
SP mode

Set point during SP ramp
MV monitor (heat)
MV monitor (cool)
Valve opening monitor
Run/Stop

Manual mode

Manual MV

Protect mode

Security
[A/M] key protect








A--12

Set point 1
Set point 2
Set point 3
Alarm value 1
Alarm value 2
Alarm value 3
Proportional band
Integral time
Derivative time
Cooling coefficient
Dead band
Position- proportional dead band
Manual reset value
Hysteresis (heat)
Hysteresis (cool)
Control period (heat)
Control period (cool)
Heater current monitor
Heater burnout

SP ramp time unit
SP ramp set value
LBA detection time
MV at stop
MV at PV error
MV upper limit
MV lower limit
MV change rate limit
Input digital filter
Open/close hysteresis
Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 3 hysteresis
Input shift upper limit
Input shift lower limit


E5AK




PARAMETER OPERATIONS LIST





Setup mode

Input type
Scaling upper limit
Scaling lower limit
Decimal point
_C/_F selection
Parameter initialize
Control output 1 assignment
Control output 2 assignment
Auxiliary output 1 assignment
Auxiliary output 2 assignment
Alarm 1 type
Alarm 1 open in alarm
Alarm 2 type
Alarm 2 open in alarm
Alarm 3 type
Alarm 3 open in alarm
Direct/Reverse operation









Calibration
mode





Expansion
mode

Set point upper limit
Set point lower limit
PID / ON/OFF
ST
ST stable range
a
AT calculated gain
Standby sequence reset method
Automatic return of display mode
AT hysteresis
LBA detection width





Option mode

Multi-SP function
Event input assignment 1
Event input assignment 2
Event input assignment 3
Event input assignment 4
Communication stop bit
Communication data length
Communication parity
Communication baud rate
Communication unit No.
Transfer output type
Transfer output upper limit
Transfer output lower limit
HBA latch
Motor calibration
Travel time
PV dead band
Remote SP enable
Remote SP upper limit
Remote SP lower limit
SP tracking



Thermocouple Platinum resistance Current input



Voltage input


Thermocouple 1 Thermocouple 2











Transfer
output

thermometer


0 to 5V 1 to 5V 0 to 10V





Data save

Only when transfer output
function is supported

Thermocouple 1
Thermocouple 2
Platinum resistance
thermometer

: K1/J1/L1/E/N/W/PLII
: K2/J2/L2/R/S/B/T/U
: JPt100/Pt100











A--13


E5AK




APPENDIX



FUZZY SELF-TUNING


Fuzzy self-tuning is a function that enables the E5AK to calculate the most
suitable PID constants for the controlled object.

J Features
• The E5AK determines by itself when to perform fuzzy self-tuning.
• At the time of fuzzy self-tuning, the E5AK does not output any signal
that disturbs the temperature or output value.

J Fuzzy Self- tuning Function
The fuzzy self-tuning function has three modes.
In SRT(step response tuning) mode, the PID constants are tuned
using a step response method at the time the set point is changed.
In DT(disturbance tuning) mode, the PID constants are amended
so that the controlled temperature will be within the target range
set in advance when there is external disturbance.
In HT(hunting tuning) mode, when hunting occurs, the PID
constants are amended to suppress the hunting.
Note: Be sure to turn on the power supply to the load either before or si-
multaneously with the start of Temperature Controller operation.
Dead time will be measured from the time the Temperature Con-
troller starts operating. If a load such as a heater is turned on after
the Temperature Controller is turned on, dead time longer than the
actual value will be measured and inappropriate PID constants will
be obtained. If an extremely large amount of dead time is measured,
the control amount will be set to 0% for a short period of time before
being returned to 100%, and the constants will then be returned.
Retuning is performed only for large amounts of dead time, so be
sure to follow the precaution given above when starting operation.

F Startup SRT will start if the following conditions are satisfied simultaneously
Conditions of when the E5AK is turned on or the set point is changed.

SRT

At the time the E5AK starts operation
1) The set point at the time the E5AK
starts operating is different from the
set point used at the time SRT was
last executed (see note).
2) The process value at the time the
E5AK starts operating is smal er than
the set point in reverse operation and
larger than the set point in normal
operation.

At the time set point is changed
1) The new set point is different from the
set point used at the time SRT was
executed last (see note).
2) The process value is in stable condi-
tion before the set point is changed.
3) A larger set point value is set in
reverse operation and a smal er set
point is set in normal operation.







A--14

Note: The last SRT-executed set point is set to 0 before shipping and when
changing from advanced PID control to advanced PID control with
fuzzy self-tuning.


E5AK








F PID Constant
Refreshing
Conditions




FUZZY SELF-TUNING



If the step control amount is applied before the maximum temperature
slope (R) is obtained, SRT will not renew any PID constant. If the propor-
tional band obtained from the R and L values that were measured before
the imposition had been completed is larger than the present proportional
band, the PID constants will be renewed because the measured value is in
the direction towards the suitable proportional band value, and the set
point at that time will be the SRT-executed set point.
Slope (R)
Temperature
Stable range
SP










Time


F Stable Temperature Status
If the temperature is within the stable range for a certain time, it is deemed
that the temperature is stable. This time is called stability judgement time.
Like PID constants, stability judgement time is adjusted with fuzzy self-
tuning according to the characteristics of the object to be controlled. Fuzzy
self-tuning will not be activated if the temperature is stable because the
Temperature Controller deems that temperature control is smooth.
Shorter than the stability judgement time


Stable range
Set point
Stable range
(Set to 15.0_C
before shipping)
Stability judgement time






F Balanced Status


Stable


Stable

If the process value is within the stable range for 60s when there is no out-
put,it is deemed that the temperature is balanced.










A--15


E5AK




APPENDIX



F Startup Conditions of DT
(1) DT will start if the temperature that has been stable varies due to ex-
ternal disturbance and the deflection of the temperature exceeds the
stable range, and then the temperature becomes stable, provided that
the number of maximum temperature values is less than four.
(2) DT will start if the set point is changed under the condition that SRT
does not start and the temperature becomes stable, provided that the
number of maximum temperature values is less than four. If there are
four or more maximum temperature values, HT will start.



Temperature

SP












F Startup Conditions of HT

Extreme value 2







Extreme value 1

Set point change
















Time

HT will be ON when there is hunting with four or more maximum temper-
ature values(extreme values) while SRT is not being executed.



Temperature

SP











Extreme
value 1

Extreme value 2









Extreme
value 3



Time

Extreme value 4
















A--16

Note: In specific applications where temperature varies periodically due
to disturbance, internal parameters need to be adjusted.


E5AK








X FORMAT










J Format




X FORMAT








The E5AK controller supports communications in the X format.
Some of the data, such as unit, may differ with the E5AX/EX series.
For details on commands and setting range, see Chapter 5 Parameters and
Chapter 6 Using the Communications Function.

Commands are structured as follows and are paired with a response.




F Command




F Response





@




@


2B
Unit
No.


2B
Unit
No.


2B
Header
code


2B
Header
code


2B
Data
code


2B
End
code


4 to 8B
Data



4 to 8B
Data


2B
FCS



2B
FCS





*




*


2B


CR

2B


CR

• “@”
The start character. This character must be inserted before the lead-
ing byte.
• Unit No.
Specifies the “unit No.” of the E5AK. If there are two or more trans-
mission destinations, specify the desired destination using “unit
No.”
• Header code/Data code
Specifies the command type. For details on the command type, see
page A-18.
• Data
Specifies the set value or setting content. The data length varies
according to the command.
• End code
Sets the communication results. For details on the types and mean-
ings of end codes, see 6.5 How to Read Communications Error
Information (page 6-12).
• FCS (Frame Check Sequence)
Set the frame check results from the start character to the data sec-
tion. For details on the frame check, see 6.6 Program Example (page
6-14).
• “*” “CR (Carriage Return) code”
Indicates the end (terminator) of the command or response block.








A--17


E5AK




APPENDIX



J X FORMAT HEAD LIST

Header Code Data Code Command Content











R/W











Data











Remarks

AP 01 AT cancel

Write None

AS
IC
MB
MA
ME
MW

R%

RB
RN
RV
RC
RD

RI

01
-
01
01
01
01
01
02
03
01
01
01
01
01
01
02

AT start
Undefined error
Remote/Local
RAM write mode
Backup mode
RAM data batch save
Alarm value 1 read
Alarm value 2 read
Alarm value 3 read
Proportional band read
Integrated time read
Derivative time read
Cooling coefficient read
Dead band read
Input shift upper limit read
Input shift lower limit read

Write None
- None
Write 4B

Write None





Read 4B




Read 4B

Read 4B


Error response















During heating and cooling
control

RL
RO
RS
RX

01
01
01
01

SP setting limit read
Manipulated variable read
Set point read
Process value read

Read

Read

Read

8B

4B

8B

Upper-and lower-limit batch
read



with status

































A--18

RW
RZ
Rb


W%

WB
WN
WV
WC
WD

WI

WS
WW

01
01
01
01
02
03
01
01
01
01
01
01
02
01
01

Heater burnout set value read Read
Heater current read
Read
Valve opening read
Alarm value 1 write
Alarm value 2 write
Alarm value 3 write
Write
Proportional band write
Integrated time write
Derivative time write
Cooling coefficient write
Write
Dead band write
Input shift upper limit write
Input shift lower limit write
Write
Set point write
Heater burnout set value write

4B

8B




4B




4B



4B



with status










During heating and cooling
control


E5AK








F RX (process value read) command status
2B 2B
Unit FCS










2B




X FORMAT

Command

@

No.


2B

R X 0 1


2B




4B

*

CR




4B




2B




2B


Response


@

Unit
No.


Bit


R


X

End
code


Content

Process value





“1”

Status

FCS



“0”



*



CR

0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15

Run/Stop
Setting level
Input error
A/D converter error
LBA
HBA

EEPROM
Alarm 1
Alarm 2
Alarm 3
AT
RAM mode
Auto/Manual
SP mode
Remote/Local

Stop
1
ON
ON
ON
ON

RAM¸EEPROM
ON
ON
ON
AT execution
RAM mode
Manual
Remote SP
Remote

Run
0
OFF
OFF
OFF
OFF

RAM=EEPROM
OFF
OFF
OFF
OFF
Backup mode
Auto
Local SP
Local





















































A--19


E5AK




APPENDIX



ASCII CODE LIST


Hex 0













1













2













3













4













5













6













7













Upper 4 bits


0

Bin
0000

0000 0001 0010 0011 0100 0101 0110 0111
SP 0 @ P p



























































A--20

1
2
3
4
5
6
7
8
9
A
B
C
D
E
F

0001
0010
0011
0100
0101
0110
0111
1000
1001
1010
1011
1100
1101
1110
1111


Lower 4 bits

!

#
$
%
&

(
)
*
+
,
-
.
/

1
2
3
4
5
6
7
8
9
:
;
< = >
?

A
B
C
D
E
F
G
H
I
J
K
L
M
N
O

Q
R
S
T
U
V
W
X
Y
Z
[
¥
]
^
_

a
b
c
d
e
f
g
h
i
j
k
l
m
n
o

q
r
s
t
u
v
w
x
y
z
{
|
}
~
DEL


E5AK




INDEX



Symbols
[A/M] key protect . . . . . . . . . . . . . . . . . . . . 5--4
° C/° F selection . . . . . . . . . . . . . . . . . . . . . 5--28
Numbers
100%AT . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--16
40%AT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--16
A
A group . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--11
A/D converter error . . . . . . . . 3--6, 8--3, 8--5
A/M key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--3
A/M key protect . . . . . . . . . . . . . . . . . . . . . 3--12
About Calibration . . . . . . . . . . . . . . . . . . . 1--11
ABOUT CURRENT
TRANSFORMER (CT) . . . . . . . . . . . A--5
About invalid parameters . . . . . . . . . . . . . 6--7
About parameter display . . . . . . . . . . . . . . 5--2
About PID Parameters . . . . . . . . . . . . . . 3--17
About the Communications Function . 1--10
About the Decimal Point
of the Alarm Value . . . . . . . . . . . . . . . 3--11
About the displays . . . . . . . . . . . . . . . . . . . 1--3
About the power blocks . . . . . . . . . . . . . . 2--10
About the temperature unit . . . . . . . . . . . 3--4
About the unit No. . . . . . . . . . . . . . . . . . . 6--12
Adjusting Control Operation . . . . . . . . . 3--14
Alarm 1 hysteresis . . . . . . . . . . . . . . . . . . 5--24
Alarm 1 open in alarm . . . . . . . . . . . . . . . 5--31
Alarm 1 type . . . . . . . . . . . . . . . . . . . . . . . 5--30
Alarm 2 hysteresis . . . . . . . . . . . . . . . . . . 5--24
Alarm 2 open in alarm . . . . . . . . . . . . . . . 5--31
Alarm 2 type . . . . . . . . . . . . . . . . . . . . . . . 5--30
Alarm 3 hysteresis . . . . . . . . . . . . . . . . . . 5--24
Alarm 3 open in alarm . . . . . . . . . . . . . . . 5--31
Alarm 3 type . . . . . . . . . . . . . . . . . . . . . . . 5--30
Alarm hysteresis . . . . . . . . . . . . . . . . . . . . 3--10
Alarm type . . . . . . . . . . . . . . . . . . . . . . . . . . 3--9
Alarm value . . . . . . . . . . . . . . . . . . . . . . . . . 3--9
Alarm value 1 . . . . . . . . . . . . . . . . . . . . . . 5--12
Alarm value 2 . . . . . . . . . . . . . . . . . . . . . . 5--12
Alarm value 3 . . . . . . . . . . . . . . . . . . . . . . 5--12
Alfa . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--34
ASCII CODE LIST . . . . . . . . . . . . . . . . . A--20
Assignment example . . . . . . . . . . . . . . . . . 4--9
AT calculated gain . . . . . . . . . . . . . . . . . . 5--35
AT Execute/Cancel . . . . . . . . . . . . . . . . . . 5--11
AT hysteresis . . . . . . . . . . . . . . . . . . . . . . . 5--36
Auto--tuning (A.T.) . . . . . . . . . . . . . . . . . 3--16
Auto--turning key . . . . . . . . . . . . . . . . . . . 1--3















B








C








Auto/Manual . . . . . . . . . . . . . . . . . . . . . . . 4--10
Automatic return of display mode . . . . . 5--36
Auxiliary output . . . . . . . . . . . . . . . . . . . . 2--10
Auxiliary output 1 assignment . . . . . . . . 5--29
Auxiliary output 2 assignment . . . . . . . . 5--29


B group . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--11
Balance--less, Bump--less Operation . . 3--14
Balanced Status . . . . . . . . . . . . . . . . . . . . A--15
Bar graph . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--3
Basic Operation Flow . . . . . . . . . . . . . . . . . 3--2
Before setup . . . . . . . . . . . . . . . . . . . . 2--3, 2--4


Cable connections . . . . . . . . . . . . . . . . . . . . 6--3
Calibrating Current Input . . . . . . . . . . . . 7--9
Calibrating inputs . . . . . . . . . . . . . . . . . . 1--11
Calibrating Platinum
Resistance Thermometer . . . . . . . . . . . 7--7
Calibrating Thermocouple . . . . . . . . . . . . 7--4
Calibrating transfer output . . . . . . . . . . 1--11
Calibrating Voltage Input . . . . . . . . . . . . 7--10
Calibration . . . . . . . . . . . . . . . . . . . . . 7--7, 7--9
Calibration : 0 to 10V . . . . . . . . . . . . . . . . 7--11
Calibration data error . . . . . . . . . . . . . . . . 8--4
Calibration item menu . . . . . . . . . . . . . . . 7--3
Calibration Mode . . . . . . . . . 1--8, 1--9, 5--46
Calibration save mark . . . . . . . . . . . . . . . . 7--3
Calibration: 0 to 5 V, 1 to 5 V . . . . . . . . . 7--10
Calibration: thermocouple 1 . . . . . . . . . . . 7--5
Calibration: thermocouple 2 . . . . . . . . . . . 7--6
Changing the set point . . . . . . . . . . . . . . . 3--14
Characteristics . . . . . . . . . . . . . . . . . . . . . A--3
Checking Indication Accuracy . . . . . . . . 7--12
Checking Operation Restrictions . . . . . . 8--6
Close in alarm/open in alarm . . . . . . . . . 3--10
Command . . . . . . . . . . . . . . . . . . . . . . . . . A--17
Command Configuration . . . . . . . . . . . . . . 6--5
Command List . . . . . . . . . . . . . . . . . . . . . . 6--10
Commands and Responses . . . . . . . . . . . . 6--6
Communication baud rate . . . . . . . . . . . 5--40
Communication data length . . . . . . . . . . 5--40
Communication parity . . . . . . . . . . . . . . . 5--40
Communication stop bit . . . . . . . . . . . . . 5--40
Communication unit No. . . . . . . . . . . . . . 5--40
Communications . . . . . . . . . . . . . . . . . . . . 2--11
Communications parameters . . . . . . . . . . 6--4
Conditions when running a program . . 6--14
Connecting the Cold
Junction Conductor . . . . . . . . . . . . . . . 7--4
CONTROL BLOCK DIAGRAM . . . . . . . A--6

E5AK








Control output . . . . . . . . . . . . . . . . . . . . . . . 2--9








How to calculate the




INDEX














D












E












F









H

Control output 1 assignment . . . . . . . . . 5--28
Control output 2 assignment . . . . . . . . . 5--28
Control period . . . . . . . . . . . . . . . . . . . . . . . 3--7
Control period (cool) . . . . . . . . . . . . . . . . 5--16
Control period (heat) . . . . . . . . . . . . . . . . 5--16
Convention Used in this Chapter . . . . . . 3--2
Conventions Used in this Chapter . . . . . 5--2
Cooling coefficient . . . . . . . . . . . . . 4--2, 5--13
CT input/Potentiometer . . . . . . . . 1--4, 2--10
Current input . . . . . . . . . . . . . . . . . 1--4, 7--13


Dead band . . . . . . . . . . . . . . . . . . . . . 4--2, 5--14
Decimal point . . . . . . . . . . . . . . . . . . . . . . 5--27
Derivative time . . . . . . . . . . . . . . . . . . . . . 5--13
Determining the LBA detection time . . 4--16
Dimensions . . . . . . . . . . . . . . . . . . . . 2--5, A--5
Direct/Reverse operation . . . . . . . . 3--7, 5--31
Display range over . . . . . . . . . . . . . . . . . . . 8--4
Down key . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--3
Draw--out . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--2


End code . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--12
Event input . . . . . . . . . . . . . . . . . . . 1--5, 2--11
Event input assignment 1 . . . . . . . . . . . . 5--39
Event input assignment 2 . . . . . . . . . . . . 5--39
Event input assignment 3 . . . . . . . . . . . . 5--39
Event input assignment 4 . . . . . . . . . . . . 5--39
Event input assignments . . . . . . . . . . . . . . 4--8
Examples of use . . . . . . . . . . . . . . . 4--14, 6--16
Expansion Mode . . . . . . . . . . 1--7, 1--9, 5--32


Features . . . . . . . . . . . . . . . . . . . . . . . . . . A--14
Fixing Screw for Front Panel . . . . . . . . . . 2--2
Fixing settings . . . . . . . . . . . . . . . . . . . . . . . 1--9
Format . . . . . . . . . . . . . . . . . . . . . . . . . . . A--17
Front panel . . . . . . . . . . . . . . . . . . . . . . . . . 1--2
FUZZY SELF--TUNING . . . . . . . . . . . A--14
Fuzzy Self--tuning Function . . . . . . . . A--14


HBA latch . . . . . . . . . . . . . . . . . . . . . . . . . . 5--42
HBA latch/release . . . . . . . . . . . . . . . . . . . 4--13
Heater burnout . . . . . . . . . . . . . . . . . . . . . 5--17
Heater burnout detection . . . . . . . . . . . . 4--13
Heater current monitor . . . . . . . . . . . . . . 5--17
Heating and cooling control . . . . . . . . . . . 4--2
Heter Burnout Alarm . . . . . . . . . . . . . . . A--3



















I

















L











M

heater burnout set value . . . . . . . . . . 4--14
How to Read Communications
Error Information . . . . . . . . . . . . . . . . 6--12
How to Use Error Output . . . . . . . . . . . . . 8--5
How to Use Event Input . . . . . . . . . . . . . . 4--8
How to use keys . . . . . . . . . . . . . . . . . . . . . . 1--3
How to use programs . . . . . . . . . . . . . . . . 6--14
How to Use the Error Display . . . . . . . . . 8--3
How to Use the
Heater Burnout Alarm . . . . . . . . . . . . 4--13
How to Use the Remote SP . . . . . . . . . . . 4--11
How to Use Transfer Output . . . . . . . . . 4--17
Hysteresis . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--4
Hysteresis (cool) . . . . . . . . . . . . . . . . . . . . 5--15
Hysteresis (heat) . . . . . . . . . . . . . . . . . . . . 5--15


Initial Checks . . . . . . . . . . . . . . . . . . . . . . . . 8--2
Input and Output . . . . . . . . . . . . . . . . . . . . 1--4
Input digital filter . . . . . . . . . . . . . . . . . . . 5--23
Input error . . . . . . . . . . . . . . . . . . . . . 3--6, 8--3
Input errors . . . . . . . . . . . . . . . . . . . . . . . . . 8--5
Input shift . . . . . . . . . . . . . . . . . . . . . . . . . . 3--4
Input shift lower limit . . . . . . . . . . . . . . . 5--24
Input shift upper limit . . . . . . . . . . . . . . . 5--24
Input type . . . . . . . . . . . . . . . . . . . . . 3--4, 5--26
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 2--5
Integral time . . . . . . . . . . . . . . . . . . . . . . . 5--13
Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--2
Issuing special commands . . . . . . . . . . . . 6--10


LBA . . . . . . . . . . . . . . . . . . . . . . . . . . 4--15, 8--5
LBA detection example . . . . . . . . . . . . . . 4--15
LBA detection time . . . . . . . . . . . . 4--15, 5--21
LBA detection width . . . . . . . . . . 4--15, 5--36
Level 0 Mode . . . . . . . . . . . . . . 1--7, 1--8, 5--6
Level 1 Mode . . . . . . . . . . . . . 1--7, 1--8, 5--10
Level 2 Mode . . . . . . . . . . . . . 1--7, 1--8, 5--18
Limiter operation conditions . . . . . . . . . . 4--6


Main parts . . . . . . . . . . . . . . . . . . . . . . . . . . 1--2
Manipulated variable at stop . . . . 3--13, 4--2
Manipulated variable at
stop/PV error . . . . . . . . . . . . . . . . . . . . . 4--3
Manipulated variable restrictions . . . . . . 4--5
Manual Mode . . . . . . . . . . . . . . 1--7, 1--9, 5--5
Manual MV . . . . . . . . . . . . . . . . . . . . . . . . . 5--5
Manual operation . . . . . . . . . . . . . . . . . . . 3--14
Manual reset value . . . . . . . . . . . . . . . . . . 5--15


E5AK




INDEX



Memory error








. . . . . . . . . . . . . . . . . . . . . . . 8--3








Platinum resistance thermometer








. . . . 7--12

Menu display . . . . . . . . . . . . . . . . . . . . . . . . 1--8

Position--proportional control

. . . . . . . . 4--3






















N




O






















P

MODEL LIST . . . . . . . . . . . . . . . . . . . . . A--11
Monitor process value . . . . . . . . . . . . . . . 6--16
Motor Calibration . . . . . . . . . . . . . . . . . . . 5--42
Motor calibration error . . . . . . . . . . . . . . . 8--4
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--6
Multi--SP . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--9
Multi--SP function . . . . . . . . . . . . . . . . . . 5--38
MV at PV error . . . . . . . . . . . . . . . . . . . . . 5--21
MV at stop . . . . . . . . . . . . . . . . . . . . . . . . . 5--21
MV change rate limit . . . . . . . . . . . . . . . . 5--22
MV change rate limiter . . . . . . . . . . . . . . . 4--5
MV limiter . . . . . . . . . . . . . . . . . . . . . . . . . . 4--5
MV lower limit . . . . . . . . . . . . . . . . . . . . . 5--22
MV monitor (cool) . . . . . . . . . . . . . . . . . . . 5--8
MV monitor (heat) . . . . . . . . . . . . . . . . . . . 5--8
MV upper limit . . . . . . . . . . . . . . . . . . . . . 5--22


Names of parts . . . . . . . . . . . . . . . . . . . . . . 1--2
No.1 display . . . . . . . . . . . . . . . . . . . . . . . . . 1--3
No.2 display . . . . . . . . . . . . . . . . . . . . . . . . . 1--3


ON/OFF control . . . . . . . . . . . . . . . . . . . . . 4--4
Open/close hysteresis . . . . . . . . . . . . . . . . 5--23
Operating Condition Restrictions . . . . . . 4--5
Operating conditions . . . . . . . . . . 4--12, 4--13
Operation at start . . . . . . . . . . . . . . . . . . . . 4--7
Operation indicators . . . . . . . . . . . . . . . . . 1--3
Option Mode . . . . . . . . . . . . . 1--7, 1--9, 5--37
Option Unit Ratings
and Characteristics . . . . . . . . . . . . . . . A--4
Other event input functions . . . . . . . . . . 4--10
Other functions . . . . . . . . . . . . . . . . . . . . . . 4--3
Outline . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6--2
Outline of the
Communications Function . . . . . . . . . 6--2
Output assignments . . . . . . . . . . . . . 1--5, 3--6
Output Unit
Ratings and Characteristics . . . . . . . A--4


Panel cutout . . . . . . . . . . . . . . . . . . . . . . . . . 2--5
Parameter initialize . . . . . . . . . . . . . . . . . 5--27
PARAMETER OPERATIONS LIST . . A--12
Parameter types . . . . . . . . . . . . . . . . . . . . . 1--7
Parameters and Menus . . . . . . . . . . . . . . . 1--7
PID / ON/OFF . . . . . . . . . . . . . . . . . . . . . . 5--33
PID Constant Refreshing Conditions . A--15




















R



























S

Position--proportional dead band . . . . . 5--14
Position--proportional
type . . . . . . . . . . . . . . . . . . 3--7, 3--15, A--7
Power supply . . . . . . . . . . . . . . . . . . . . . . . . 2--8
Precautions when wiring . . . . . . . . . . . . . 2--8
Preparation . . . . . . . . . . . . . . 7--7, 7--9, 7--10
Preparations . . . . . . . . . . . . . . . . . . . . . . . . 7--4
Preparing for Communications . . . . . . . . 6--3
Procedure . . . . . . . . . . . . . . . . 2--3, 2--4, 6--14
Program Example . . . . . . . . . . . . . . . . . . . 6--14
Program list . . . . . . . . . . . . . . . . . . . . . . . . 6--15
Proportional band . . . . . . . . . . . . . . . . . . 5--13
Protect Mode . . . . . . . . 1--7, 1--9, 3--12, 5--3
PV dead band . . . . . . . . . . . . . . . . . . . . . . . 5--43
PV/SP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--6


Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . A--2
Reading parameters . . . . . . . . . . . . . . . . . . 6--6
Reading/writing parameters . . . . . . . . . . . 6--6
Registering calibration data . . . . . . . . . . 1--11
Relationship with set point limiter . . . . 4--11
Remote SP enable . . . . . . . . . . . . . . . . . . . 5--44
Remote SP input . . . . . . . . . . . . . . . 1--4, 2--10
Remote SP input error . . . . . . . . . . . . . . . 8--5
Remote SP lower limit . . . . . . . . . . . . . . . 5--44
Remote SP monitor . . . . . . . . . . . . 4--12, 5--7
Remote SP upper limit . . . . . . . . . . . . . . 5--44
Remote/Local . . . . . . . . . . . . . . . . . 4--10, 5--19
Response . . . . . . . . . . . . . . . . . . . . . . . . . . A--17
Restrictions during SP ramp . . . . . . . . . . 4--7
RS--232C . . . . . . . . . . . . . . . . . . . . . 1--10, 6--3
RS--422 . . . . . . . . . . . . . . . . . . . . . . . 1--10, 6--3
RS--485 . . . . . . . . . . . . . . . . . . . . . . . 1--10, 6--4
RSP input error . . . . . . . . . . . . . . . . . . . . . 3--6
Run/Stop . . . . . . . . . . . . . . . . . . . . . . 4--10, 5--9
RX (process value read)
command status . . . . . . . . . . . . . . . . . A--19


Scaling . . . . . . . . . . . . . . . . . . . . . . . . 3--4, 4--11
Scaling lower limit . . . . . . . . . . . . . . . . . . 5--27
Scaling upper limit . . . . . . . . . . . . . . . . . . 5--27
Security . . . . . . . . . . . . . . . . . . . . . . . 3--12, 5--3
Selecting modes . . . . . . . . . . . . . . . . . . . . . . 1--8
Selecting parameters . . . . . . . . . . . . . . . . . 1--9
Selecting the Control Method . . . . . . . . . . 4--2
Sensor input . . . . . . . . . . . . . . . . . . . . . . . . . 2--9
Set point 0 . . . . . . . . . . . . . . . . . . . . . . . . . 5--11
Set point 1 . . . . . . . . . . . . . . . . . . . . . . . . . 5--11


E5AK




INDEX




Set point 2
Set point 3




. . . . . . . . . . . . . . . . . . . . . . . . . 5--11
. . . . . . . . . . . . . . . . . . . . . . . . . 5--11




Startup Conditions of DT . . . . . . . . . . . A--16
Startup Conditions of HT . . . . . . . . . . . A--16

Set point during SP ramp . . . . . . . . . . . . . 5--8
Set point limiter . . . . . . . . . . . . . . . . . . . . . 4--6

Startup Conditions of SRT . . . . . . . . . . A--14
Structure of Parameters . . . . . . . . . . . . . . 7--2

Set point lower limit

. . . . . . . . . . . . . . . . 5--33

Summary of alarm operations . . . . . . . . 3--10

Set point upper limit . . . . . . . . . . . . . . . . 5--33
Set the set point to “300.0” . . . . . . . . . . . 6--16
Set the unit No. to “00” . . . . . . . . . . . . . . 6--16
Setting Alarm Type . . . . . . . . . . . . . . . . . . 3--9
Setting Input Specifications . . . . . . . . . . . 3--4
SETTING LIST . . . . . . . . . . . . . . . . . . . . A--8
Setting Output Specifications . . . . . . . . . 3--6
Setting the
communications specifications . . . . . . 6--4
Setting the LBA detection time . . . . . . . 4--16
Setting up . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--2
Setting up the option unit . . . . . . . . . . . . . 2--4
Setting up the output unit . . . . . . . . . . . . 2--3
Setting up the terminal covers . . . . . . . . . 2--7
Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3--3
Setup Mode . . . . . . . . . . . . . . 1--7, 1--9, 5--25
SP mode . . . . . . . . . . . . . . . 4--10, 4--11, 5--19
SP ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4--6
SP ramp set value . . . . . . . . . . . . . . . . . . . 5--20
SP ramp time unit . . . . . . . . . . . . . . . . . . 5--20
SP tracking . . . . . . . . . . . . . . . . . . . . . . . . 4--12
SP tracking enable . . . . . . . . . . . . . . . . . . 5--45
SPECIFICATIONS . . . . . . . . . . . . . . . . . . A--2
Specifications . . . . . . . . . . . . . . . . . . . . . . . A--5


T
















U




V

Switching with Manual operation . . . . . . 4--2


Temperature input . . . . . . . . . . . . . . . . . . . 1--4
Terminal arrangement . . . . . . . . . . . . . . . 2--8
The meaning of
icons used in this chapter . . . . . . . . . . 5--2
Thermocouple . . . . . . . . . . . . . . . . . . . . . . 7--12
Transfer output . . . . . . . . . . . . . . . . 1--6, 2--11
Transfer output lower limit . . . . . . . . . . 5--41
Transfer output scaling . . . . . . . . . . . . . . 4--17
Transfer output type . . . . . . . . . . 4--17, 5--41
Transfer output upper limit . . . . . . . . . . 5--41
Transfer procedure . . . . . . . . . . . . . . . . . . . 6--2
Travel Time . . . . . . . . . . . . . . . . . . . 4--3, 5--43


Undefined error . . . . . . . . . . . . . . . . . . . . 6--13
Up key . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1--3
Using Event Input . . . . . . . . . . . . . . . . . . 3--13


Valve opening monitor . . . . . . . . . . . 4--3, 5--9
Voltage input . . . . . . . . . . . . . . . . . . 1--4, 7--13

ST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5--34
ST stable range . . . . . . . . . . . . . . . . . . . . . 5--34
Stable Temperature Status . . . . . . . . . . A--15
Standard type . . . . . . . . . . . . 3--6, 3--14, A--6
Standby sequence . . . . . . . . . . . . . . . . . . . 3--10
Standby sequence reset method . . . . . . . 5--35
Start running . . . . . . . . . . . . . . . . . . . . . . . 6--16
Starting and Stopping Operation . . . . . 3--13

W




X


Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2--8
Wiring Terminals . . . . . . . . . . . . . . . . . . . . 2--8
Writing parameters . . . . . . . . . . . . . . . . . . 6--6


X FORMAT . . . . . . . . . . . . . . . . . . . . . . . A--17
X FORMAT HEAD LIST . . . . . . . . . . . A--18


E5AK








Revision History


A manual revision code appears as a suffix to the catalog number on the front cover of the manual.


Cat. No. H083-E1-02A


Revision code



The following table outlines the changes made to the manual during each revision. Page numbers refer
to previous version.

Revision code
1

Date
July 1996



Original production

Revised content



2



April 1997

Page 1- 7: Modified the diagram of mode.
Page 2- 6: Modified the power specifications in “Terminal arrange-
ment”.
Page V: Changed “100 to 240 VAC” to AC100- 240V or AC/DC24V
Page 1- 6: Modified the item of “Model” on the table.
Page 2- 8: Modified the diagram in “Terminal arrangement”.
Changed the Power specifications in “Power supply”.
Page 3- 3: Modified the diagram in “Setup”.
Page 3- 8: Added “run/stop”= “run” to Setting Example.
Page 5- 8: Added “Model” and “Power specifications” to MV monitor.
Page 5- 9: Added “Model” and “Power specifications” to Valve opening mon-
itor.
Page 5- 13: Added “Model” and “Power specifications” to Cooling coefficient.
Page 5- 14: Added “Model” and “Power specifications” to Dead band and
Position- proportional dead band.
Page 5- 15: Added “Model” and “Power specifications” to Manual reset value
and Hysteresis.
Page 5- 16: Added “Model” and “Power specifications” to Control period.
Page 5- 17: Added “Model” and “Power specifications” to Heater current
monitor and Heater burnout.
Page 5- 23: Added “Model” and “Power specifications” to Open/close hyster-
esis.
Page 5- 28: Added “Model” and “Power specifications” to Control output as-
signment.
Page 5- 33: Added “Model” and “Power specifications” to PID/ON/OFF.
Page 5- 42: Added “Model” and “Power specifications” to HBA latch.
Added “Model” and “Power specifications” to Motor Calibration.
Page 5- 43: Added “Model” and “Power specifications” to Travel Time.
Added “Model” and “Power specifications” to PV dead band.
Page 6- 3: Modified the diagram in “RS- 232C”.
Page 7- 4: Modified the diagram in “Preparations”.
Page 7- 7: Modified the diagram in “Preparation”.
Page 7- 9: Modified the diagram in “Preparation”.
Page 7- 10: Modified the diagram in “Preparation”.
Page 7- 12: Modified the diagram in “Thermocouple” and “Platinum resis-
tance thermometer”.
Page 7- 13: Modified the diagram in “Current input” and “Voltage input”.
Page 8- 4: Added “Motor calibration error”.
Page A- 2: Modified “Ratings specifications”.
Page A- 11: Changed “Type Name” and “Specification” in “Base unit”.
Page A- 14: Deleted 2) of “At the time the E5AK starts operation” in “Startup
Conditions of SRT”.
Deleted 2) of “At the time set point is changed”.
Page A- 15: Deleted “Imposition Completion Condition of Step Control
Amount”.
Modified the diagram in “PID Constant Refreshing Conditions”.

02A

December 2003 Page 2- 9: Modified the diagram in “Control output”.
Page 4- 8: Changed the title from ”Input assignments” to ”Event input as-
signments and deleted the flowchart below.
Page 4- 9: Modified the table contents for “Event input” and added a note
below the table.
Page 5- 3: Modified the tabel.
Page A- 8: Changed the unit from “%” to “%FS” for Alram 1 hysteresis,
Alarm 2 hysteresis, and Alarm 3 hysteresis.






OMRON ELECTRONICS LLC
1 Commerce Drive
Schaumburg, IL 60173
847.843.7900
For US technical support or
other inquiries: 800.556.6766

OMRON CANADA, INC.
885 Milner Avenue
Toronto, Ontario M1B 5V8
416.286.6465

OMRON ON-LINE
Global - http://www.omron.com
USA - http://www.omron.com/oei
Canada - http://www.omron.ca







































H083-E1-02A 5/04







































©2004 OMRON ELECTRONICS LLC Specifications subject to change without notice.
Printed in the U.S.A.

Tidak ada komentar:

Posting Komentar

terimakasih atas kunjungan anda di blog ini | add my facebook @nurdiansyahusm